ICM450 ICM, ICM450 Datasheet

no-image

ICM450

Manufacturer Part Number
ICM450
Description
3-Phase Voltage Monitor
Manufacturer
ICM
Datasheet
www.DataSheet4U.com
LIS39-2
315.233.5266
Phone
At power up, the ICM450 evaluates the incoming power for proper phase sequence, amplitude, and symmetry (voltage
unbalance). If the three phase input at the line side connections is within user-set parameters, the load energize LED is
turned on and the internal relay is energized. Continuity will be across terminals 4 and 6. If connections are made to the
load side terminals, the ICM450 will transfer monitoring over to the load side only.
When a critical fault condition (phase loss or phase reversal) is present, the relay will immediately de-energize, the load-
energized LED will turn off, the fault LED will flash, and the fault is written to memory. Continuity will be across terminals
4 and 5.
If a non-critical fault condition (unbalance, high or low voltage) is present, the ICM450 will ignore it during the interro-
gation delay time. If it is still present following the interrogation delay time, the relay will de-energize, the load-energized
LED will turn off, the fault LED will flash, and the fault is written to memory. Continuity will be across terminals 4 and 5.
The ICM450 will store the last 25 faults in memory. The relay will not energize if any fault conditions exist. The integral
adjustable delay on break timer will prevent short cycling.
• Reliable, high temperature LCD display
• Simultaneous voltage display (an ICM exclusive)
• Fully adjustable variables
• 25-fault memory and storage
• Ultra bright LED indicators
• Easy to install and configure
Stop Motor Burnouts!
Programmable 3-phase line voltage monitor
with 25-fault memory, high temperature LCD
display, easy setup & clear, diagnostic readout
of system faults, 190 to 630 VAC operation...
The ICM450 was specifically designed to protect motors and
other 3-phase loads from premature failure and damage due
to common voltage faults such as voltage unbalance, over/
under voltage, phase loss, reversal, incorrect sequencing and
rapid short cycling.
Features
Mode of Operation
– Simplifies system setup and diagnostics. Indicates
– Temperature: -20°C to +75°C (-4°F to + 167°F)
– View all 3 phases, no need to scroll through readouts.
– User may easily set and adjust variables in SETUP
– Clearly displayed on LCD
– Shows current mode:
– Simple 7-step push-button setup
– Wiring diagram on unit
– Installation and application guide included
condition of incoming line voltage, fault conditions,
system setpoints and other user adjustments.
mode:
• Line voltage: 190 to 600 VAC
• Voltage unbalance: 2 to 20%
• Delay on break period: 0 to 10 minutes
• Fault interrogation: 0 to 15 seconds
• Over/under voltage: 2 to 25%
• Reset modes: AUTO or 0 to 10 retries
• Control mode: ON or OFF
• Setup LED
• Control voltage LED
T
visit us at: www.icmcontrols.com
HREE
800.365.5525
Application Assistance
• Load energized LED
• Fault LED
All features and specifications subject to change without notice.
-P
HASE
ICM450
V
OLTAGE
Wiring Diagram
* Thermostat, pressure switch, etc.
315.233.5276
M
Fax
ONITOR
Voltage
Control
L01
L02
L03
*
LI1
L0AD
LI2
LI3

Related parts for ICM450

ICM450 Summary of contents

Page 1

... LED will turn off, the fault LED will flash, and the fault is written to memory. Continuity will be across terminals 4 and 5. The ICM450 will store the last 25 faults in memory. The relay will not energize if any fault conditions exist. The integral adjustable delay on break timer will prevent short cycling. ...

Page 2

Specifications Input • Line Voltage: Universal (190-630 VAC) • Frequency: 50/60 Hz Output • Type: Relay • Form: SPDT • Voltage Range 240 VAC (maximum: 10 amps) • Frequency: 50/60 Hz Control Operating Temperature • Operating Temperature: -40ºC ...

Related keywords