TRIP CURVE - Approximate Time, Current Characteristics At 77°F (25°C)
DIMENSIONS - CDM
1000
500
100
1.145 [29.08]
2 AMP THRU 10 AMP
.10
.047 [1.19] REF. THK.
LOCKWASHER (2 PLACES)
BOTTOM VIEW
Dotted Lines:
Solid Lines:
1.586 [40.28]
1.562 [39.67]
.430 [10.92]
.641 [16.28]
10 amps or below
Above 10 amps
.312 [7.93]
SEE NOTE 1
2.0 [
MIN. PANEL HOLE DIA.
1.221 [31.01]
1.159 [29.44]
.250 [6.35] LONG
#8-32 UNC-2A ROUND
HEAD SCREW (2 PLACES)
.562 [
.380 [9.65]
1
50.8]
14.27]
12½ AMP THRU 40 AMP
(DOES NOT INCLUDE SEALING GASKET)
BOTTOM VIEW
.906 [23.01]
OPTIONAL #8-32 UNC-2B
MOUNTING NUT
(2 PLACES)
Sensata Technologies Inc.
529 Pleasant Street
Attleboro, MA 02703, USA
Phone: +1 508-236-3287
http://www.sensata.com/
Trip Time in Seconds
INCHES [MM]
10
EYELET FOR
#10 SCREW
(2 PLACES)
Performance characteristics are based on room
temperature (77°F, 25°C). Consult Derating curve for
ambient temperatures significantly higher or lower than
standard room temperature.
Example: At 77°F (25°C) the device is calibrated to hold
at 100% of rated current (1) and trip at 135% of rated
current (2). At 140°F (60°C), the same device will hold
at approximately 78% of rated current (3), and trip at
approximately 115% of rated current (4).
DERATING CURVE
160˚F
140˚F
100˚F
-40˚F
-60˚F
70˚F
32˚F
0˚F
100
40
Important Notice: Sensata Technologies (Sensata) reserves
the right to make changes to or discontinue any product or
service identified in this publication without notice. Sensata
advises its customers to obtain the latest version of the
relevant information to verify, before placing any orders,
that the information being relied upon is current. Sensata
assumes no responsibility for infringement of patents or
rights of others based on Sensata applications assistance
or product specifications since Sensata does not possess
full access concerning the use or application of customers’
products. Sensata also assumes no responsibility for
customers’ product designs.
60
Ultimate Trip in % Rated Load
3
80
100
1
4
120
1000
2
140
77°F, 25°C
160
180
-18˚C
-40˚C
-51˚C
10,000
71˚C
60˚C
38˚C
21˚C
0˚C