XTSC012BBA Eaton / Control Automation, XTSC012BBA Datasheet

no-image

XTSC012BBA

Manufacturer Part Number
XTSC012BBA
Description
MANUAL MOTOR CONTROLLER; 8-12A; FRAME B MMP W/FRAME B CONTACTOR 1NO; 120VAC COIL
Manufacturer
Eaton / Control Automation
Type
Motorr
Datasheet

Specifications of XTSC012BBA

Brand/series
XT Series
Coil Voltage
120
Current, Input
12 A
Current, Rating Max
12
Dimensions
45mmL×95.7mmW×209.2mmH
Frame Contactor
B/B
Horsepower, Max, 3 Phase, At 200 V
3
Horsepower, Max, 3 Phase, At 240 V
3
Horsepower, Max, 3 Phase, At 480 V
7.5
Horsepower, Max, 3 Phase, At 600 V
10
Ip Rating
IP20
Motor, Amp, Full Load
8-12
Mounting Type
DIN Rail
Power, Rating
5.5 kW
Primary Type
Motor Controller
Standards
CE
Voltage, Supply
120 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
For Use With
3-Phase Motor
174
Contents
Description
Standards and
Catalog Number
Product Selection . . . . . . . . . .
Accessories . . . . . . . . . . . . . . .
Technical Data and
Dimensions . . . . . . . . . . . . . . .
Reference Data . . . . . . . . . . . . .
Product Description
The new Cutler-Hammer
Non-reversing and Reversing Manual
Motor Controllers from Eaton’s electrical
business combine a Manual Motor
Protector with an IEC Contactor(s) to
provide a complete motor protection
solution by combining motor disconnect
function, thermal overload protection,
magnetic short circuit protection and
remote control operation in one com-
pact, assembled unit. These assembled
Manual Motor Controllers cover
motors with FLA ratings from 0.10A to
63A.
The UL 508 Type F labeled Combination
Motor Controller (CMC) includes a Line
Side Adapter (LSA). These assembled
Combination Motor Controllers cover
motors with FLA ratings from 0.10A to
52A.
Certifications . . . . . . . . . . . . .
Selection . . . . . . . . . . . . . . . .
Specifications . . . . . . . . . . . .
XT IEC Power Control
Combination Motor Controllers
Product Family Overview
XT Combination Motor Controller
and Manual Motor Controller
®
XT IEC Open
Page
175
176
177
179
182
186
199
Application Description
The XT IEC Non-reversing and Revers-
ing Manual and Combination Motor
Controllers can be used in the follow-
ing applications:
XTSC and XTSR
XTFC and XTFR
For Group Installations (in-panel
SCPD) applying the traditional 1/3 tap
rule, the Manual Motor Protectors and
Combination Motor Controllers may
be used on 480V Delta systems along
with 480Y/277V and 600Y/347V slash
rated Wye systems. For Group Installa-
tions, applying the more recent 1/10
tap conductor rule, a maximum 240V
Delta is permitted or 480Y/277V and
600Y/347V slash rated Wye systems.
For more information visit: www.eaton.com
Manual Motor Controller for Single
and Multi Motor Panels — The pre-
assembled XT Manual Motor Con-
trollers (MMC) combine a Manual
Motor Protector, a Wiring Connector
Link and IEC Contactor. MMCs can
also be field installed with separate
MMP, WCL and Contactor(s). An IEC
magnetic contactor has been added
to allow for remote operation of the
motor circuit.
Combination Motor Controller (UL
508, Type F), for Single and Multi
Motor Panels — The preassembled
IEC Combination Motor Controllers
combine a Line Side Adapter, Man-
ual Motor Protector, Wiring Connec-
tor Link and IEC Contactor. The
XTPR Manual Motor Protectors are
UL listed as UL 508, Type E Self-
Protected Manual Combination
Starters. This UL listing allows these
devices to be used in motor circuits
without having to add separate
branch short circuit protection. An
IEC magnetic contactor has been
added to allow for remote operation
of the motor circuit.
Group Motor Installations — Since
the Manual Motor Protectors
(Manual Combination Starters) are
UL listed for Group Motor Installa-
tions, the IEC Manual Motor Control-
lers provide a compact, assembled
package for Group Motor Installa-
tions up to 600V.
For actual UL 508 Type E/F applications
(out-of-panel upstream feeder Short-
Circuit Protective Device [SCPD] only),
a maximum 240V Delta is permitted or
480Y/277V and 600Y/347V slash rated
Wye systems.
For Manual “At Motor” Disconnect
applications, a maximum 240V Delta is
permitted or 480Y/277V and 600Y/347V
slash rated Wye systems.
Features
ON/OFF rotary handle with lockout
provision
Visible trip indication
Test trip function
Motor applications from 0.10A to
63A
Class 10 overload protection
Built-in heater and magnetic trip
elements to protect the motor
Phase loss sensitivity
Type 2 coordination
Ambient compensated up to 55°C
[140°F]
Control inputs located at front of
starter for easy access and wiring
Wide range of coils
DIN Rail mount — XTSC…BB_
Mounting plates — XTSC…BC_,
XTSC…D motor controllers
Adjustment dial for setting motor
FLA
Short circuit trip at 14 times the
maximum setting of the FLA
adjustment dial
UL 508 Type F CMC High Fault Short
Circuit Ratings: Refer to Table 232.
1NO-1NC Auxiliary Contact as
standard on Manual Motor
Controller and Combination Motor
Controller
CA03407001E
May 2007

Related parts for XTSC012BBA

XTSC012BBA Summary of contents

Page 1

XT IEC Power Control 174 Combination Motor Controllers Product Family Overview Contents Description Page Standards and Certifications . . . . . . . . . . . . . 175 Catalog Number Selection . . . . . . ...

Page 2

May 2007 Standards and Certifications UL 508 Type F Combination Motor Controller ■ IEC Type 2 Approved per IEC 60947-4-1 ■ UL Listed File No. E245398 ■ CE Mark Note: For Type 2 Coordination of MMCs, see Tables 247 through ...

Page 3

XT IEC Power Control 176 Combination Motor Controllers Catalog Number Selection Catalog Number Selection Table 222. Combination Motor Controllers — Catalog Numbering System Design IEC Power Control Type SC = Manual Motor Controller — FVNR SR = ...

Page 4

May 2007 Product Selection Table 223. XTSC and XTSR Manual Motor Controllers (MMC) / Starter Combinations Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor FLA Short- Maximum Motor Ratings — P Adjustment Circuit Maximum Motor kW ...

Page 5

XT IEC Power Control 178 Combination Motor Controllers Product Selection Table 224. XTFC and XTFR Combination Motor Controllers (CMC), UL508 Type F Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor + Required Line Side Adapter FLA ...

Page 6

May 2007 Table 225. AC and DC Coil Suffixes Coil Voltage Suffix Code Frame B Contactors 110V 50 Hz, 120V 220V 50 Hz, 240V 230V 24V 50/ 24V DC ...

Page 7

XT IEC Power Control 180 Combination Motor Controllers Accessories Combination Connection Kits Combination Connection Kits include the necessary components to field assemble a Manual Motor Controller with an MMP (XTPR) and Contactor (XTCE). Table 227. Combination Connection Kits For Use ...

Page 8

May 2007 Combination Connection Kits Table 227. Combination Connection Kits (Continued) For Use with… Electric Contact Module XTPR...B + XTCE...C XTPR...D + XTCE...D DIN Rail Adapter Plates XTPAXTPCB XTPAXTPCRB XTPR...B + XTCE...C XTPAXECMC XTPAXECMD XTPR...D + XTCE...C XTPR...D + XTCE...D ...

Page 9

XT IEC Power Control 182 Combination Motor Controllers Technical Data and Specifications Technical Data and Specifications Table 228. Manual and Combination Motor Controllers Motor Ratings Assembled Controller FLA Adjustment Range / Overload Release — Non-reversing Reversing I r (Amps) XTSC ...

Page 10

May 2007 Table 229. XTSC and XTSR Manual Motor Controllers (MMC) / Starter Combinations — Component Bill of Material Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor Assembled Manual FLA Adjustment Range / Motor Controller Overload ...