Safety Isolation System
ElectroGuard
Overview
The ElectroGuard Safety Isolation System is used in place of a
disconnect switch for Lockout and Tagout (LOTO). It uses power
contactors and Remote Lockout Stations to accomplish LOTO.
Isolating the electrical energy usually involves calling an electrician to
turn “Off ” the main disconnecting means. The electrician would
then perform LOTO of the disconnecting means operating handle.
This same procedure is required to perform cleaning, maintenance,
setup, lubrication or adjustment. Machines or processes with
multiple access points may require operator/maintenance
intervention several times a shift (perhaps as often as 60 times per
shift).
To perform these activities, the operator/maintenance person may
be required to place part of his or her body into an area not accessed
during normal operation. This may cause serious or fatal injury if
LOTO procedures are not followed.
The ElectroGuard Safety Isolation System allows the machine
operator to safely and quickly accomplish LOTO with dramatically
reduced downtime.
Provides Energy Isolation
• Power isolation accomplished by means of contactors rather than
• Uses redundant, independent and self-monitoring circuits to
• Prevents accumulation of faults in order to maintain the integrity
• Tamper-resistant design.
Convenient Remote Lockout Station
• Allows remote isolation of the electrical power to the machine or
• A light on the Remote Lockout Station indicates that the three-
• If a fault occurs in the Safety Isolation System, the “System
• Easy Lockout/Tagout.
Certified by TUV to meet requirements of Category 4
• Certified by TUV to meet Category 4, the most stringent safety
• Subjected by TUV to rigorous third party testing and verification
12-2
disconnect switches.
detect a system fault.
of the safety system.
process—machine operator simply turns “Off ” a Remote
Lockout Station.
phase power source to the machine or process has been isolated.
No Light Means No Entry.
Isolated” light on the Remote Lockout Stations will not
illuminate.
category defined within International Standard EN 954-1/ISO
13849-1.
of the Failure Mode & Effect Analysis (FMEA).
Status Communication Capability to a Remote PLC
• Optional Remote I/O via Flex modules. Communication can be
Available from 23-1200 Amperes.
Specifications
Approvals
Standards
Estimated Component Life
Environmental
Power Panel Construction
Remote Lockout Station
Construction
Expansion Module
Construction
Safety Isolation Sys. Inputs
System Operational Limits
Use of any of these input devices will not meet Lockout/Tagout (LOTO)
via the DeviceNet communication platform or the Remote I/O
communication platform.
requirements.
Remote Lockout Station 250,000 operations
(Isolation & Grounding) 110A-1200A: 1,000,000 operations
Operating Temperature 0°C...+40°C (32°F...104°F) (Ambient)
Rockwell Automation
Storage Temperature -10°C...+60°C (14°F...140°F)
Standard Inputs from Remote Lockout Stations
Optional Inputs from
Power Contactors 23A - 85A: 2,000,000 operations
Relative Humidity,
Non condensing 90% Relative Humidity
Safety Products
C
TUV Rheinland certified; CE marked
for all applicable directives
IEC/EN 60204-1; IEC/EN 60439-1;
Category 4 to International Standard
EN 954-1/ISO 13849-1; 98/37/EC
Machinery Directive; 89/336/EC EMC
Directive; 73/23/EC Low Voltage
Directive; Fulfils the function of an
energy isolating device in accordance
with the conditions set forth in the
FedOSHA letter of interpretation
pertaining to Section 1910.147(b);
Cal/OSHA 3314.
Tamper-resistant Control Module
23A-85A systems support up to 4
Remote Lockout Stations without an
110A-1200A systems support up to 6
Control Module with viewing window
for visual check of status indicator lights
Top and bottom 25.4mm (1.0in)
Sealing provision for tamper-resistance
Operating handle accepts up to 3
padlocks
4 port—supports up to 4 lockout
stations
10 port—supports up to 10 lockout
stations
Window for viewing status indicator
lights; Sealed for tamper-resistance
Safety Mats,
Light Curtains,
E-Stop Stations,
Proximity Switches,
Photo Switches
+10%, -15% of the line voltage
Expansion Module
Remote Lockout Stations without an
Expansion Module
conduit entry (removable plug in
bottom conduit hole)
UL
• allows the systems to
• allows the systems to
US
accommodate up to 24 Remote
Lockout Stations
accommodate up to 60 Remote
Lockout Stations
Listed Industrial Control Panel;

Related parts for 2032-C0023PX-25D

2032-C0023PX-25D Summary of contents

Page 1

Safety Isolation System ElectroGuard Overview The ElectroGuard Safety Isolation System is used in place of a disconnect switch for Lockout and Tagout (LOTO). It uses power contactors and Remote Lockout Stations to accomplish LOTO. Isolating the electrical energy usually involves ...

Page 2

... Lockout Stations to be used (see page 12-16 for details). • Pneumatic Isolation Module to isolate pneumatic energy (see page 12-15 for details). • Status communication to a remote PLC (see page 12-17 for details). • Fusible disconnect switch (Bulletin 2032) or thermal-magnetic circuit breaker (Bulletin 2033) to provide branch circuit protection. To Motor Controllers ...

Page 3

... IP 65 Enclosure 2032-!0023H -23B 2032-C0023W -23B 2032-!0023H -24B 2032-C0023W -24B 2032-!0023H -25B 2032-C0023W -25B ...

Page 4

... Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus Input Line Voltage Code The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below. Example: Catalogue Number 2032-C0085W -26B becomes Catalogue Number 2032-C0085WN-26B for a 380V 50Hz Input Line Voltage application. Input Line Voltage 220V 50Hz ...

Page 5

Combination Systems with Thermal-magnetic Circuit Breaker/Optional Features Product Selection for Outside of North America (see page 12-19 for Ordering Instructions) ! Bussing Designation The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below. ! ...

Page 6

... Bulletin 2032 or 2033 Systems only) e.g. Catalogue Number 2032T -A0630JB-30L becomes Catalogue Number 2032T -A0630JB-30L-2EUT to indicate a 630A Safety Isolation System that includes 2 internally installed 10 port Expansion Modules without the time delay feature. Open Type Expansion Module for Field Addition ...

Page 7

Status Communication to a remote PLC (Should be ordered with Safety Isolation System) This option provides Remote I/O via “Flex” modules. Communication can be via: • The DeviceNet communication platform, or • The Remote I/O communication platform. Note: The status ...

Page 8

Safety Isolation System ElectroGuard Typical Wiring Diagram/Wire Length Considerations Typical Wiring Diagram Safety Isolation System GC with Optional Fusible Disconnecting Means 1IC 2IC Designates Remote field Lockout connection Station(s) points Wire Length Considerations ATTENTION: ...

Page 9

The total wire length for the 5 RLS to be wired to the Control Module will be: 100ft + 400ft + 200ft + 600ft + 1,000ft = 2,300ft Per the table entitled Total Wire Length for Remote Lockout Stations on ...