E2E-X2Y1-US Omron, E2E-X2Y1-US Datasheet

Proximity Sensors Proximity Sensor

E2E-X2Y1-US

Manufacturer Part Number
E2E-X2Y1-US
Description
Proximity Sensors Proximity Sensor
Manufacturer
Omron
Series
E2Er
Type
Inductive Proximity Sensorr
Datasheets

Specifications of E2E-X2Y1-US

Proximity Sensor Type
Inductive
Proximity Sensor Sensing Distance
2mm
Proximity Sensor Sensing Distance Range
2 to 7mm
Proximity Sensor Switching Mode
NO
Ac Supply Voltage
20 to 264VAC
Mounting
Panel
Operating Temp Range
-40C to 85C
Operating Temperature Classification
Industrial
Pin Count
2
Maximum Operating Temperature
+ 85 C
Supply Voltage
30 V
Operating Supply Voltage
24 VAC to 240 VAC
Sensing Distance
2 mm
Minimum Operating Temperature
- 40 C
Maximum Output Current
200 mA
Features
High visibility indicator
Sensor Type
Inductive
Sensing Object
Metallic
Response Frequency
25Hz
Material - Body
Nickel-Plated Brass
Shielding
Shielded
Voltage - Supply
20 VAC ~ 264 VAC
Output Type
SCR-NO
Terminal Type
2-Wire
Package / Case
Cylinder, Threaded - M12
Lead Free Status / Rohs Status
Supplier Unconfirmed
Short Barrel 2-Wire AC Prox Sensors
Meet IP67
H
H
H
H
Ordering Information
J PREWIRED SENSORS WITHOUT SHORT-CIRCUIT PROTECTION
* N ot e: A diff er ent os c illat ing f r equenc y is av ailable t o pr ev ent mut ual int er f er enc e. A dd a “ 5” t o t he par t number ( e. g. , E 2E - X 5Y 15- U S ) .
Type
Shielded
Unshielded
Short Barrel Inductive Prox
yp
Thick nickel-plated brass barrel has wrench
flats for easy installation
Solid potted internal circuitry withstands
shocks and water washdown to IP67
High visibility indicator
Choose prewired models with or without
short-circuit protection and connector
models
Size
M8
M12
M18
M30
M8
M12
M18
M30
Sensing distance
1.5 mm
2 mm
2 mm
5 mm
5 mm
R
g
18 mm
10 mm
10 mm
Part number
NO
E2E -X1R 5Y1
E2E -X2Y1 -U S
E2E -X5Y1 -U S
E2E -X10Y1 -U S
E2E -X2MY1 -U S
E2E -X5MY1 -U S
E2E -X10MY1 -U S
E2E -X18MY1 -U S
2
NC
E2E -X1R 5Y2
E2E -X2Y2 -U S
E2E -X5Y2 -U S
E2E -X10Y2 -U S
E2E -X2MY2 -U S
E2E -X5MY2 -U S
E2E -X10MY2 -U S
E2E -X18MY2 -U S
E2E 2-WIRE AC

Related parts for E2E-X2Y1-US

E2E-X2Y1-US Summary of contents

Page 1

... E2E -X5Y1 -U S E2E -X10Y1 -U S E2E -X2MY1 -U S E2E -X5MY1 -U S E2E -X10MY1 -U S E2E -X18MY1 - E2E 2-WIRE AC NC E2E -X1R 5Y2 E2E -X2Y2 -U S E2E -X5Y2 -U S E2E -X10Y2 -U S E2E -X2MY2 -U S E2E -X5MY2 -U S E2E -X10MY2 -U S E2E -X18MY2 -U S ...

Page 2

... Fits M30 size sensors See Y96E Connector Cordsets data sheet for details 3 E2E 2-WIRE AC NC E2E-X5Y2-53-US E2E-X10Y2-53-US E2E-X10MY2-53-US E2E-X18MY2-53-US NC E2E -X2Y2 -M1 E2E -X5Y2 -M1 E2E -X10Y2 -M1 E2E -X5MY2 -M1 E2E -X10MY2 -M1 E2E -X18MY2 -M1 E2E-X2Y2-M4 E2E-X5Y2-M4 E2E-X10Y2-M4 E2E-X5MY2-M4 E2E-X10MY2-M4 E2E-X18MY2-M4 Part number Y92E-B8 Y92E-B12 Y92E-B18 ...

Page 3

... NEMA 12, 13 Note: 1. When using an M18 or M30 size E2E at an ambient temperature between 70°C and 85°C (158°F and 185°F), make sure that the E2E has a control output of 200 mA maximum. 2. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is - -25°C to 85°C (- -13° ...

Page 4

... Weight g Prewired Approx Connector --- Approx Material Body Stainless steel Sensing PBT face J SENSORS WITH SHORT-CIRCUIT PROTECTION (E2E- -53-US) Part number E2E-X5Yj-53-US Body y Size M18 Type Shielded Supply voltage 90 to 140 VAC, 50/60 Hz Effective maximum detecting distance 5 mm (0.20 in) ±10% (with standard target) ...

Page 5

... E2E 2-WIRE AC Operation J OUTPUT CIRCUITS Sensors without Short-Circuit Protection (E2E-XjYj) E2E - -wire Models Brown 1 (or 3) Load Main circuit Blue 2 (or 4) Sensors with Short-Circuit Protection (E2E-XjYj-US-53) Prox. switch main circuit Note: IEC colors are shown in parenthesis With Short-Circuit Protection E2E-XjY1-53 NO Load Shorted ...

Page 6

... E2E 2-WIRE AC Engineering Data J OPERATING RANGE (TYPICAL) Shielded Models E2E -XjYj E2Ej-X2j E2Ej-X1R5j Y (mm) Unshielded Models E2E -XjMY j E2Ej-X5Mj E2Ej-X2Mj Y (mm) J LEAKAGE CURRENT (TYPICAL) E2E -XjYj Proximity Protective Sensor resistance (when OFF) AC power supply Supply voltage (V) E2Ej- -X10j E2Ej- -X5j Y (mm) ...

Page 7

... E2E 2-WIRE AC RESIDUAL OUTPUT VOLTAGE (TYPICAL) J E2E -XjYj Residual output voltage Proximity Sensor 24 VAC Residual load volt- age Load current (mA) J SENSING DISTANCE VS. SENSING OBJECT (TYPICAL) E2E -X1R 5Yj Mild steel Stainless steel (SUS304) Brass Aluminum Side length of target d (mm) E2E -X10Yj ...

Page 8

... E2E 2-WIRE AC J SENSING DISTANCE VS. SENSING OBJECT (TYPICAL CONTINUED E2E -X10MY Mild steel Stainless steel (SUS304) Brass Aluminum Side length of target d (mm) Models with Short Circuit Protection (E2E-XjYj-53-US) E2E-X5jj, E2E-X10jj Size of target d [mm (inch)] E2E -X18MYj Mild steel Stainless steel (SUS304) Brass Aluminum ...

Page 9

... M30 E2E-X18MYj M18 E2E-X5Yj-53-US M30 E2E-X10Yj-53-US M18 E2E-X10MYj-53-US M30 E2E-X18MYj-53-US M12 E2E-X2Y-j-M1 M18 E2E-X5Y1-M1 M30 E2E-X10Y- j-M1 M12 E2E-X5MY-j-M1 M18 E2E-X10MY- j-M1 M30 E2E-X18MY- j-M1 M12 E2E-X2Y-j-M4 M18 E2E-X5Y-j-M4 M30 E2E-X10Y-j-M4 M12 E2E-X5MY-j-M4 M18 E2E-X10MY-j-M4 M30 E2E-X18MY-j-M4 10 E2E 2-WIRE AC Figure number ...

Page 10

... 18MY j 42 dia. (1.65) 26.8 dia. Round vinyl-insulated Cable 6 dia. (0.12 dia. x 45), 2/3 cores 6 dia. (0.08 dia. x 6/17) robotics cable models Standard length E2E 2-WIRE AC E2E -X2MYj 40 (1.57) 36 (1.42) Operation indicator Two clamping Round vinyl-insulated cable nut 4 dia. (0.08 dia. x 60), 2 cores ...

Page 11

... Fig (1.417) across flats Indicator 30.5 dia Cable: (1.201) 6 (0.24) dia (6.56 ft) Connector Models (Unshielded) Fig. 14: E2E -X5MYj - dia. (0.83) 38 (1.50) 7 (0.28) 9 dia. M12 x 1 Fig. 16: E2E -X10MYj - dia. (1.14) 10 M12 x 1 (0.39) 14.8 dia. 12 E2E 2-WIRE AC E2E-X10MYj-53-US M18 P=1 ...

Page 12

... M30 x 1.5 Two clamping nut Toothed washer J MOUNTING HOLES F Dimensions M8 +0.5 F (mm) 8.5 / dia. 0 Installation J PIN ARRANGEMENT E2E-XjYj-M1 AC 2-wire Models Output Applicable models configuration NO E2E-XjY1-M1 NC E2E-XjY2-M1 NO, NC E2E-XjYj-M4 Connector Models (Unshielded), continued 18: 42 dia. (1.65) M12 x 1 Operation indicator M12 M18 +0 ...

Page 13

... B applies. If this nut is in part A, the tightening torque for part A applies instead. J EFFECTS OF SURROUNDING METAL When mounting the E2E within a metal panel, ensure that the clearances given in the following table are maintained. Failure to maintain these distances may cause deterioration in the performance of the sensor. Type ...

Page 14

... E2E 2-WIRE AC J MUTUAL INTERFERENCE When installing two or more Sensors face-to-face or side-by-side, ensure that the minimum distances given in the following table are main- tained Type Dimension E2E-XjYj Shielded 2-wire B Unshielded A B Note: The figures in parentheses refer to Sensors operating at different frequencies. J INSTALLATION ...

Page 15

... Correct voltage, the load will not operate. Load A maximum of three Proximity Sensors can be connected in series provided that the supply voltage is 100 V minimum. Load V ≧ 100 E2E 2-WIRE AC VAC power supply V S (i.e., the voltage imposed on the is lower than the load operating L ...

Page 16

... To prevent the instantaneous resetting of the load, use a relay as shown on the left. OMRON ON- -LINE Global -- http://www.omron.com USA -- http://www.omron.com/oei Canada -- http://www.omron.com/oci Specifications subject to change without notice. E2E 2-WIRE AC OMRON CANADA, INC. 885 Milner Avenue Scarborough, Ontario M1B 5V8 416-286-6465 Printed in U.S.A. ...

Related keywords