CP1WAD041 Omron Automation, CP1WAD041 Datasheet - Page 33

no-image

CP1WAD041

Manufacturer Part Number
CP1WAD041
Description
Analog Input Unit
Manufacturer
Omron Automation
Type
I/Or
Datasheet

Specifications of CP1WAD041

Application
Logic Control
Brand/series
CP1
Function
Automation Control
Input Type
Analog
Mounting Type
DIN Rail or Panel
Primary Type
Expansion
Termination
Screw Terminals
Lead Free Status / Rohs Status
RoHS Compliant part
For Use With
Micro Controllers
46
Expansion Unit Specifications
■ CP1W-AD041/DA041/MAD11 Analog Units
■ Analog Input Unit: CP1W-AD041
■ Analog I/O Unit: CP1W-MAD11
Note: 1. The voltage output and current output can be used at the same time for analog outputs, but the total output current must not exceed 21 mA.
Analog values that are input are converted to binary data and stored in the input area, or binary data is output as analog values.
Item
Number of inputs
Input signal range
Max. rated input
External input
impedance
Resolution
Overall
accura-
cy
Conversion time
A/D conversion
data
Averaging
Open-circuit
detection
Insulation resis-
tance
Dielectric
strength
Isolation method
Item
Analog
Input
Section
Analog
Output
Section
(See
note 1.)
Conversion time (See note 2.)
Isolation method
2. The conversion time is the total time for 2 analog inputs and 1 analog output.
25°C
0 to
55°C
Number o f inputs
Input signal range
Max. rated input
External input impedance
Resolution
Overall
accuracy
A/D conversion data
Averaging
Disconnection detection
Number of outputs
Output signal range
External output max. current
Allowable external output
load resistance
External input impedance
Resolution
Overall
accuracy
Data setting
D/A conversion data
Model
4
0 to 5 V, 1 to 5 V,
0 to 10 V, −10 to 10 V
±15 V
1 MΩ min.
6000
±0.3% of full scale
±0.6% of full scale
2.0 ms/point
Binary data with resolution of 6,000
Full scale for −10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Supported.
Supported.
20 MΩ. min. (at 250 VDC, between isolated circuits)
500 VAC for 1 min (between isolated circuits)
Photocoupler isolation (between analog inputs and
secondary internal circuits).
No isolation between input signals.
Input voltage
25°C
0 to 55°C
25°C
0 to 55°C
Model
CP1W-AD041
2 inputs
0 to 5 V, 1 to 5V, 0 to 10 V, or −10 to 10V
±15 V
1 MΩ min.
1/6000 (full scale)
±0.3% of full scale
±0.6% of full scale
Binary data (hexadecimal, 4 digits)
−10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Supported (Set for each input using a DIP switch.)
Supported
1 output
1 to 5 V, 0 to 10 V, −10 to 10 V
---
1 kΩ min.
0.5 Ω max.
1/6000 (full scale)
±0.4% of full scale
±0.8% of full scale
---
Binary data (hexadecimal, 4 digits)
−10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
2 ms/point (6 ms for all points)
Photocoupler isolation between analog I/O and internal circuits (There is no isolation between the analog I/O signals.)
0 to 20 mA
4 to 20 mA
±30 mA
Approx. 250 Ω
±0.4% of full scale
±0.8% of full scale
Input current
Voltage I/O
■ Analog Output Unit: CP1W-DA041
Item
Number of
outputs
Output signal
range
Allowable exter-
nal output load
resistance
External output
impedance
Resolution
Overall
accura-
cy
Conversion time
D/A conversion
data
Insulation resis-
tance
Dielectric
strength
Isolation method
CP1W-MAD11
25°C
0 to
55°C
Model
0 to 20 mA, 4 to 20 mA
±30 mA
250 Ω
±0.4% of full scale
±0.8% of full scale
0 to 20 mA, 4 to 20 mA
600 Ω max.
---
4
0 to 5 V, 0 to 10 V,
or −10 to 10 V
2 kΩ min.
0.5 Ω max.
6000
±0.4% of full scale
±0.8% of full scale
2.0 ms/point
Binary data with resolution of 6,000
Full scale for −10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
20 MΩ min. (at 250 VDC between isolated circuits)
500 VAC for 1 min between isolated circuits
Photocoupler isolation between analog inputs and
secondary internal circuits.
No isolation between analog input signals.
Input voltage
Current I/O
CP1W-DA041
0 to 20 mA or 4 to 20 mA
350 Ω max.
---
Input current

Related parts for CP1WAD041