GPM40-24G SL Power, GPM40-24G Datasheet - Page 2

Linear & Switching Power Supplies 40W 24V @ 1.7A

GPM40-24G

Manufacturer Part Number
GPM40-24G
Description
Linear & Switching Power Supplies 40W 24V @ 1.7A
Manufacturer
SL Power
Series
GPMr
Datasheet

Specifications of GPM40-24G

Product
Switching
Commercial/medical
Medical
Output Power Rating
41 W
Input Voltage
85 VAC to 264 VAC
Number Of Outputs
1
Output Voltage (channel 1)
24 V
Output Current (channel 1)
1.7 A
Mounting Style
Chassis
Open Frame/enclosed
Open Frame
Output Type
Single Output
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
GPM40-24-G
SL Power Electronics Corp, 6050 King Drive, Bldg. A, Ventura, CA 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 www.slpower.com. Rev. 1/07.
Data Sheet © 2007 SL Power Electronics Corp. The information and specifications contained in this data sheet are believed to be correct at time of publication.
However, Condor accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without notice.
Note: For 48 volt model, GPC40-48 or GPM40-48, contact factory for availability.
A. Total regulation is defined as the maximum deviation from the nominal voltage for all steady-state conditions of initial voltage setting, input line voltage and output load.
B. To maintain these regulation conditions, the 5.1V current must be at least 1/4 of V2 and not greater than 5 times the V2 current.
C. Requires +5.1V to be adjusted within ±1% with at least a 0.4A load to maintain regulation on this output.
D. Add “G” suffix to model number for RoHS compliant model.
Commercial
Model
GPC40A
GPC40B
GPC40D
GPC40-3.3
GPC40-5
GPC40-9
GPC40-12
GPC40-15
GPC40-24
GPC40-28
ENVIRONMENTAL SPECIFICA-
TIONS
Temperature (A)
Humidity (A)
Shock (B)
Altitude
Vibration (C)
GPC40/GPM40 MECHANICAL SPECIFICATIONS
3
Medical
Model
GPM40A
GPM40B
GPM40D
GPM40-3.3
GPM40-5
GPM40-9
GPM40-12
GPM40-15
GPM40-24
GPM40-28
OPERATING
See individual specs.
0 to 95% RH
20 g
-500 to 10,000 ft
1.5 g
Output No.
pk
rms’
1
2
3
1
2
3
1
2
3
1
1
1
1
1
1
1
0.003 g
2
/Hz
Output
+5.1 V
+5.1 V
+5.1 V
+12 V
+15 V
+24 V
-12 V
-15 V
-12 V
3.3 V
12 V
15 V
24 V
28 V
5 V
9 V
NON-OPERATING
-40 to +85°C
0 to 95% RH
40 g
-500 to 40,000 ft
5 g
rms’
pk
0.026 g
2
/Hz
Minimum
Output
0.4 A
0.4 A
0.4 A
0 A
0 A
0 A
0 A
0.A
0.A
0 A
0 A
0 A
0 A
0 A
0
0
A. Units should be allowed to warm up/operate under non-condensing
B. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction,
C. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to
onditions before application of power.
3 orthogonal axes, total 6 shocks.
2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating and
1 hr./axis non-operating.
Maximum
3
Output
0.4 A
0.4 A
0.4 A
4.5 A
3.3 A
2.7 A
1.7 A
1.4 A
4 A
2 A
4 A
2 A
4 A
1 A
8 A
8 A
Output
Peak
0.7 A
0.7 A
1.5 A
0.7 A
4.2 A
3.3 A
2.1 A
1.8 A
10 A
10 A
5 A
3 A
5 A
3 A
5 A
6 A
Noise P-P
120 mV
120 mV
150 mV
150 mV
240 mV
120 mV
120 mV
150 mV
240 mV
280 mV
50 mV
50 mV
50 mV
35 mV
50 mV
90mV
Regulation
Total
2%
5%
3%
2%
5%
3%
2%
5%
3%
2%
2%
2%
2%
2%
2%
2%
Notes