Specifications of CR4160-100

Current - Sensing
100A
Accuracy
±0.5%
Sensitivity
-
Current - Supply
40mA
Sensor Type
Current Sensor
Voltage - Supply
24V
Output
4 ~ 20mA DC
Frequency
20Hz ~ 4kHz
Response Time
250ms
Polarization
Unidirectional
Operating Temperature
0°C ~ 50°C
Package / Case
Module
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
C
True RMS AC Current Transducer
Another HUNTINGTON ELECTRIC Company
DIN RAIL / PANEL MOUNT, TRUE RMS
CR4110(S)
CR4111(S)
CR4120(S)
CR4150
CR4160
CR4170
CR4180
CR4110 CR4120
CR4111
CR4150
CR4170
Single Element - 0.79” Window
Three Element - 0.26” Window
Two Element - 0 .26” Window
0.5 to 150 AAC Input Range
0.5 to 30 AAC Input Range
0.5 to 30 AAC Input Range
* Two and three element transducers are available only in ranges of 0.5 to 30 AAC
CR4160
CR4180
-
-
-
-
-
-
-
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
PART NUMBERS
Single element with 4 - 20 mADC output (split core design)
Single element with 0 - 10 VDC output (split core design)
Single element with 0 - 5 VDC output (split core design)
Three element with 4 - 20 mADC output *
Two element with 4 to 20 mADC output *
Three element with 0 - 5 VDC output *
Two element with 0 - 5 VDC output *
The CR4100 Series True RMS Current Transducers and
Transmitters are designed for applications where AC
current waveforms are not purely sinusoidal. More
precise and accurate than other transducers, these
devices are ideal in chopped wave and phase fired
control systems.
Applications
Phase fired controlled heaters
Quickly varying motor loads
Chopped wave form drivers
Harmonic currents
Features
35mm DIN Rail or Panel Mount
Available with 0 - 5 VDC or 4 - 20 mA DC outputs
24 VDC powered
Use with external current transformers
Highest precision available
Connection diagram printed on case
Regulatory Agencies
Approved to UL3111-1, First Edition, Amendment 2
Approved to CAN/CSA-C22.2, No. 1010.1-92
Meets requirement of IEC 61010-1 and BS EN 61010-1
26
Simply put an “S” at the end of the prefix*
All single element current transducers are
* UL Recognition Pending
available in split core design.
E-mail: sales@crmagnetics.com
Add suffix for input range
other ranges available
100
150
10
20
25
30
40
50
75
15
.5
5
E199795
-
-
-
-
-
-
-
-
-
-
-
-
0-25 AAC
0-30 AAC
0-.5 AAC
0- 5 AAC
0-10 AAC
0-15 AAC
0-20 AAC
0-40 AAC
0-50 AAC
0-75 AAC
0-100 AAC
0-150 AAC
*
*
*
*
*
*
*

Related parts for CR4160-100

CR4160-100 Summary of contents

Page 1

... CR4110(S) - CR4111(S) - CR4120(S) - CR4150 - CR4160 - CR4170 - CR4180 * Two and three element transducers are available only in ranges of 0 AAC CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119 Web: http://www.crmagnetics.com Another HUNTINGTON ELECTRIC Company The CR4100 Series True RMS Current Transducers and Transmitters are designed for applications where AC current waveforms are not purely sinusoidal ...