h3de-s Omron Corporation, h3de-s Datasheet

no-image

h3de-s

Manufacturer Part Number
h3de-s
Description
Solid-state Timer
Manufacturer
Omron Corporation
Datasheet
DIN Track Mounted, Standard 22.5-mm Width Timer Range
• A wide AC/DC power supply range (24 to 230 VAC/DC) reduces the number of timer models kept in stock. (except for H3DE-H)
• 12-VDC model available for a specific application. (H3DE-M2)
• Nameplate provided for easy timer identification and management.
• Terminal clamp left open when delivered.
• Finger protection terminal block to meet VDE0106/P100.
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
• Incorporates environment-friendly, cadmium-free contacts. (except for H3DE-H)
• High immunity to inverter noise.
• Approved by UL and CSA.
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives.
■ Broad Line-up of H3DE Series
Solid-state Timer
H3DE
Standard Timer
H3DE-M
H3DE-S
H3DE-M/S
Solid-state Timer
Common to ALL Timers
H3DE-M/-S......................................................................................................................................
H3DE-F ...........................................................................................................................................
H3DE-G ..........................................................................................................................................
H3DE-H...........................................................................................................................................
Accessories.....................................................................................................................................
Precautions .....................................................................................................................................
Twin Timer
H3DE-F
H3DE-F
Contents
H3DE
Star-delta Timer
H3DE-G
H3DE-G
Power OFF-delay Timer
H3DE-H
12
18
24
30
31
H3DE-H
2
CSM_H3DE_DS_E_3_1
1

Related parts for h3de-s

h3de-s Summary of contents

Page 1

... Approved by UL and CSA. • Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives. ■ Broad Line-up of H3DE Series H3DE-M/S Standard Timer Twin Timer H3DE-F H3DE-M H3DE-S Solid-state Timer H3DE-M/-S...................................................................................................................................... H3DE-F ........................................................................................................................................... H3DE-G .......................................................................................................................................... H3DE-H........................................................................................................................................... Common to ALL Timers Accessories..................................................................................................................................... Precautions ..................................................................................................................................... ...

Page 2

... Solid-state Multi-functional Timer H3DE-M/-S • Eight operating modes (H3DE-M) and four operating modes (H3DE-S) cover a wide range of applications. • Programmable contact enables the building of a self-holding re- lay circuit (-@2 models). • A wide time setting range of 0. 120 h. Model Number Structure ■ Model Number Legend ...

Page 3

... Relay: SPDT Relay: DPDT Time unit display min 0.1 to 1.2 min 0 min VDC with resistive load (cosφ -25°C to 65°C (with no icing) H3DE-M/-S H3DE-S2 H3DE-S1 Relay: SPDT hrs 120 h 3 ...

Page 4

... IP30 (Terminal block: IP20) Weight 120 g Note: 1. With the H3DE-M@, if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes: Accuracy of operating time: ±1% ±50 ms max. at 1.2-s range Setting error: ±10% +100/-50 ms max. Signal input time: 100 ms min. ...

Page 5

... H3DE-M1/-M2 No input is available. Outputs are turned ON according to designated out- put mode when preset value is reached. (see note.) H3DE-M/-S Operating mode selector Output circuit Indicator circuit Power-ON Output indicator indicator Operating mode selector Output circuit Indicator circuit Power-ON Output indicator indicator H3DE-S1/-S2 5 ...

Page 6

... Timer (+) VDC (− Sensor Operates with NPN transistor ON and A must be more than 1 2 and A must be less than 1 2 and A must be within 1 2 H3DE-M/-S H3DE- (see note 25/ (see note 2) ...

Page 7

... Turn the operating mode selector with a screwdriver until the desired operating mode ( B2 for the H3DE-M and for the H3DE-S) appears in the operating mode display win- dow located below the selector. Selection of Time Unit and Time Scale ...

Page 8

... The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set. 3. There is no start input with H3DE-S@ models. Operation starts when the power is turned ON. 4. There is no instantaneous output with H3DE-M1/-S1 models. ...

Page 9

... Instantaneous contacts and 26 Instantaneous contacts and 28 Power indicator Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement on page 6). Timing chart t−a t−a t− ...

Page 10

... Timer gives output.) Operating mode selector (select a mode from B2 and G for the H3DE-M1/-M2, from and B2 for the H3DE-S1/S2) Power-on indicator (green) (Lit while the power is on.) Output type selector switch for H3DE-M2/-S2 (default setting is time-limit output) Nameplate for user use ( ...

Page 11

... ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. H3DE-M/-S Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON) Output type selector switch (default setting: Time-limit output) ...

Page 12

... Combinations of long ON- or OFF-time and short OFF- or ON- time setting are possible. • Long time range from 0 for both ON and OFF time settings. Model Number Structure ■ Model Number Legend H3DE - Twin timers Ordering Information ■ List of Models Operating mode Flicker-OFF/Flicker-ON start ■ ...

Page 13

... AC: Approx. 3 230 VAC DC: Approx. 0 VDC Contact output 250 VAC with resistive load (cosφ VDC with resistive load (cosf = 1) Operating: -10°C to 55°C (with no icing) Storage: -25°C to 65°C (with no icing) Operating: 35% to 85% H3DE-F min hrs 0 ...

Page 14

... EN55011 Group 1 class B EN61000-3-2 EN61000-3-3 EN61812-1 EN61000-4- contact discharge (level 3) EN61000-4- power port and output port (level 3) EN61000-4- common mode (level 3) H3DE air discharge (level control port with capacitive clamp (level differential mode (level 3) 14 ...

Page 15

... Outputs are turned ON/OFF according to the time set by the ON-and OFF-time setting dial. ■ Terminal Arrangement Note: DC supply voltage does not require the designation of polarity. OFF indicator ON/OFF start selector Indicator circuit ROM RAM Clock One-chip microcomputer (DIN notation H3DE-F Time unit selector Output circuit 15 ...

Page 16

... ON set time OFF set time OFF ON Power (A and OFF Output relay and 18 OFF (ON indicator) ON Output relay: NC OFF 15 and 16 ON OFF indicator OFF set time OFF set time OFF H3DE-F ON-time setting dial OFF-time setting dial 0.1 s min. 0.1 s min. 16 ...

Page 17

... OFF-time unit selector (select one from s, 10s, min OFF-time unit display window (Front View) ON/OFF Start Selector Switch Settings Setting Operating mode Flicker-ON start Flicker-OFF start (Bottom View) Terminal block (black) Terminal block (black) H3DE-F Surface color: Light gray 5Y7/1 (OMRON) 17 ...

Page 18

... Solid-state Star-delta Timer H3DE-G • A wide star-time range (up to 120 seconds) and star-delta trans- fer time range (up to 0.5 seconds) Model Number Structure ■ Model Number Legend H3DE - Star-delta timer Ordering Information ■ List of Models Supply voltage 24 to 230 VAC/VDC H3DE-G ■ ...

Page 19

... AC: Approx (1 230 VAC DC: Approx. 0 VDC Contact output 250 VAC with resistive load (cosφ VDC with resistive load (cosφ Operating: -10°C to 55°C (with no icing) Storage: -25°C to 65°C (with no icing) Operating: 35% to 85% H3DE-G 19 ...

Page 20

... EN55011 Group 1 class B EN61000-3-2 EN61000-3-3 EN61812-1 EN61000-4- contact discharge (level 3) EN61000-4- power port and output port (level 3) EN61000-4- common mode (level 3) H3DE air discharge (level control port with capacitive clamp (level differential mode (level 3) 20 ...

Page 21

... Star output is turned OFF when the dial set value is reached and delta output is ON after the preset transfer time elapses (DIN notation H3DE-G Star operation Output circuit Delta operation Delta operation indicator 21 ...

Page 22

... The operation time of the Timer is set with the time setting dial. 0 Star operation time setting Star-delta transfer time 2 Nameplate for user use (20 x 5.4 mm white panel) Time setting dial (for setting star operation time) Star-delta transfer time selector Star-delta transfer time display window (Front View) H3DE-G Time setting dial 22 ...

Page 23

... H3DE-G ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON) Terminal block (black) H3DE-G 23 ...

Page 24

... Supply voltage 100 to 120 VAC 200 to 230 VAC 24 VAC/VDC 48 VAC/VDC Note: Specify both the model number and supply voltage when ordering. Example: H3DE-H 24 VAC/DC S ■ Accessories (Order Separately) Mounting Track 50 cm (l) x 7 (l) x 7 (t) End Plate ...

Page 25

... AC: Approx. 1 230 VAC Contact output 250 VAC with resistive load (cosφ VDC with resistive load (cosφ Operating: -10°C to 55°C (with no icing) Storage: -25°C to 65°C (with no icing) Operating: 35% to 85% H3DE-H Min. power ON time 0.1 s minimum 0.3 s minimum 25 ...

Page 26

... EN55011 Group 1 class A EN61000-3-2 EN61000-3-3 EN61812-1 EN61000-4- contact discharge (level 3) EN61000-4- power port and output port (level 3) EN61000-4- common mode (level 3) H3DE air discharge (level control port with capacitive clamp (level differential mode (level 3) 26 ...

Page 27

... Timer is turned OFF and the output of the Timer is turned OFF when the preset time elapses. ■ Terminal Arrangement Note: DC supply voltage does not require the designation of polarity. Indicator Time scale circuit selector Oscillation Counting Output circuit circuit circuit (DIN notation H3DE-H 27 ...

Page 28

... Power indicator (green) Lit when the Timer is turned ON. Time Setting The operating time of the Timer is set with the time setting dial. Time setting dial Nameplate for user use (20 x 5.4 mm white panel) Time setting dial (for setting power OFF-delay time) (Front View) H3DE-H 28 ...

Page 29

... H3DE-H ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON) Terminal block (black) H3DE-H 29 ...

Page 30

... Accessories (Order Separately) (Common) Note: The following is common for all H3DE models. Note: All units are in millimeters unless otherwise indicated. ■ Dimensions Mounting Track PFP-100N, PFP-50N 7.3±0.15 4 Length 1 m PFP-100N 50 cm PFP-50N 1 m PFP-100N2 End Plate PFP ...

Page 31

... Rail stopper The H3DE can be mounted and dismounted with ease if a distance more is kept between the H3DE and the top surface of other equipment located below the H3DE. ■ Power Supplies The H3DE Series is provided with a transformerless power supply system ...

Page 32

... Wiring (H3DE-H) The H3DE has a high impedance circuit. Therefore, the H3DE may not be reset if the H3DE is influenced by inductive voltage. In order to eliminate any influence of inductive voltage, the wires connected to the H3DE must be as short as possible and should not be installed alongside power lines ...

Page 33

... Operation (H3DE-H) An interval minimum is required to turn on the H3DE after the H3DE is turned off. If the H3DE is turned on and off repeatedly with an interval of shorter than 3 s, the internal parts of the H3DE may deteriorate and the H3DE may malfunction min. Power ...

Page 34

... OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ Read and Understand This Catalog Warranty and Limitations of Liability Application Considerations Disclaimers In the interest of product improvement, specifications are subject to change without notice. (c)Copyright OMRON Corporation 2008 All Right Reserved. 2008.11 ...

Related keywords