LSZ4001FP Honeywell, LSZ4001FP Datasheet

no-image

LSZ4001FP

Manufacturer Part Number
LSZ4001FP
Description
Switch Hardware Plug in Base Recpt. Limit Switch
Manufacturer
Honeywell
Datasheet

Specifications of LSZ4001FP

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Installation Instructions for the
HDLS Series Switches
MOUNTING
All Heavy Duty Limit Switches (HDLS) have exactly the
same mounting dimensions. Mount by either of two
methods: (a) use two #10 screws from the front, or (b)
use two #10-32 UNF screws from the back. HDLS offers
the advantage of front mount construction. The
electrician will find a complete switch, with no parts
missing and ample wiring space.
With plug-in construction, wiring and conduit connection
is made to the base receptacle. This feature also
reduces downtime, since plug-in unit can be removed
without disconnecting wiring or conduit.
To mount either switch, merely tighten mounting screws,
tighten plug-in unit or cover screws, and make sure
conduit section is sealed. Use of sealant (teflon tape,
pipe dope, etc.) is recommended to seal conduit
connection.
Because of moisture condensation problems, it is not
good practice to mount the switch upside down or at the
low point of conduit runs.
Single-Pole – Plug-in Type
Sensing and Control
PERSONAL INJURY
DO NOT USE these products as safety or emergency
stop devices or in any other application where failure
of the product could result in personal injury.
Failure to comply with these instructions could
result in death or serious injury.
WARNING
Double-Pole – Non
Plug-in Type
Sealing
Enclosure Type
Rated Operational Voltages (Ue) and Currents (Ie)
Ue
120 Vac
600 Vac
125 Vdc
250 Vdc
WIRING
Use size #12AWG or smaller solid or
stranded wire to connect to the
pressure type connector terminals.
Spades may be up to .312" wide,
rings up to .312" dia. With spade or
ring type connections, preinsulated
connectors or heat-shrinkable tubing
should be used to provide insulation
between terminals. Circuit diagram is
shown on the nameplate.
It will be easier to wire the double-
pole units by connecting lead wires to
the terminals nearest the conduit opening first. A
grounding screw is located in the housing near the
conduit opening.
Switch units with an indicator light in the cover are
furnished with the lead wires from the light connected to
the normally-open male terminals (#3 and #4) unless
otherwise specified on the order. Wires can be
unsoldered and reconnected to the normally-closed male
terminals or they can be ordered connected to the
normally-closed terminals by using a modification code
(refer to Catalog 40). Always connect these wires to the
same set of terminals used for the load. Across the
normally open male terminals (#3 and #4) the light will
be On (Fig. 1). Across the normally closed terminals (#1
and #2) the light will be Off.
IP67/68
1, 3, 3R, 4, 4X, 6, 6P, 12, 13
Ie
6 A
1.2 A
0.22 A
0.11 A
PK 81116
ISSUE 2

Related parts for LSZ4001FP

LSZ4001FP Summary of contents

Page 1

... Failure to comply with these instructions could result in death or serious injury. MOUNTING All Heavy Duty Limit Switches (HDLS) have exactly the same mounting dimensions. Mount by either of two methods: (a) use two #10 screws from the front, or (b) use two #10-32 UNF screws from the back. HDLS offers the advantage of front mount construction ...

Page 2

... Referring to Fig. 3, slide cam all the way back, so cam is free to rotate on the shaft. 2 Honeywell • Sensing and Control 4. Using a screwdriver or similar tool, rotate cam to desired actuating position (Fig and 6.) 5. Slide cam all the way forward to its original position, and close hinged cover ...

Page 3

... LSZ3K LSZ1F LSZ3L LSF1G ** LSZ1H LSZ3K LSZ1H LSZ3 L LSZ1JGA LSZ3 L LSZ1JGM LSZ3 K LSZ1JGA LSZ3 L LSZ1JGM LSZ3 L LSZ1KHA LSZ3 K LSZ1KHA LSZ3 L LSZ1L LSZ3 M LSZ1M LSZ3M LSZ1N ** LSZ1N * * LSZ1P LSZ3 K LSZ1P LSZ3 L LSZ1R LSZ3 K LSZ1R LSZ3 L LSZ1U LSZ3 K Honeywell • Sensing and Control 3 ...

Page 4

... In no event shall Honeywell be liable for consequential, special, or indirect damages. While we provide application assistance personally, through our literature and the Honeywell web site the customer to determine the suitability of the product in the application. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing ...