ARP120A3R Macromatic, ARP120A3R Datasheet - Page 2

no-image

ARP120A3R

Manufacturer Part Number
ARP120A3R
Description
Relay; E-Mech; Alternating; DPDT; Cur-Rtg 10A; Ctrl-V 120AC; Vol-Rtg 240/30AC/DC; 8 Pin
Manufacturer
Macromatic
Datasheet

Specifications of ARP120A3R

Contact Form
DPDT
Current, Rating
10 A
Dimensions
1.7" × 2.4" × 3.1"
Function
Alternating
Material, Contact
Silver Alloy
Mounting Type
Socket
Number Of Pins
8
Relay Type
Electro Mechanical
Resistance, Insulation
1000 Megohms
Standards
cUL, UL, CSA, CE
Temperature, Operating
-28 to +65 °C
Termination
Plug-In
Voltage, Control
120 VAC
Voltage, Rating
240 VAC
Temperature
–28°C to +65°C
Lead Free Status / Rohs Status
RoHS Compliant part
Application Data
Voltage Tolerances: +10%/-15% of control voltage at 50/60Hz.
Load (Burden): Less than 3VA
Output Contacts:
10A Resistive @ 240V AC/30V DC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240VAC (N.C.)
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Temperature: -28
Dimensions
Typical Installations
In the off state, both the LEAD Control Switch and the LAG Control Switch are open, the Alternating Relay is in the LOAD A
position, and both loads are off. When the LEAD Control Switch closes, it energizes the first load (M1). The red LED marked
“LOAD A” glows. As long as the LEAD Control Switch remains closed, M1 remains energized. If the LAG Control Switch closes, it
energizes the second load (M2). When the LAG Control Switch opens, the second load (M2) is turned off. When the LEAD
Control Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B position. When the LEAD
Control Switch closes, it turns on the second load (M2). The red LED marked “LOAD B” glows. If the LAG Control Switch closes,
it will energize the first load (M1). When the LAG Control Switch opens, the first load (M1) is turned off. When the LEAD Control
Switch opens, the second load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process can
be repeated again.
To eliminate any bounce condition of the Control Switch, the addition of a second switch (OFF) along with two auxiliary contacts is
recommended as shown in Figure B.
o
to 65
2.4 (60)
o
C (-20
Figure A
o
to 150
o
F)
(43)
1.7
ALTERNATING RELAYS
File #E109466
Transient Protection: 10,000 volts for 20 microseconds
Indicator LED's: 2 LED's marked LOAD A and LOAD B
Optional Selector Switch Settings:
ALTERNATE
LOCK LOAD A
LOCK LOAD B
Approvals:
(74)
2.9
(79)
3.1
File #LR45565
Application Data & Dimensions
DPDT Cross-Wired
Figure B
File #E109466
Inches (Millimeters)
All Dimensions in
with
appropriate
socket
55