S8TS-03012F-E1 Omron Automation, S8TS-03012F-E1 Datasheet - Page 8

no-image

S8TS-03012F-E1

Manufacturer Part Number
S8TS-03012F-E1
Description
Power Supply; 12 V; 2.5 A; 50/60 Hz; 50 A (Max.); 1.69 in.; 4.72 in.; 5 mm
Manufacturer
Omron Automation
Datasheet

Specifications of S8TS-03012F-E1

Brand/series
S8TS Series
Configuration
Enclosed
Current, Inrush
50 A (Max.)
Current, Rating
2.5 A
Diameter
5 mm
Frequency
50⁄60 Hz
Height
4.72 in.
Mounting Type
DIN Rail
Number Of Outputs
1
Operation
Switching
Output
12 VDC @ 2.5 A
Power, Output
30 W
Primary Type
AC-DC
Temperature, Operating, Maximum
+65 °C (Ambient)
Temperature, Operating, Minimum
-25 °C (Ambient)
Voltage, Input
100 to 240 VAC
Voltage, Output
12 VDC
Voltage, Rating
12 V
Width
1.69 in.
Lead Free Status / Rohs Status
RoHS Compliant part
Engineering Data
■ Derating Curves
Note: 1. If there is a derating problem, use forced air-cooling.
■ Overload Protection
The Power Supply is provided with an overload protection function
that protects the Power Supply from possible damage by overcurrent.
When the output current rises above 105% min. of the rated current
(100% min. of the rated current for parallel operation), the protection
function is triggered, automatically decreasing the output voltage.
When the output current falls within the rated range, the overload
protection function is automatically cleared.
The values shown in the above diagram are for reference only.
Note: Internal parts may occasionally deteriorate or damaged if a
120
100
80
60
40
20
−20 −10 0
Parallel Operation and Side-by-side
Mounting
0
2. The ambient temperature is specified for a point 50 mm below the Power Supply.
3. Use the rated output for single operation multiplied by N as a reference for the load ratio for an N+1 redundant system.
short-circuited or overcurrent continues for 20 min. or longer.
200 V input (side-by-side mounting)
100/200-V input
(parallel operation),
100-V input
(side-by-side mounting)
10 20 30 40 50 55 60 70
Ambient temperature (°C)
0
50
Output current (%)
100
120
100
80
60
40
20
−20 −10 0
0
Single Operation with Spaces
between Blocks
10 20 30 40 50
20 mm min.
Ambient temperature (°C)
100 V input
200 V input
■ Overvoltage Protection
An overvoltage protection function is provided so that excessive
voltage is not applied to the load, e.g., if the feedback circuit in the
Power Supply fails. When a voltage that is approximately 120% of the
rated voltage or more is output, the output voltage is shut OFF. Reset
the input power by turning it OFF for at least 1 minute and then
turning it back ON again.
12-V and 5-V Models
24-V Models
The values shown in the above diagrams are for reference only.
Note: Do not turn ON the input power again until the cause of the
60 70
overvoltage has been removed.
Rated output
voltage
Rated output
voltage
120
100
80
60
40
20
−20 −10 0
0
N+1 Redundant System
+10%
–10%
28 V
22 V
0 V
0 V
10 20 30 40 50
Ambient temperature (°C)
Variable range
Variable range
Overvoltage
protection
operating
Overvoltage
protection
operating
60 70
S8TS