61F-HSL AC115 Omron, 61F-HSL AC115 Datasheet

no-image

61F-HSL AC115

Manufacturer Part Number
61F-HSL AC115
Description
Controllers LEVEL CONTROL
Manufacturer
Omron
Datasheets

Specifications of 61F-HSL AC115

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Ideal for Detecting Ice, Pure Water, or
Humidity
• Applicable for detecting ice, pure water steam, humidity, or other
• Two types of model available: Ultra high-sensitivity and variable
■ Ordering Information
Note: When ordering, specify the desired operating voltage at the end of the model number.
■ Ultra High-sensitivity Models
Use these models for sensing objects such as ice, high-purity distilled water, moisture, or other objects with low electrical conductivity.
Specifications
Note: 1. Use 61F-UHS for detecting water leakage with high specific resistance. Connect a sensor cable between terminals 1 and 7.
Ultra high-
sensitivity
Supply voltage
Operating voltage range
Interelectrode voltage
Interelectrode current
Power consumption
Interelectrode operate resistance
Interelectrode release resistance
Cable length
Control output
Ambient temperature
Ambient humidity
Insulation resistance
Dielectric strength
Life expectancy
Weight
substances that conduct electricity poorly.
ultra high-sensitivity.
Floatless Level Switch (Ultra High-sensitivity Type)
61F-UHS/-HSL
Type
Example: 61F-UHS [220VAC]
2. Two Electrodes can be connected to the 61F-HSL. Use them for an alarm, not for creating a self-holding circuit.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm
4. It is recommended that the cable length be kept as short as possible since the Electrode circuit current is at DC micro-current level. More-
Refer to Safety Precautions for Floatless Level
Controllers.
the cable diameter or number of conductors becomes larger. For more details, refer to Safety Precautions for Floatless Level Controllers.
over, the Electrodes will corrode rapidly if the current is allowed to constantly flow between the Electrodes.
Be careful with the electrode polarity and grounding when wiring.
61F-UHS
Ultra high-sensitivity
Item
Model
Desired supply voltage
100, 200, or 220 VAC; 50/60 Hz
85% to 110% of rated voltage
24 VAC
Approx. 1 mA AC max.
3.2 VA max.
0 to approx. 1 MΩ (see note 1)
Approx. 5 M to ∞ Ω
5 m (see note 2)
0.3 A, 220 VAC (Inductive load: cosφ = 0.4)
1 A, 220 VAC (Resistive load)
Operating:–10 to 55°C
Operating:45% to 85% RH
100 MΩ max. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min
Electrical:
Mechanical: 5,000,000 operations min.
Approx. 210 g
61F-HSL
Variable ultra high-
sensitivity
High-sensitivity 61F-UHS
Model
50,000 operations min.
2
) cabtire cables. Usable cable lengths will become shorter as
24, 100, 110, 200, or 220 VAC; 50/60 Hz
13 VDC max.
Approx. 1 mA DC max.
0 to approx. 5 MΩ (variable)
Operate resistance + 2.5 MΩ max.
(see note 3)
2 A, 220 VAC (Inductive load: cosφ = 0.4)
5 A, 220 VAC (Resistive load)
Electrical:
Mechanical: 5,000,000 operations min.
Variable high-sensitivity 61F-HSL
500,000 operations min.
CSM_61F-UHS_-HSL_DS_E_2_2
1

61F-HSL AC115 Summary of contents

Page 1

... Weight Approx. 210 g Note: 1. Use 61F-UHS for detecting water leakage with high specific resistance. Connect a sensor cable between terminals 1 and 7. 2. Two Electrodes can be connected to the 61F-HSL. Use them for an alarm, not for creating a self-holding circuit. 3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm the cable diameter or number of conductors becomes larger ...

Page 2

... External Circuit Diagrams (Example) 61F-UHS Power 4 5 source Socket: 8PFA1 (track mounted)/ PL08 (back connecting) 61F-HSL each circuit Power supply Relay Relay Ground X 61F-HSL Power 4 5 source (+) (-) Socket: 8PFA (track mounted)/ PL08 (back connecting) 61F-UHS/-HSL Relay To each circuit Relay 2 ...

Page 3

... PL08 (Read-connecting) Connect terminal 3 to the contactor coil terminal. Principles of Operation Pump OFF • When the water level reaches E when the water level reaches E stops. 61F-UHS/-HSL Ultra High-sensitivity Type Dimensions: Page 4 Automatic Drainage Control 61F-UHS Control circuit 24 V Power U ...

Page 4

... PF2 parallel thread (effective dia.: 58.135) 9-dia. rubber bushing (inner) Note: The PS-3SR, PS-4SR, and PS-5SR have built-in resistor of 6.8 kΩ and used for the two-wire 61F models. PS-31 Weight: approx. 325 g Electrode SUS304 F03-31 Dust-preventive rubber cap (optional) Note: Standard holder construction includes three integral Weight: approx ...

Page 5

... Width across flats: 20 Terminal bolt M18 Two, M4 P=0.7 SUS304 (M4) P=0.7 P=1.5 24 dia 101 61F-UHS/-HSL Two, M5 × 25 mounting screws Mounting Holes 26-dia. 48 hole Two, 6-dia. holes Mounting Holes 64-dia. hole 1 120° Two, 6-dia. holes Mounting Holes Two, 6-dia. hole ...

Page 6

... F03-14 3P for three poles Three, 7 dia Weight: Approx 3-core 61F-UHS/-HSL Mounting Holes 24 dia. M18 P=1.5 (fine screw thread) *This nut is made of Teflon **A connecting nut made of Hastelloy B, Hastelloy C, or titanium is not supplied with two M4 screws and thus has no holes for such screws. ...

Page 7

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...