2D10UM Altech Corp., 2D10UM Datasheet - Page 13

no-image

2D10UM

Manufacturer Part Number
2D10UM
Description
CIRC BRKR; UL508; THERM/MAG; HNDL; CUR-RTG 10A; DIN RAIL; 2 POLE; DUAL TERM; D
Manufacturer
Altech Corp.
Type
Thermal/Magneticr
Datasheet

Specifications of 2D10UM

Actuator Type
Toggle
Brand/series
UL508 V-EA Series
Characteristic
D
Current, Rating
10 A
Mounting Type
DIN Rail
Number Of Poles
2
Termination
Box clamp/Ring Tongue
Time, Trip
100 ms
Voltage, Rating
277 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
V-EA INTERNAL RESISTANCE
l in e c u r r e n t f r e Qu e n c Y e f f e c t s o n t r iP c u r v e s
me c h a n ic a l  e n d u r a n c e r at in g s (o n /o f f o Pe r at io n s )
Application
AC General Use
AC Motor Starting Across the Line
AC Incandescent Lamps (Tungsten)
AC Electrical Discharge Lamps (Ballast)
AC Resistance
Manufacturers self certification
Trip
Curve
G
Z
B
C
D
E
Rated
Current
(Amp)
0.3
0.5
0.75/0.8
1.0
1.6
2.0
2.5
3.0
3.5
4.0
5.0
6.0
8.0
10
12/12.5
13
15/16
20
25
30/32
40
50
60/63
16 2/3 - 60Hz
Altech Corp.
Trip Zone
10 - 16
14 - 18
Frequency Effects on Magnetic Trip Curves
5 - 10
8 - 10
(x RC)
2 - 3
3 - 5
At
(Ohms)
0.0528
0.0216
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
0.0113
B
®
11.0 - 17.6
15.4 - 19.8
Trip Zone
5.5 - 11.0
8.8 - 11.0
• 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
2.2 - 3.3
3.3 - 5.5
100 Hz
(x RC)
At
16.8620
(Ohms)
6.8540
3.0540
1.7000
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0528
0.0278
0.0216
0.0084
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
C
12.0 - 19.2
16.8 - 21.6
Trip Zone
9.6 - 12.0
2.4 - 3.6
3.6 - 6.0
6.0 - 12
200 Hz
(x RC)
At
Trip Characteristic
16.8620
(Ohms)
6.0009
3.0540
1.7560
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0491
0.0240
0.0187
0.0085
0.0076
0.0064
0.0041
0.0027
0.0022
0.0018
0.0017
2 x (1.15 x RC)
D
14.0 - 22.4
19.6 - 25.2
11.2 - 14.0
Trip Zone
7.0 - 14.0
2.8 - 4.2
4.2 - 7.0
400 Hz
(x RC)
At
1000
14.52000
(Ohms)
5.92000
2.70000
1.48000
0.57400
0.40500
0.26900
0.18600
0.13900
0.10600
0.05900
0.04600
0.03040
0.02020
0.00724
0.00724
0.00731
0.00582
0.00411
0.00272
0.00212
0.00184
0.00172
E
12.0 - 15.0
15.0 - 24.0
21.0 - 27.0
Trip Zone
7.5 - 15.0
3.0 - 4.5
4.5 - 7.5
(x RC)
DC
At
20000 ON/OFF operations with no load
2 x RC
6000
6000
6000
16.8620
(Ohms)
6.8540
3.0540
1.7560
0.5870
0.4190
0.2950
0.2020
0.1390
0.1090
0.0654
0.0491
0.0333
0.0211
0.0084
0.0084
0.0076
0.0064
0.0046
0.0030
0.0022
0.0019
0.00179
G
For example, at 16 2/3 - 60 Hz the magnetic trip zone for
the “G” characteristic is 8 to 10 times the rated current of
the specific V-EA (i.e., hold for at least 100ms at 8 x RC,
trip in less than 100ms at 10 x RC). With a 400Hz current,
a magnetic trip at 10 x RC would be greatly delayed
(thermal would likely trip first), as the magnetic trip zone is
now 11.2 to 14 x RC. If a quicker magnetic trip is required
with 400Hz, the “B” or “C” characteristic should be
considered.
The thermal trip is not affected by the frequency of the line
current. The magnetic trip is within the trip zone of the
characteristic curve for frequencies from 16 2/3 to 60Hz. At
lower and higher frequencies, the magnetic trip will be
delayed longer than indicated by the characteristic curve,
roughly as follows:
At 100Hz: Mag. Trip Current = 1.1 x curve current
At 200Hz: Mag. Trip Current = 1.2 x curve current
At 400Hz: Mag. Trip Current = 1.4 x curve current
At DC:
31.5060
10.2460
(Ohms)
5000
6000
0.00195
RC
5.3920
2.6910
0.9440
0.8900
0.4290
0.3460
0.1790
0.1620
0.1050
0.0823
0.0371
0.0278
0.0151
0.0151
0.0114
0.0075
0.0050
0.0032
0.0022
Z
Mag. Trip Current = 1.5 x curve current
No Load
Resistances listed are “hot” values, as
opposed to cold start values. Operating
voltage drop across the V-EA and power
loss per pole can be approximated with
basic formulas:
V DROP
P LOSS P/P = I
Voltage drops should be reviewed when
V-EAs with high internal resistance are
used (e.g., load voltage minimums).
Power loss should be reviewed when
V-EAs with high rated currents are used
(e.g., enclosure heating).
The listed V-EA internal resistance
values should not be used in
calculations of available short-circuit
current downstream of the V-EA. The
dynamic impedance of the V-EA under
short-circuit conditions can vary
significantly from internal resistance
values in normal operation.
4000
4000
4000
4000
4000
= I OPERATING x R TABLE
10000
10000
10000
10000
10000
Total
2
OPERATING x R TABLE
33