zen-20c2dt-d-v2 Omron Corporation, zen-20c2dt-d-v2 Datasheet - Page 13

no-image

zen-20c2dt-d-v2

Manufacturer Part Number
zen-20c2dt-d-v2
Description
Programmable Relay
Manufacturer
Omron Corporation
Datasheet
Units with DC Power Supply
Note: 1. Be sure to connect the COM terminal before turning ON the power supply. If the COM terminal is disconnected, or if the wiring is changed
CPU Units with 10 I/O Points
For Connections to Negative (−) Common (PNP Connection)
For Connections to Positive (+) Common (NPN Connection)
For Connecting Analog Input Devices to Input Terminals I4 and I5
Note: When connecting an analog input device, always connect the negative side to the COM terminal.
Note: When connected to the positive (+) common, I4 and I5 cannot be used as analog inputs.
2. Apply the power supply voltage through a relay or switch in such a way that the voltage reaches the rated value within 4 s. If the voltage
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
after turning ON the power supply, a malfunction may occur.
is applied gradually, the power may not be reset or unstable output operations may result.
+
CPU Unit with 10 I/O points
CPU Unit with 10 I/O points
CPU Unit with 10 I/O points
COM
COM
COM
I0
I0
I1
I1
I2
I2
I3
I3
I 4
I4
I5
I5
Input device
Input
device
ZEN V2 Units
13