TR-60628 Macromatic, TR-60628 Datasheet

no-image

TR-60628

Manufacturer Part Number
TR-60628
Description
Relay; Timer; True Off Delay, 0.05S-30M; DPDT, 10A, 240VAC/28VDC; Ctrl-V 24AC/DC; Octal
Manufacturer
Macromatic
Datasheet

Specifications of TR-60628

Temperature
–28° to +65°C
Dimensions
1.7" × 2.4" × 3.5"
Lead Free Status / Rohs Status
RoHS Compliant part
58
TIME DELAY RELAYS
Time Ranger
Plug-in
True Off Delay
u
u
u
u
u
u
u
www.macromatic.com
sales@macromatic.com
800-238-7474
Provides Off Delay function
without requiring input voltage
during Off time delay
Duplicates operation of pneu-
matic Off Delay timers
Each unit has 8 timing ranges
built-in, covering 0.05 seconds
to 30 minutes
Selecting a range is easy using
a rotary switch (no math is
required or DIP switches to
set)
Uses industry-standard 8 pin
octal socket
10A DPDT output contacts
appropriate
socket
TM
with
Programmable
Most electronic time delay relays with an off delay function require input voltage to be
applied continuously in order to operate correctly. However, there are many applications
where this is not possible--keeping a relay energized for some amount of time after input
voltage has been removed. A true off delay product provides this function even when
input voltage is removed. It duplicates the operation of the older off delay pneumatic
time delay relays.
Operation of True Off Delay: Upon
application of input voltage, the relay is
energized. When the input voltage is
removed, the preset time begins. At the
end of the preset time, the relay is de-
energized. Voltage must be applied for
a minimum of 0.1 second to assure
proper operation. Any application of
the input voltage during the preset time will keep the relay energized & reset the time
delay. No external trigger switch is required.
Timing Ranges
Sockets & Accessories-Pages 81 & 82
Dimensions-Page 59
120V AC/DC
24V AC/DC
VOLTAGE
240V AC
50/60Hz.
INPUT
Select one of the 8 built-in time ranges by setting the rotary
switch per the chart on the unit or below and adjust within that
range using the knob on top:
0.05 Sec. - 30 Min.
0.05 Sec. - 30 Min.
0.05 Sec. - 30 Min.
RANGE
TIMING
Setting
Dial
G
A
B
C
D
E
H
F
Application Data-Page 59
Standard Modifications-Page 80
PRODUCT
NUMBER
TR-60622
TR-60628
TR-60621
0.05 - 5 Sec.
0.1 - 10 Sec.
0.3 - 30 Sec.
0.6 - 60 Sec.
1.8 - 180 Sec.
0.1 - 10 Min.
0.3 - 30 Min.
3 - 300 Sec.
Timing
Range
8 PIN OCTAL
DIAGRAM 1
SOCKETS
WIRING/
70169-D
1/09

Related parts for TR-60628

TR-60628 Summary of contents

Page 1

... Select one of the 8 built-in time ranges by setting the rotary switch per the chart on the unit or below and adjust within that range using the knob on top: PRODUCT WIRING/ NUMBER SOCKETS TR-60622 8 PIN OCTAL 70169-D TR-60628 TR-60621 DIAGRAM 1 Application Data-Page 59 Standard Modifications-Page 80 Dial Timing Setting Range A ...

Page 2

... OFF state prior to use in the application. Please note that it will take as long as the OFF Delay setting to reset the unit once input voltage has been removed. 2.9 (74) 3.5 (89) True Off Delay All Dimensions in Inches (Millimeters) 59 ...

Related keywords