... Note: 1. When ordering, add the rated coil voltage to the model number. Rated coil voltages are given in the coil ratings table. Example: LY2, 6 VAC 2. Relays with #187 quick connect terminals are also available with SPDT and DPDT contact. Ask your OMRON representative for details. ...
Page 2
... PT11 PTP-1-3 PT11QN PT14 PTP-1 PT14QN Socket-Hold-down Clip Pairings Relay type Poles Standard, bifurcated 1, 2 contacts operation 3 indicator, built-in diode 4 CR Circuit 2 Specifications Coil Rating ■ Single- and Double-pole Relays Rated voltage Rated current 214.1 mA 183 106 53 25 100/110 V 11.7/12.9 mA 10/11 mA 110/120 V 9.9/10.8 mA 8.4/9.2 mA 4,430 Ω ...
Page 3
... 100/110 V 14.1/16 mA 12.4/13.7 mA 2,300 Ω 200/220 V 9.0/10.0 mA 7.7/8 234 112 58 28.2 mA 100/110 V 12.7/13 mA Note: See notes under next table. Four-pole Relays Rated voltage Rated current 386 mA 330 199 mA 170 93 46 100/110 V 22.5/25.5 mA 19/21.8 mA 1,600 Ω 200/220 V 11.5/13.1 mA 9.8/11.2 mA 6,700 Ω ...
Page 4
... Operating 85% Weight Single- and double-pole: approx three-pole: approx four-pole: approx Note: 1. The values given above are initial values 2. The upper limit of 40°C for some Relays is because of the relationship between diode junction temperature and the element used. Single Contact 2 4-pole Resistive load Inductive load (cosϕ ...
Page 5
General Purpose Relay – LY Endurance Under Real Loads (reference only) ■ LY1 Rated voltage Load type 100 VAC AC motor AC lamp Capacitor (2,000 µF) AC solenoid LY2 Rated voltage Load type 100 VAC AC motor AC lamp Capacitor ...
Page 6
General Purpose Relay – LY Approved Standards ■ UL 508 Recognitions (File No. 41643) No. of poles 240 VAC 6 to 125 VDC 2 3 and 4 CSA 22.2 No. 14 Listings (File No. LR31928) No. of ...
Page 7
General Purpose Relay – LY Approved Standards (cont.) ■ LR Recognitions (No. 563KOB-204523) No. of poles 240 VAC 6 to 110 VDC Engineering Data LY1 Maximum Switching Power (cosφ = 0.4) 1 ...
Page 8
... DC resistive load 1 0 Life: 500,000 operations 10 50 100 Switching voltage (V) Dimensions Note: All units are in millimetres unless otherwise indicated. Relays with Solder/Plug-in Terminals ■ LY1 LY1N (-D2) LY1-D Eight, 2-dia. holes 3 36 max. 6.4 Note: The DC models have polarity. AC resistive load AC (cosφ ...
Page 9
General Purpose Relay – LY LY2 LY2Z LY2-D LY2Z-D LY2N LY2ZN LY2N-D2 LY2ZN-D2 Eight, 3-dia. holes 3 36 max. 6.4 LY2(Z)N DC Model Note: The DC models have polarity. LY3 LY3N LY3-D 36.5 max. 6.4 LY3 Note: The DC models ...
Page 10
... LY2-CR LY2Z-CR LY2N-CR LY2ZN-CR 0.5 Eight, 3-dia. holes max. 6.4 Model: LY2N-CR Relays with PCB Terminals ■ LY1-0 LY3-0 LY2-0 LY4-0 0 max. 4.5 (see note 2) Note: 1. The above model is the LY2-0. 2. This figure is 6.4 for the LY1-0 Terminal Arrangement/Internal Connections 0.5 28 max ...
Page 11
... General Purpose Relay – LY Upper Mounting relays ■ LY1F LY2F 2 35.5 max. Note: 1. Eight 3-dia. holes should apply to the LY2F model. LY3F 2 36 max. LY4F 2 35.5 max. 452 22.5 max. 0.5 44 max max Eight, 2-dia. holes (see note) 6.4 3.5 32 max. ...
Page 12
General Purpose Relay – LY Mounting Height with Socket ■ The following Socket heights should be maintained. Back-connecting Front-connecting LY 40 (57) 67 (84) 71 (see note) PTF@A (-E) Sockets ■ PTF08A-E PTF11A PTF14A-E PT14QN PT11QN Mounting Plates for Back-connecting ...
Page 13
... General Purpose Relay – LY Hold-down Clips ■ Hold-down clips are used to hold Relays to Sockets and prevent them from coming loose due to vibration or shock. Used with Socket PYC-A1 PYC-P Precautions Connections ■ Do not reverse polarity when connecting DC-operated Relays with built-in diodes or indicators. ...
Page 14
... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...