S8VS-18024BE Omron, S8VS-18024BE Datasheet

no-image

S8VS-18024BE

Manufacturer Part Number
S8VS-18024BE
Description
POWER SPLY SW 100-240VAC 7.5A
Manufacturer
Omron
Series
S8VSr
Datasheet

Specifications of S8VS-18024BE

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
180W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 7.5A
2nd Output
-
3rd Output
-
4th Output
-
Size / Dimension
4.93" L x 2.95" W x 4.53" H (125mm x 75mm x 115mm)
Operating Temperature
-10°C ~ 60°C
Power (watts) - Max
180W
Efficiency
80%
Approvals
CE, CSA, cUL, EN, UL, VDE
Line Regulation
-
Load Regulation
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8VS18024BE
Z3187
60/90/120/180/240/480-W Models
New Models with Indication
Monitor and Simple Functions
for Easy System
Commissioning
15/30-W Models
Compact, Thin Power Supplies
That Mount Just About Anywhere
to Contribute to Control Panel
Downsizing
Features Common to All Models
• New 90-W models with indication monitor that
• New models with screwless terminal blocks
• Status displayed on 3-digit, 7-segment display.
• Safety standards:
• Input conditions: DC input is also possible from 80 to 370 VDC (BE models only, not compliant with EC Directives
• Compact and thin: 22.5 × 85 × 96.5 mm (W × H × D).
• Three mounting directions
• Mounting directly to the panel is possible.
• Safety standards:
• Mount to DIN Rail.
• Complies with SEMI F47-0706 (200-VAC input).
• RoHS-compliant.
Switch Mode Power Supply
S8VS
conform to UL Class 2 Output standards.
and indication monitor.
UL508/60950-1,
CSA C22.2 No. 14/60950-1
(15-W and 30-W models),
CSA C22.2 No. 107.1/60950-1
(60-W to 240-W and 480-W models),
EN 50178 (= VDE0160)
and other safety standards).
(standard, horizontal, facing horizontal).
UL508/60950-1/1604, cUL: CSA C22.2 No. 14/60950-1/213,
EN50178 (= VDE0160).
New Product
(15/30/60/90/120/180/240/480-W Models)
!
Refer to Safety Precautions for All Power Supplies and Safety
Precautions on page 31.
1

Related parts for S8VS-18024BE

S8VS-18024BE Summary of contents

Page 1

... New Product Switch Mode Power Supply S8VS (15/30/60/90/120/180/240/480-W Models) 60/90/120/180/240/480-W Models New Models with Indication Monitor and Simple Functions for Easy System Commissioning • New 90-W models with indication monitor that conform to UL Class 2 Output standards. • New models with screwless terminal blocks and indication monitor. • ...

Page 2

... S8VS Model Number Structure Model Number Legend Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below. S8VS- @@@@@@@@-@ Power Ratings 015 030 060 090 120: 120 W 180: 180 W 240: 240 W 480: 480 W 2. Output voltage Indication monitor None: Without indication monitor (standard model) ...

Page 3

... Model number (screw terminal block) (screwless terminal block) S8VS-06024B S8VS-06024B-F S8VS-09024BE S8VS-09024BE-F S8VS-09024BES S8VS-09024BES-F S8VS-09024B S8VS-09024B-F S8VS-09024BS S8VS-09024BS-F S8VS-09024BP S8VS-09024BP-F S8VS-09024BPS S8VS-09024BPS-F S8VS-12024BE S8VS-12024BE-F S8VS-12024B S8VS-12024B-F S8VS-12024BP S8VS-12024BP-F S8VS-18024BE S8VS-18024BE-F S8VS-18024B S8VS-18024B-F S8VS-18024BP S8VS-18024BP-F S8VS-24024BE S8VS-24024BE-F S8VS-24024B S8VS-24024B-F S8VS-24024BP S8VS-24024BP-F S8VS-48024B S8VS-48024B-F 3 ...

Page 4

... Power Supply and be sure that the load is not damaged. *4. The overvoltage protection of the S8VS-015 @@ uses a zener diode clamp. If the internal feedback circuit is destroyed by any chance, the load may be destroyed by the clamped output voltage (approx. 140% to 190% of the rated output voltage). ...

Page 5

... Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B Conforms to EN61204-3 high severity levels UL: UL508 (Listing), UL60950-1 UL: UL508 (Listing; Class 2 Output: Per UL1310), UL for S8VS-09024S-@@@S-@ only: UL508 (Listing, Class 2 Output: Per UL60950-1 UL1310), UL60950-1 cUL: CSA C22.2 No.107.1 (Class 2 Output: Per cUL: CSA C22.2 No.107.1 CSA C22 ...

Page 6

... S8VS Power ratings Item Efficiency (typical) (rated input voltage) Voltage *1 Frequency *1 With 100-VAC input Current With 200-VAC input Power factor Input Harmonic current regulation With 100-VAC input Leakage current With 200-VAC input With 100-VAC input Inrush current *2 With 200-VAC input Voltage adjustment range *3 ...

Page 7

... Conforms to EN61204-3 high severity levels UL: UL508 (Listing), UL60950-1 cUL: CSA C22.2 No.107.1, cUR: CSA No. 60950-1, EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil 1) *12 KOSHA S Mark *10 F47-0706 (200-VAC input) 1,150 g max. S8VS 480 W Maintenance Total run time Standard forecast monitor monitor 83% min. 7.4 A max. ...

Page 8

... Drive control circuit S8VS-06024A (60 W) S8VS-06024B (60 W) Fuse 3. (L) INPUT Noise filter AC (N) Inrush current protection circuit Drive control circuit S8VS-06024A-F (60 W) S8VS-06024B-F (60 W) Fuse 6 (L) INPUT Noise filter AC (N) Inrush Rectifier current protection circuit Drive control circuit 8 Undervolt- ...

Page 9

... Drive control circuit Photocoupler +V DC OUTPUT −V Rectifier/smoothing circuit Overcurrent Current detection circuit circuit Voltage detection circuit Overvoltage detection circuit Sinking type (S8VS-09024A, S8VS-09024B) Display circuit Switch Alarm DC Low Arithmetic operation circuit Yrs/kh Rectifier/smoothing circuit Common Photocoupler +V DC OUTPUT −V Rectifier/smoothing circuit ...

Page 10

... Sourcing type (S8VS-12024AP-F, S8VS-12024BP-F) Display circuit Switch Alarm DC Low Arithmetic operation circuit Yrs/kh Rectifier/smoothing circuit Common Photocoupler +V DC OUTPUT −V Type with no alarm output (S8VS-12024BE-@) Display circuit Switch Arithmetic operation circuit Rectifier/smoothing circuit Alarm DC Low Yrs/kh Common Alarm DC Low Yrs/kh Common ...

Page 11

... Display circuit Alarm Alarm DC Low DC Low Arithmetic operation circuit Yrs/kh Rectifier/smoothing circuit Common Sourcing type (S8VS-18024AP-F, S8VS-18024BP-F) Switch Display circuit Alarm DC Low Arithmetic operation circuit Yrs/kh Rectifier/smoothing circuit Common Type with no alarm output (S8VS-18024BE-@) Display circuit Switch Arithmetic operation circuit Rectifier/smoothing circuit 11 ...

Page 12

... Sourcing type (S8VS-24024AP-F, S8VS-24024BP-F) Display circuit Switch Alarm DC Low Arithmetic operation circuit Yrs/kh Rectifier/smoothing circuit Common Photocoupler + OUTPUT −V Type with no alarm output (S8VS-24024BE-@) −V Display circuit Switch Arithmetic operation circuit Rectifier/smoothing circuit Alarm DC Low Yrs/kh Common Alarm DC Low Yrs/kh Common ...

Page 13

... Noise filter AC (N) Inrush current Harmonic Rectifier protection current circuit suppression Drive control circuit Overcurrent detection circuit S8VS-48024-@ (480 W) S8VS-48024A-@ (480 W) S8VS-48024B-@ (480 W) Fuse 12A AC (L) INPUT Noise filter AC (N) Inrush Rectifier current protection circuit +V DC OUTPUT −V Smooth- Rectifier/smoothing circuit ...

Page 14

... Output voltage adjuster (V.ADJ) 6 *1. The fuse is located on the (L) side NOT user-replaceable. *2. This is the protective earth terminal specified in the safety standards. Always ground this terminal. 3 Note: The S8VS-01505 is shown above. Engineering Data (15-W, 30-W Models) Derating Curve S8VS-015@@ 120 100 80 ...

Page 15

... The values shown in the above diagram is for reference only. Note not turn ON the power again until the cause of the overvoltage has been removed. 2. The overvoltage protection of the S8VS-015@@ uses a zener diode clamp. The output voltage will be clamped at approx. 140% or higher of the rated output voltage. If the ...

Page 16

... Standard Model Models with Indication Monitor S8VS-24024 S8VS-24024@@@ Note: The S8VS-24024A is shown above. * The terminal arrangement is the same for models with screwless terminal blocks and standard models. 16 (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models) No. AC Input terminals 1 (L), (N) Protective Earth ...

Page 17

... S8VS-48024 1 2 Models with Indication Monitor S8VS-48024 Note: The illustration shows the S8VS-48024A model. * The terminal arrangement is the same for models with screwless terminal blocks and standard models. No. Name AC Input terminals 1 (L), (N) Protective Earth 2 terminal (PE) DC Output terminals 3 (−V), (+V) Output indicator ...

Page 18

... Maintenance forecast Note: 1. Press and hold the (9) Up Key U or (10) Down Key D for two seconds or more to increase or decrease the value rapidly. 2. The S8VS-06024@ is not provided with the setting mode and its parameters are fixed at the shipment setting. 18 and Models with Total Run Time Monitor (S8VS-@@@24B@@/ ...

Page 19

... The above displays are for models with a maintenance forecast monitor (S8VS-@@@24A@@). Multiple Alarms When two or more different alarms occur at the same time Operation Mode ...

Page 20

... OFF (no continuity). Replace the power supply if this condition occurs even if the output is correct, as internal parts may be deteriorated. h\t 4. The “ ” error detection function is only for the S8VS-@@@24A@@. 20 Output status Restoration method No change Automatic reset ...

Page 21

... Maintenance Forecast (S8VS-@@@24A@@) Displays when the maintenance forecast has reached the set value. Operation Mode The maintenance forecast has reached the set value. Maintenance forecast monitor (See note.) Output voltage Note: This indicator alternately Output current Peak-hold current Indication and Output When the Product is purchased, “ ...

Page 22

... Capacity level at replacement Capacity of Capacitor Maintenance forecast monitor output Note: This function can be set only on the S8VS-09024A@@, S8VS-12024A@, S8VS-18024A@, S8VS-24024A@, and S8VS-48024A. Principle of Operation The deterioration speed of the electrolytic capacitor varies considerably according to the ambient temperature. (Generally the speed follows “Rule of Two for every 10°C”; for every 10°C increase in temperature the rate of degradation doubles according to Arrhenius’ ...

Page 23

... OFF, i.e., no continuity at the total run time output terminal (kh)) The alarm set value can be changed in the setting mode. The S8VS-09024BE@, S8VS-12024BE, S8VS-18024BE, and S8VS- 24024BE do not have an alarm output. Example: Alarm Displays When a Total Run Time Set Value Reached Note: The total run time cannot be reset ...

Page 24

... Power Supply fails excessive voltage that is approximately 130% of the rated voltage (but approximately 110% of the rated voltage for the S8VS-09024@@@S) or more is output, the output voltage is shut OFF. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again. ...

Page 25

... S8VS-06024A/S8VS-06024B/S8VS-@@@24BE@). (Output voltage drop = OFF, i.e., no continuity at the undervoltage output terminal (DC LOW).) Example: Outputting an Alarm When the Voltage Output by the S8VS-09024A@@ Drops to the Set Value (19 Lower In the case that the output voltage drops below the set value (19.0 V) and an alarm is issued Note: 1 ...

Page 26

... S8VS-09024A@ (90 W) /S8VS-09024A@S (90 W) /S8VS-12024A@ (120 W) S8VS-09024B@ (90 W) /S8VS-09024B@S (90 W) /S8VS-12024B@ (120 W) S8VS-09024BE (90 W) /S8VS-09024BES (90 W) /S8VS-12024BE (120 W) Note: The illustration is the S8VS-12024A model. S8VS-18024 (180 W) S8VS-18024A@ (180 W) S8VS-18024B@ (180 W) S8VS-18024BE (180 W) Note: The illustration is the S8VS-18024A model. 26 Five, M3.5 terminal screws with square washers 10 35 ...

Page 27

... S8VS-06024A-F (60 W) S8VS-06024B-F (60 W) Note: The illustration shows the S8VS-06024-F model. S8VS-09024-F (90 W) /S8VS-09024S-F (90 W) /S8VS-12024-F (120 W) S8VS-09024A@-F (90 W) /S8VS-09024A@S-F ( /S8VS-12024A@-F (120 W) S8VS-09024B@-F (90 W) /S8VS-09024B@S-F (90 W) /S8VS-12024B@-F (120 W) S8VS-09024BE-F (90 W) /S8VS-09024BES-F (90 W) /S8VS-12024BE-F (120 W) 35.4 Note: The illustration shows the S8VS-12024-F model. ...

Page 28

... S8VS S8VS-18024-F (180 W) S8VS-18024A@-F (180 W) S8VS-18024B@-F (180 W) S8VS-18024BE-F (180 W) Note: The illustration shows the S8VS-18024-F model. S8VS-24024-F (240 W) S8VS-24024A@-F (240 W) S8VS-24024B@-F (240 W) S8VS-24024BE-F (240 W) Note: The illustration shows the S8VS-24024-F model. S8VS-48024-F (480 W) S8VS-48024A-F (480 W) S8VS-48024B-F (480 W) Note: The illustration shows the S8VS-48024-F model. ...

Page 29

... Note: If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from aluminum abrasion. PFP-100N PFP-50N 1,000 (500 Values in parentheses are for the PFP-50N. PFP-100N2 1,000 PFP-M 10 6.2 1.8 M4×8 pan- head screw 1 35.5 35.5 1.8 11.5 10 1.3 M4 spring washer 4.8 7.3 ± 0.15 35 ± 27 ± 0.3 0.15 15( ± 0 29.2 1 1.5 S8VS 29 ...

Page 30

... S8VS Mounting Brackets Side-mounting Bracket (for 15- and 30-W models) Side-mounting Bracket (for 60-, 90-, and 120-W models) Side-mounting Bracket (for 180-W models) Side-mounting Bracket (for 240-W models) Front-mounting Bracket (for 60-, 90-, 120-, 180-, and 240-W models) * Note: Brackets cannot be used for 480-W models. ...

Page 31

... Make sure that the wires are securely connected to the terminal block after wiring. Never insert wires into the tool insertion holes. 3.7 mm • Use the following material for the wires to be connected to the S8VS to prevent smoking or ignition caused by abnormal loads. Recommended Wire Type 15-W and 30-W Models Model ...

Page 32

... It may take from several years to more than 10 years under general operating conditions for the power supply to output the maintenance forecast monitor alarm (S8VS-@@@24A@@). The total run time monitor (S8VS-@@@24B@@/S8VS-@@@24BE@) may be a similar number of years as the maintenance forecast monitor according to some settings ...

Page 33

... A harmonic current suppression circuit is built into the Power Supply. This circuit can create noise when the input is turned ON, but it will last only until the internal circuits stabilize and does not indicate any problem in the Product. +V −V +V −V Incorrect AC ( (N) − (N) −V S8VS 33 ...

Page 34

MEMO ...

Page 35

... Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority ...

Page 36

... São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON ELECTRONICS MEXICO • HEAD OFFICE Apodaca, N.L. • 52.811.156.99.10 • 001.800.556.6766 • mela@omron.com OMRON EUROpE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.industrial.omron.eu Cat. No. T026-E1-05 01/11 OMRON ARGENTINA • ...

Related keywords