SUA3000RM2U American Power Conversion (APC), SUA3000RM2U Datasheet - Page 4

no-image

SUA3000RM2U

Manufacturer Part Number
SUA3000RM2U
Description
UPS, Rack Mount, 3000VA/2700W, Input 120V/Output 120V, 2U Rack Height
Manufacturer
American Power Conversion (APC)
Type
Networkr
Datasheet

Specifications of SUA3000RM2U

Battery Type
Lead-Acid
Brand/series
SMX
Capacity
3000 VA
Color
Black
Communication
DB9, RS232, SmartSlot, USB
Dimensions
432mmH×196mmW×546mmD
Input Type
NEMA L5-30P
Interface
DB-9 RS-232, USB, Smartslot
Length, Cord
1.83 m
Mounting Type
Rack/Tower
Output Type
(6) NEMA 5-15R, (2) NEMA 5-20R
Power, Rating
2700 W
Time, Backup
3 min.
Voltage, Output
120 V
Voltage, Supply
2700/3000 W/VA
Weight
52.73 kg
Output
Input
Batteries & Runtime
Energy Use/Efficiency
Output Power Capacity
Max Configurable Power
Nominal Output Voltage
Output Voltage Distortion
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor
Waveform Type
Output Connections
Nominal Input Voltage
Input Frequency
Input Connections
Cord Length
Input voltage range for main
operations
Input voltage adjustable range for
mains operation
Battery Type
Typical recharge time
Replacement Battery
RBC™ Quantity
Typical Backup Time
at Half Load
Typical Backup Time
at Full Load
Runtime Chart
2700 Watts / 3000 VA
2700 Watts / 3000 VA
120V
Less than 5% at full load
up to 5 : 1
Sine wave
120V
50/60 Hz +/- 3 Hz (auto sensing)
2.44 meters
82 - 144V
75 - 154V
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
3 hour(s)
RBC43
1
11.3 minutes (1350 Watts)
3.0 minutes (2700 Watts)
Smart-UPS
(6) NEMA 5-15R
(2) NEMA 5-20R
NEMA L5-30P