20062-85 Deltrol Controls, 20062-85 Datasheet

no-image

20062-85

Manufacturer Part Number
20062-85
Description
Series Relay 5 And 10 Amp General Purpose
Manufacturer
Deltrol Controls
Datasheet
6
FEATURES
CONTACT DATA
CONFIGURATION:
MATERIALS:
CONTACT RATINGS
**UL/CSA On 100U/101U Series Only
**3 Pole Devices Rated at 6-2/3 Amp When Switching
UL RECOGNIZED FILE NO.: E37066 (100U/101U Only)
CSA CERTIFIED FILE NO.: LR20690 (100U/101U Only)
EXPECTED LIFE
Electrical At Rated Load (Minimum)
Mechanical Life
DIELECTRIC STRENGTH
CONTACT SIZE CONFIGURATION
Gold Diffused Available on Special Order – Min. Qty. Req’d.
Greater Than 150VAC, Unless Polarity is the Same on
All Poles
3/16" Diameter
1/8" Diameter
MOVEABLE
Class F Coil Insulation System for 155°C
Total Temperature
Coil Molded in DuPont Rynite
Protection
Unique Armature Stop Maintains Adjustment
Thru 3PDT
5 AMP:
1/8" Diameter Moveable Fine Silver
3/16" Diameter Stationary Fine Silver
10 AMP:
3/16" Diameter Moveable Silver Cadmium Oxide
3/16" Diameter Stationary Fine Silver
100,000 Operations
10,000,000 Operations
800 VRMS, 60 Hz Between Contacts
1500 VRMS (Model 100), 2200 VRMS
(Model 100U/101U), 60 Hz Between Other Elements
Gold Flash is Standard on All Contacts
thru 3PDT
thru 3PDT
POLE
100U/101U
®
for Environmental
1/8 HP or 5 amp at
1/4 HP or 5 amp at
5 amp at 28VDC
10 amp or 1/3 HP
1/2 HP or 10 amp at
10 amp at 28VDC
120VAC
277VAC
at 120VAC**
277VAC
RATINGS*
UL
100
MODELS
100:
100RF: With Diallyl Phthalate Panel For Switching RF
100U:
101U:
101UP: 10 Amp Unit with Printed Circuit Terminals
COIL DATA
Coil Voltages:
Coil Treatment: Molded Rynite
Insulation Resistance: 100 Megohms Minimum
UL Insulation System File No.: E74443
OPERATE DATA
Pick Up (at 25°C): AC Volts 85% or Less of Nominal
Operate Time:
Release Time:
ENVIRONMENTAL DATA
Operating Ambient: AC: -45° to 70°C
Coil Temperature Rise: (25°C Ambient – Continuous Duty)
MECHANICAL DATA
Terminals: 100/100U/101U Pierced Solder Lugs .125" x .032"
Weight:
Pole Units
Pole Units
Pole Units
AC Coils
AC Coils
DC Coils
Single
2 & 3
S155D 155°C Total Temperature Std.
(Covers S105 Class A and S130D Class B Requirements)
1-3
5 & 10 Amp with Solder Lug Terminals
5 Amp Unit with UL and CSA Recognition
10 Amp Unit with UL and CSA Recognition
100UP/101UP Printed Circuit Pins
All Versions Approx. 2.0 oz. (57 g)
AC: 45°C Approx. @ 60 Hz – Use at 50 Hz
DC: 25°C Approx.
DIVISION OF DELTROL CORP.
VOLTAGE
NOMINAL
SERIES RELAY
5 AND 10 AMP
GENERAL PURPOSE
110VDC
120VAC
240VAC
120VAC
240VAC
12VDC
24VDC
48VDC
12VAC
24VAC
48VAC
12VAC
24VAC
48VAC
AC: Up to 277 Volts/60 Hz
DC: Up to 125 Volts
will Cause Slight Increase in Coil Rise
6VDC
6VAC
6VAC
DC Volts 75% or Less of Nominal
Approx. 15 Milliseconds
Approx. 15 Milliseconds
DC: -45° to 85°C
RESISTANCE
®
IN OHMS
10,000
Std. Class F
± 10%
2025
8000
1850
7200
1850
315
285
120
480
5.0
4.5
20
80
18
72
30
NOMINAL
POWER
2.0VA
2.2VA
COIL
1.2W

Related parts for 20062-85

Related keywords