cs1w-srm21 Omron Corporation, cs1w-srm21 Datasheet - Page 2

no-image

cs1w-srm21

Manufacturer Part Number
cs1w-srm21
Description
Cs-series Compobus/s Master Unit
Manufacturer
Omron Corporation
Datasheet
Communication Specifications
Ordering Information
International Standards
Specifications
* Uses Special I/O Unit Area (in CIO Area).
Communications method
Communications baud rate
Modulation method
Coding method
Error control checks
Cable
Communications
distance
CS1 Special
I/O Units
• The standards indicated in the "Standards" column are those current for UL, CSA, cULus, cUL, NK, and Lloyd standards and EC Directives as
Applicable PLC models
Unit type
Internal current consumption
Weight
I/O points
Allocated words *
No. of mountable Master Units
Node address
No. of connectable Slaves
Status information
of the end of October 2008. (The standards are abbreviated as follows: U: UL, U1: UL Class I Division 2 Products for Hazardous Locations, C:
CSA, US: cULus Class I Division 2 Products for Hazardous Locations, CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
Ask your OMRON representatives for the conditions under which the standards were met.
Unit type
CompoBus/S
Master Unit
Name
VCTF cable (JIS C 3306)
Special Flat Cable
2-conductor VCTF cable
4-conductor VCTF cable
Special Flat Cable
Item
Remote I/O
communications
Communications
CS-series PLCs
CS1 Special I/O Unit
5 VDC, 150 mA max.
167g max.
256 (128 inputs and 128 outputs)
20 words (8 for inputs, 8 for outputs, 4 for status)
95
8 addresses per node
32
Communications Error Flags, Participation Flags
functions
Special CompoBus/S protocol
High-speed Communications Mode: 750 kbps
Long-distance Communications Mode: 93.75 kbps
Baseband method
Manchester coding method
Manchester code check, frame length check, and parity check
Two 0.75 mm
Four 0.75 mm
Four 0.75 mm
High-speed Communications Mode
Main line length:
Branch line length:
Total branch line length:
Long-distance Communications Mode
Main line length:
Branch line length:
Total branch line length:
High-speed Communications Mode
Main line length:
Branch line length:
Total branch line length:
Long-distance Communications Mode: Flexibly branched, provided that the total length of cable is a maximum
of 200 m.
High-speed Communications Mode
Main line length:
Branch line length:
Total branch line length:
When 4-conductor VCTF cable or Special Flat Cable is used to connect fewer than 16 Slaves, the main line can
be up to 100 m long and the total branch line length can be up to 50 m in High-speed Communications Mode.
Long-distance Communications Mode: Flexibly branched, provided that the total length of cable is a maximum
of 200 m.
256 max.
(128 inputs and 128 outputs)
128 max.
(64 inputs and 64 outputs)
Specifications
No. of I/O points
2
2
2
conductors (2 signal wires)
conductors (2 signal wires and 2 power supply wires)
conductors (2 signal wires and 2 power supply wires)
100 m max.
3 m max.
50 m max.
500 m max.
6 m max.
120 m max.
30 m max.
3 m max.
30 m max.
30 m max.
3 m max.
30 m max.
per CPU Unit
mountable
Max. Units
95
96
Specification
128 (64 inputs and 64 outputs)
10 words (4 for inputs, 4 for outputs, 2 for status)
96
No. of unit
allocated
numbers
2
1
consumption (A)
0.15
5 V
Current
24 V
CS1W-SRM21
CS1W-SRM21 U, C, CE
Model
Standards
2

Related parts for cs1w-srm21