TRW27 Eaton / Control Automation, TRW27 Datasheet
TRW27
Specifications of TRW27
Related parts for TRW27
TRW27 Summary of contents
Page 1
... Notes Applies to TRN model only. Applies to TRF model only. The E5-248 is battery powered and has three programmable trigger functions. This product may perform somewhat differently from the standard timing relays. Refer to the operator instructions for details. Control Relays and Timers Contents ...
Page 2
... Control Relays and Timers Timing Relays Product Overview 49 Timer Function Descriptions 49 Function #1—Universal TR, TMR5, E5-248 Asymmetrical Flasher, Pause First 49 Repeat Cycle, OFF/ON Delay When the supply voltage applied, the set interval t1 begins. After the interval t1 49 has expired, the output relay ...
Page 3
... OFF position. the OFF position. Input Power (U) LED U/t* Output LED** Output Relay (R) t Control Relays and Timers Function #10—Universal TR, TRF, TMR5, TMRP, E5-248 OFF Delay/Signal OFF Delay Delay ON Release The supply voltage U must be constantly applied to the device. When the control ...
Page 4
... Control Relays and Timers Timing Relays Function #13—Universal Delay Control Signal Start, Trailing Edge OFF 49 The supply voltage U must be constantly applied to the 49 device. When the control switch S is applied, the set 49 interval t begins. After the interval t has expired, the 49 output relay R switches to the ON position ...
Page 5
... Input Power (U) Trigger Signal Output LED** Output Relay ( Control Relays and Timers Function #22—TMRP, E5-248 Single Pulse Generator, Voltage Controlled When the supply voltage U is applied, the set interval t begins. After the interval t has expired, the relay will switch to the ON position for ...
Page 6
... Control Relays and Timers Timing Relays 49 Universal TR Series Universal TR Series 49 Product Description Eaton’s Universal TR Series 49 timers are our most flexible and cost-effective timing 49 relays available. Products are available with up to seven user-selectable functions and 49 seven user-selectable time ranges. Each unit is DIN rail ...
Page 7
... Automatic adaption to supply voltage supply voltage DC 50 ms/AC 100 ms/AC 100 ms Control Products Catalog CA08102001E—September 2010 www.eaton.com 49.8 Timing Relays TRW27 49 Ii, Ip, ER, Ewu, Ews, WsWa, Wt 0.05 sec to 100 hours 49 12–240 Vac/Vdc 49 ±10 (2W) 100% 49 100 ms 10% 49 >30% of rated supply voltage 49 ...
Page 8
... Self-extinguishing plastic housing, IP40 rating Mounted on DIN rail TS 35 according to EN 60715, any position Shockproof terminal connection according to VBG 4 (PZ1 required), IP20 rating Max Double-Pole, Double-Throw Units (DPDT)— TRL27 and TRW27 (+) U = (–) S (Used only for control switch triggered functions) TRL27 TRW27 ± ...
Page 9
... Dimensions Approximate Dimensions in Inches (mm) 17.5 mm (TRL04 and TRL07) 0.20 1.73 (44.0) (5.0) 2.36 (60.0) Control Relays and Timers 35 mm (TRL27 and TRW27) 3.43 1.77 (87.0) (45.0) 0.20 1.73 0.69 (44.0) (5.0) (17.5) Control Products Catalog CA08102001E—September 2010 www.eaton.com 49.8 Timing Relays 3 ...