CSW2410P Crydom Company, CSW2410P Datasheet - Page 3

no-image

CSW2410P

Manufacturer Part Number
CSW2410P
Description
Relay; SSR; Zero-Switching; Cur-Rtg 10A; Ctrl-V 32DC; Vol-Rtg 24-280AC; Pnl-Mnt; 4 Pin
Manufacturer
Crydom Company
Datasheet

Specifications of CSW2410P

Brand/series
CSW Series
Current, Rating
10 A
Function
Zero-Switching
Mounting Type
Panel
Number Of Pins
4
Relay Type
Solid State
Standards
UL, CSA, VDE
Termination
Saddle Clamp
Voltage, Control
32 VDC
Voltage, Rating
280 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
G E N E R A L N O T E S
OUTPUT SPECIFICATIONS 1
Operating Voltage (47-63 Hz) [Vrms]
Load Current Range
Transient Overvoltage [Vpk]
Max. Surge Current, (16.6ms) [Apk]
Max. On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (R
Maximum I 2 t for Fusing, (8.3 msec.) [A 2 sec]
Max. Off-State Leakage Current @ Rated Voltage [mA]
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]
Max. Turn-On Time
Max. Turn-Off Time
Power Factor (Min.) with Max. Load
INPUT SPECIFICATIONS
Control Voltage Range
Max. Turn-On Voltage
Min. Turn-Off Voltage
Nominal Input Impedence
Typical Input Current
1
2
3
4
SERIES CSW.
Rev. 012506
PAGE 1 OF 3
Input Circuit Incorporates Active Current Limiter.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
All parameters at 25ºC unless otherwise specified.
Heat sinking required, for derating curves see page 2.
3
[Arms]
M O D E L N U M B E R S
1
θJC
) [°C/W]
2
• Zero Voltage Switching
• Wide Control Range
Panel Mount
Low Leakage
SCR Output
CSW2410
1/2 Cycle
1/2 Cycle
0.15-10
24-280
1.48
600
120
500
1.6
1.0
0.5
60
CSW2425
1/2 Cycle
1/2 Cycle
0.15-25
24-280
1.02
600
250
260
500
1.6
1.0
0.5
DC CONTROL
10mA @ 12 Vdc
See note 4
© 2006 CRYDOM CORP, Specifications subject to change without notice.
3-32 Vdc
1.0 Vdc
3 Vdc
10-90Amp • 120/240 Vac • AC OUTPUT
CSW2450
1/2 Cycle
1/2 Cycle
0.15-50
24-280
1620
The Series CS has an SCR AC switch
output featuring low off-state leakage
(1mA, snubberless), zero-voltage
switching and a broadened operating
range (24-280Vac). This wide range
permits optimum performance at both
120Vac and 240Vac line voltages.
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
0.63
600
625
500
1.6
1.0
0.5
Series
CSW2475
1/2 Cycle
1/2 Cycle
0.25-75
24-280
1000
4150
0.31
600
500
1.6
1.0
0.5
CSW
CSW2490
1/2 Cycle
1/2 Cycle
0.25-90
24-280
1200
6000
0.28
600
500
1.6
1.0
0.5