Powerware series Eaton 5130 UPS Product snapshot Power rating: 1250 VA/1150W 1750 VA/1600W 2500 VA/2250W 3000 VA (2880 VA)/2700W Voltage 120, 208 and 230 Vac, user-selectable voltages Frequency: 50/60 Hz (auto-sensing) Topology: Line-interactive, 0.9+ power factor Configuration: Two-in-one rack/tower; pedestal ...
Page 2
Maximum availability • Load segments allow for selective load shedding dur- ing outages • Optional extended battery modules (EBMs) extend back- up runtime up to hours during power outages • Hot-swappable batteries • UPS startup on battery power • Optional ...
Page 3
... PW5130L2500-XL2U / PW5130i2500-XL2U (with PW5130N3000-EBM2U) 250/225 90 375 625/563 44 198 1250/1125 17 85 2153/1938 11 50 2500/2250 6 30 PW5130L3000-XL2U / XL3U / PW5130i3000-XL2U / XL3U / PW5130G3000-XL2U (with PW5130N3000-EBM2U or -EBM3U, depending on UPS height) 300/270 80 320 750/675 40 158 1500/1350 15 60 2250/2025 9 37 3000/2700 Battery backup times, shown at 0.7 power factor, are approximate and may vary with equipment, configuration, battery age, temperature, etc ...
Page 4
General LEDs 13 status-indicating LEDs Topology Line-interactive Diagnostics Full system self-test at power up Transfer time 1–4 ms typical ROO/RPO Rear deck emergency stop connector (for remote on/off and power off) Rail kit/tower stand Included with all units Electrical ...