E2E2-X18MY1-US Omron Automation, E2E2-X18MY1-US Datasheet - Page 4

no-image

E2E2-X18MY1-US

Manufacturer Part Number
E2E2-X18MY1-US
Description
Sensor; Inductive Sensing Mode; M30; 18 mm; 24 to 240 VAC; 25 Hz; -40 to degC
Manufacturer
Omron Automation
Type
Inductiver
Datasheet

Specifications of E2E2-X18MY1-US

Body Style
Cylindrical
Current, Leakage
1.7 mA (Max.)
Current, Switching
300 mA
Frequency, Operating
50⁄60 Hz
Frequency, Switching
25 Hz
Function
Proximity
Indicator
Red LED (Operation Indicator)
Ip Rating
IP67
Material, Housing
Thick Nickel Plated Brass
Mounting Type
M30 Threaded
Output
NO
Primary Type
Proximity
Range, Measurement
18 mm
Standards
UL Recognized, CSA Certified, CE Marked
Technology
Inductive
Temperature Range
-40 to +85 °C
Termination
Pre-Wired
Voltage, Supply
240 VAC
Voltage, Switching
3 V
Supply Voltage Range
10-55 VDC or 20-264 VAC, 50/60 Hz (Model Dependant)
Load Rating
200 mA (DC) or 5-200 mA/5-300 mA (AC) (Model Dependant)
Approvals
CE, UL, CSA (Model Dependant)
Lead Free Status / Rohs Status
RoHS Compliant part
E2E2-X@Y@ AC 2-Wire Models
*1. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is at least −25°C to 85°C.
*2. When using an M18 or M30 Connector Model at an ambient temperature between 70 and 85°C, make sure that the Sensor has a control output (load current) of 5
Item
Sensing distance
Set distance
Differential travel
Sensing object
Standard sensing object
Response frequency
Power supply voltage (op-
erating voltage range) *1
Leakage current
Control
output
Indicators
Operation mode
(with sensing object ap-
proaching)
Ambient temperature *1, 2
Ambient humidity
Temperature influence
Voltage influence
Insulation resistance
Dielectric strength
Vibration resistance
(destruction)
Shock resistance
(destruction)
Degree of protection
Connection method
Weight (packed state)
Materi-
als
Accessories
to 200 mA max.
Load current *2
Residual voltage Refer to Engineering Data on page 5.
Case
Sensing surface PBT
Clamping nuts
Toothed washer Zinc-plated iron
Shielding
Model
Size
2 mm±10%
0 to 1.6 mm
10% max. of sensing distance
Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on
page 5.)
Iron,
12 × 12 × 1 mm
25 Hz
24 to 240 VAC (20 to 264 VAC), 50/60 Hz
1.7 mA max.
5 to 200 mA
Operation indicator (red)
Y1 Models: NO
Y2 Models: NC
Operating/Storage: −40 to 85°C (with no icing or condensation)
Operating/Storage: 35% to 95% (with no condensation)
±15% max. of sensing distance at 23°C in the temperature range of −40 to 85°C,
±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C
±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
50 MΩ min. (at 500 VDC) between current-carrying parts and case
4,000 VAC, 50/60 Hz for 1 minute between current carry parts and case
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
1,000 m/s
IEC IP67, in-house standard for oil resistance
Pre-wired Models (Standard cable length: 2 m) and Connector Models
Approx. 65 g
Brass
Nickel-plated brass
Instruction sheet
E2E2-X2Y@
Shielded
2
10 times each in X, Y, and Z directions
M12
Refer to the timing charts under I/O Circuit Diagrams on page 8 for details.
5 mm±10%
0 to 4 mm
Iron,
15 × 15 × 1 mm
E2E2-X5MY@
Unshielded
5 mm±10%
0 to 4 mm
Iron,
18 × 18 × 1 mm
5 to 300 mA
Approx. 150 g
E2E2-X5Y@
Shielded
M18
10 mm±10%
0 to 8 mm
Iron,
30 × 30 × 1 mm
E2E2-X10MY@
Unshielded
10 mm±10%
0 to 8 mm
Iron,
30 × 30 × 1 mm
Approx. 210 g
E2E2-X10Y@
Shielded
M30
18 mm±10%
0 to 14 mm
Iron,
54 × 54 × 1 mm
E2E2-X18MY@
Unshielded
E2E2
4

Related parts for E2E2-X18MY1-US