H5CX-A11DNDC12-24/AC24 Omron Automation, H5CX-A11DNDC12-24/AC24 Datasheet - Page 41

no-image

H5CX-A11DNDC12-24/AC24

Manufacturer Part Number
H5CX-A11DNDC12-24/AC24
Description
Relay; E-Mech; Timing; Multi-Function; Cur-Rtg 5A; Ctrl-V 24/12-24AC/DC; Socket Mnt
Manufacturer
Omron Automation
Type
Timerr
Datasheet

Specifications of H5CX-A11DNDC12-24/AC24

Brand/series
H5CX
Connection Type
11 Pin Socket
Contact Form
5 A at 250VAC/30 VDC
Dimensions
58H x 48W x 62.5D
Display Type
7 Segment LCD
Function
Multifunction Digital Timer
Input Type
Signal, Reset and Gate
Ip Rating
IP66
Mounting Type
Flush, Surface or Din Rail
Number Of Inputs
3
Number Of Outputs
1
Output Type
SPDT
Primary Type
Digital Timer
Voltage, Supply
12-24 VDC/24 VAC
Safety Precautions for All H5CX Series (Common)
Do not allow pieces of metal, wire clippings, or fine
metallic shavings or fillings from installation to enter
the product. Doing so may occasionally result in
electric shock, fire, or malfunction.
Minor injury due to explosion may occasionally occur.
Do not use the Timer where subject to flammable or
explosive gas.
Fire may occasionally occur. Tighten the terminal
screws to the rated torque.
H5CX terminals: 6.55 to 7.97 lb-in (0.74 to 0.90 N m)
P2CF Socket terminals: 4.4 lb-in (0.5 N m)
Minor injury due to electric shock may occasionally
occur. Do not touch any of the terminals while power
is being supplied. Be sure to mount the terminal cover
after wiring.
The life expectancy of the output relay varies
considerably according to its usage. Use the output
relay within its rated load and electrical life
expectancy. If the output relay is used beyond its life
expectancy, its contacts may become fused or there may be a
risk of fire. Also, be sure that the load current does not exceed
the rated load current and when using a heater, be sure to use a
thermal switch in the load circuit.
Minor electric shock, fire, or malfunction may
occasionally occur. Do not disassemble, modify, or
repair the Timer or touch internal components.
• The panel surface of the H5CX is water-resistant (conforming to
• When mounting the Timer to a panel, tighten the two mounting
• Store the Timer at the specified temperature. If the Time has been
• Mounting the Timer side-by-side may reduce the life expectancies
• Use the Timer within the specified ranges for the ambient operating
• Do not use in the following locations:
• Do not use the Timer outside of the rated ranges for vibration,
• Do not use this Timer in dusty environments, in locations where
• Install the Timer well away from any sources of static electricity,
NEMA4, IP66, UL Type 4X (Indoor Use Only). To protect the
internal circuits from water penetration through the space between
the H5CX and operating panel, waterproof packing is included.
Attach the Y92F-30 Adapter with sufficient pressure with the
reinforcing screws so that water does not penetrate the panel.
screws alternately, a little at a time, so as to keep them at an equal
tightness. If the panel screws are tightened unequally, water may
enter the panel.
stored at a temperature of less than -10°C, allow the Time to stand
at room temperature for at least 3 hours before use.
of internal components.
temperature and humidity.
shock, water exposure, and oil exposure.
corrosive gasses are present, or in locations subject to direct
sunlight.
such as pipes transporting molding materials, powders, or liquids.
• Locations subject to sudden or extreme changes in
• Locations where high humidity may result in condensation.
temperature.
Precautions for Safe Use
0.5 to 1 mm
CAUTION
It is recommended that the
space between the screw
head and the Adapter be 0.5
to 1 mm.
• Internal elements may be destroyed if a voltage outside the rated
• Be sure that polarity is correct when wiring the terminals.
• Separate the Timer from sources of noise, such as devices with
• Do not connect more than two crimp terminals to the same
• Up to two wires of the same size and type can be inserted into a
• Use the specified wires for wiring. Applicable Wires: AWG 18 to
• Install a switch or circuit breaker that allows the operator to
• When the Timer is operated with no-voltage input (NPN input),
• Use a switch, relay, or other contact so that the rated power supply
• Use a switch, relay, or other contact to turn the power supply OFF
• H5CX-A@-N/-L@-N:
• H5CX-B@-N:
• Do not use organic solvents (such as paint thinners or benzine),
• Confirm that indications are working normally, including the
• The waterproof packing may deteriorate, shrink, or harden
voltage range is applied.
input signals from power lines carrying noise, and wiring for I/O
signals.
terminal.
single terminals.
AWG 22, solid or twisted, copper.
immediately turn OFF the power, and label it to clearly indicate its
function.
approximately 14 V is output from the input terminals. Use a sensor
that contains a diode.
voltage will be reached within 0.1 seconds. If the power supply
voltage is not reached quickly enough, the Timer may malfunction
or outputs may be unstable.
instantaneously. Outputs may malfunction and memory errors may
occur if the power supply voltage is decreased gradually.
When changing the set value during a timing operation, the output
will turn ON if the set value is changed as follows because of the
use of a constant read-in system:
Elapsed time (UP) mode: Present value
Remaining time (DOWN) mode: Elapsed time
present value is set to 0.)
When in the remaining time mode, the amount the set value is
changed is added to or subtracted from the present value.
Operation with a set value of 0 will vary with the output mode. Refer
to the timing charts on page 20.
When changing the set value during a timing operation, the output
will turn ON if the set value is changed as follows because of the
use of a constant read-in system:
1. Forecast Value Setting
2. Absolute Value Setting
strong alkali, or strong acids. They will damage the external finish.
backlight LED, and LCD. The indicator LEDs, LCD, and resin parts
may deteriorate more quickly depending on the application
environment, preventing normal indications. Periodic inspection
and replacement are required.
depending on the application environment. Periodic inspection and
replacement are required.
When the present value
turns ON.
When the present value
set value - forecast set value), OUT1 (forecast output) turns ON.
When the present value
turns ON.
When the present value
set value - forecast set value), OUT1 (control output 1) turns
ON.
When the set value is 0, the output turns ON the moment the
signal is input. The reset operation turns OFF the output.
Sensor
0V
the set value, OUT2 (control output)
set value 2, OUT2 (control output 2)
the forecast value (forecast value =
the forecast value (forecast value =
Input
Diode
Set value
H5CX-@-N
Set value (The
41

Related parts for H5CX-A11DNDC12-24/AC24