SMT750 American Power Conversion (APC), SMT750 Datasheet

no-image

SMT750

Manufacturer Part Number
SMT750
Description
UPS; SMART-UPS; LCD; 750VA; 120V; 500W
Manufacturer
American Power Conversion (APC)
Datasheet

Specifications of SMT750

Lead Free Status / Rohs Status
RoHS Compliant part
APC Smart-UPS 750VA LCD 120V
Part Number: SMT750
Output
Input
Batteries & Runtime
Energy Use/Efficiency
Output Power Capacity
Max Configurable Power
Nominal Output Voltage
Output Voltage Distortion
Output Frequency (sync to mains)
Crest Factor
Waveform Type
Output Connections
Nominal Input Voltage
Input Frequency
Input Connections
Cord Length
Input voltage range for main operations 82 - 144V
Input voltage adjustable range for mains
operation
Battery Type
Typical recharge time
Replacement Battery
RBC™ Quantity
Typical Backup Time
at Half Load
Typical Backup Time
at Full Load
Runtime Chart
500 Watts / 750 VA
500 Watts / 750 VA
120V
Less than 5% at full load
47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
up to 5 : 1
Sine wave
120V
50/60 Hz +/- 3 Hz (auto sensing)
1.83 meters
75 - 154V
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
3 hour(s)
RBC48
1
15.9 minutes (250 Watts)
4.6 minutes (500 Watts)
Smart-UPS
(6) NEMA 5-15R
NEMA 5-15P

Related parts for SMT750

SMT750 Summary of contents

Page 1

... APC Smart-UPS 750VA LCD 120V Part Number: SMT750 Output Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Distortion Output Frequency (sync to mains) Crest Factor Waveform Type Output Connections Input Nominal Input Voltage Input Frequency Input Connections Cord Length ...

Page 2

Communications & Management Interface Port(s) Available SmartSlot™ Interface Quantity1 Control panel Audible Alarm Emergency Power Off (EPO) Surge Protection and Filtering Surge energy rating Filtering Physical Maximum Height Maximum Width Maximum Depth Net Weight Shipping Weight Shipping Height Shipping Width ...

Page 3

Regulatory Approvals Standard Warranty Environmental Compliance **The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS. Copyright © American Power Conversion Corp., ...