PM-10-5 Mean Well, PM-10-5 Datasheet

Linear & Switching Power Supplies 10W 5V 2A

PM-10-5

Manufacturer Part Number
PM-10-5
Description
Linear & Switching Power Supplies 10W 5V 2A
Manufacturer
Mean Well
Datasheet

Specifications of PM-10-5

Product
Switching
Commercial/medical
Medical
Output Power Rating
10 W
Input Voltage
85 VAC to 264 VAC, 120 VDC to 370 VDC
Number Of Outputs
1
Output Voltage (channel 1)
5 V
Output Current (channel 1)
2 A
Mounting Style
Chassis
Output Type
DC
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
OVERLOAD
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
10W Output Switching Power Supply
Note.3
Note.2
1800ms, 20ms/230VAC
100ms/230VAC
85 ~ 264VAC
47 ~ 440Hz
PM-10-3.3
3.3V
2.5A
0 ~ 2.5A
8.25W
150mVp-p
0.25A/115VAC
Above 105%
Protection type : Hiccup mode, recovers automatically after fault condition is removed
3.8 ~ 4.95V
Protection type : Shut off o/p voltage, clamping by zener diode
-20 ~ +70
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL60601-1, TUV EN60601-1, IEC60601-1 approved
I/P-O/P:4KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, EN60601-1-2, EN61204-3, medical level, criteria A
723.2Khrs min.
70*50*22.7mm (L*W*H)
0.105Kg; 120pcs/13.6Kg/0.97CUFT
66%
COLD START 25A/115VAC
3.0%
1.0%
1.0%
0.03%/
(0 ~ 50
(Refer to output load derating curve)
rated output power
120 ~ 370VDC
MIL-HDBK-217F (25 )
0.15A/230VAC
24ms/115VAC at full load
(CISPR11)
5V
2A
0 ~ 2A
10W
150mVp-p
PM-10-5
5.75 ~ 6.75V
74%
2.0%
1.0%
1.0%
1800ms, 20ms/115VAC at full load
45A/230VAC
,EN55022 (CISPR22) Class B
PM-10-12
12V
0.85A
0 ~ 0.85A
10.2W
150mVp-p
78%
13.8 ~ 16.2V
2.0%
0.5%
1.0%
PM-10-15
15V
0.67A
0 ~ 0.67A
10.05W
150mVp-p
79%
17.25 ~ 20.25V
2.0%
0.5%
1.0%
P M - 1 0
File Name:PM-10-SPEC 2010-07-19
PM-10-24
24V
0.42A
0 ~ 0.42A
10.08W
240mVp-p
79%
27.6 ~ 32.4V
EN60601-1
IEC60601-1
2.0%
0.5%
0.5%
s e r i e s

Related parts for PM-10-5

PM-10-5 Summary of contents

Page 1

... HARMONIC CURRENT Compliance to EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, EN60601-1-2, EN61204-3, medical level, criteria A EMS IMMUNITY MTBF 723.2Khrs min. 70*50*22.7mm (L*W*H) OTHERS DIMENSION 0.105Kg; 120pcs/13.6Kg/0.97CUFT PACKING NOTE PM-10 10W 150mVp-p 3.0% 2.0% 1.0% 1.0% 1.0% 1.0% 1800ms, 20ms/115VAC at full load 24ms/115VAC at full load ...

Page 2

... CONTROL Output Derating VS Input Voltage 100 (HORIZONTAL Case No. 949A Unit:inch(mm) 0.89"(22.7mm) 0.138" (3.5 1mm) RECTIFIERS & FILTER DETECTION CIRCUIT 95 100 115 120 140 160 180 200 220 INPUT VOLTAGE (VAC) 60Hz File Name:PM-10-SPEC 2010-07- fosc : 67KHz +V -V Ta=25 240 264 ...