W23-X1A1G-1 TE Connectivity, W23-X1A1G-1 Datasheet

no-image

W23-X1A1G-1

Manufacturer Part Number
W23-X1A1G-1
Description
CIRCUIT BREAKER, THERMAL, 1P, 250V, 1A
Manufacturer
TE Connectivity
Series
W23r
Type
Thermalr
Datasheet

Specifications of W23-X1A1G-1

Voltage Rating Vdc
50V
Voltage Rating Vac
250V
Current Rating
1A
No. Of Poles
1
Mounting Type
Screw
Voltage Ac
250V
Rohs Compliant
Yes
Actuator Type
Push/Pull
Brand/series
W23 Series
Color
Black with White Amp Rate Marking and White Trip Band (Button)
Current, Rating
1 A
Dimensions
2.035"Lx0.69"Wx1.384"H
Mounting Hole Size
0.375 "
Number Of Poles
1
Standards
UL Recognized, CSA Certified
Termination
Screw
Time, Trip
11 to 30 Sec
Tyco Part Number
6-1393246-4
Voltage, Rating
250/50 VAC/VDC
Lead Free Status / Rohs Status
RoHS Compliant part

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
W23-X1A1G-15
Manufacturer:
TE
Quantity:
1
116
Dimensions are shown for
reference purposes only.
Features
• 0.5 amp to 50 amp ratings may be used as on/off switch.
• Cannot be reset against overload.
• W23 has visible trip indicator.
• Screw termination.
• Trip-free operation.
Agency Approvals
W23 and W31 are UL 1077 Recognized as Supplementary Protectors.
File E69543, and CSA Certified as Appliance Component Protectors,
File LR15734.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Electrical Data @ +25°C
Calibration: Will continuously carry 100% of rating, may trip between
Maximum Operating Voltages: 50VDC or 250VAC (to 400 Hz).
Interrupting Capacity:
Resettable Overload Capacity: Ten times rated current.
Dielectric Strength: Over 1,500 volts RMS.
Time Vs. Current Trip Curve @ +25°C
With 4X Max. Series Fuse Protection
Without 4X Max. Series Fuse Protection
0.5-50 amp models — 1000 amps at 240VAC.
30-50 amp models — 1000 amps at 50VDC.
0.5-25 amp models — 2000 amps at 50VDC.
10-20 amp models — 2000 amps at 120VAC.
1000
900
800
700
600
500
400
300
200
100
0
.1
101% and 134% of rating at 25°C. Must trip at 135% in
one hour.
W23
(A)
1
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Time In Seconds
10
(B)
(A) All 5-50 Amp Models
Overload
1000%
W31
100%
135%
200%
400%
600%
800%
Trip in 1 hour
0.45-1.5 Sec.
0.25-0.6 Sec.
1.0-3.0 Sec.
0.3-0.8 Sec.
Trip Times
6.0-22 Sec.
No Trip
Catalog 1308242
Issued 3-03
100
(B) All 0.5-4 Amp Models
Overload
1000%
100%
135%
200%
400%
600%
800%
Specifications and availability
subject to change.
Maximum Resistance vs. Current Rating @ +25°C
W23/W31
Toggle or
Push/Pull Actuator
Thermal Circuit Breaker
Mechanical/Environmental Data
Endurance Cycling: More than 6,000 cycles at 100% of rating, or 10,000
Humidity: Will meet requirements of MIL -STD-202, Method 106.
Salt Spray: Will meet requirements of MIL-STD-202, Method 101, Test
Termination: Two #8-32 screw terminals.
Mounting: W23 — Threaded bushing, 3/8” (9.53mm) diameter.
Weight: Less than 2 oz. (57g).
Trip in 1 hour
2.0-8.0 Sec.
1.0-5.5 Sec.
0.6-4.0 Sec.
0.4-2.5 Sec.
Trip Times
11-30 Sec.
No Trip
1000
W31 — Threaded bushing, 15/32” (11.91mm) diameter, with or
without anti-rotation flats.
Condition B.
in Amps
Current
Rating
15
20
30
40
50
10
1
5
mechanical cycles.
Ambient Compensation Chart
To use this chart: Read up from the ambient
temperature to the curve, and across to find a correction
factor. Multiply the breaker rating by the correction factor
to determine the compensated rating. Calculate the
overloads in terms of the compensated rating to use the
published trip curve.
1.40
1.30
1.20
1.10
1.00
0.90
0.80
0.70
0.60
Ambient Temperature In Degrees Centigrade (°C)
series
–20 –10 0
10 20 30 40 50 60
in Ohms ± 30%
Resistance
Maximum
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
.61
.03
.01
.006
.004
.003
.002
.002
P&B

Related parts for W23-X1A1G-1

W23-X1A1G-1 Summary of contents

Page 1

... W23 has visible trip indicator. • Screw termination. • Trip-free operation. Agency Approvals W23 and W31 are UL 1077 Recognized as Supplementary Protectors. File E69543, and CSA Certified as Appliance Component Protectors, File LR15734. Users should thoroughly review the technical data before selecting a product part number ...

Page 2

... Stock Items – Authorized distributors are more likely to stock the following items. W23-X1A1G-1 W23-X1A1G-7 .50 W23-X1A1G-25 W23-X1A1G-2 W23-X1A1G-10 W23-X1A1G-30 W23-X1A1G-3 W23-X1A1G-15 W23-X1A1G-35 W23-X1A1G-5 W23-X1A1G-20 W23-X1A1G-40 Ordering Information Typical Part No. 1. Designator Circuit breaker 2. Series Number Single pole, toggle actuator 3. Circuit Function Series trip 4. Mounting Bushing 15/32” ...

Page 3

... W23 Outline Dimensions Terminal Style 1 RESET BUTTON IN “ON” POSITION WHITE INDICATOR NOT VISIBLE .690 (17.53) AMP RATING 1.384 .315 Dia. 5 (35.15) (8.00) Mounting Hardware Hex Nut (55-001D - Silver Color) .085 .545 – .567 (2.16) (13.84 – 14.40) W31 Outline Dimensions Terminal Style 1 ...

Related keywords