G3J-T205BL-C OMRON [Omron Electronics LLC], G3J-T205BL-C Datasheet

no-image

G3J-T205BL-C

Manufacturer Part Number
G3J-T205BL-C
Description
Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output
Manufacturer
OMRON [Omron Electronics LLC]
Datasheet
New Models with AC Power Supply Input and
Monitor Output Equivalent to Non-contact
SPST-NO Join the G3J-T Series
• Limiting the starting current saves energy.
• Certified for UL and CSA.
• Mounts with screws or to DIN Track.
• Compact design with heat sinks (3.7-kW models: 100 × 100 ×
• Built-in snubber circuit and thyristor.
• Built-in operation indicator.
Appearance
Ordering Information
■ List of Models
■ Accessories (Order Separately)
Mounting Bracket
Note: Use this Bracket when mounting Thermal Relay to a G3J-series SSR.
3
Number of
R99-14 FOR G3J (See note.)
130 mm (W × H × D)).
elements
Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output
G3J-T-C
Operation indicator
Input terminals
Refer to Safety Precautions for All Solid State
Relays.
Model
Phototriac
coupler
Isolation
method
100 to 240 VAC
12 to 24 VDC
supply voltage
Rated power
No-voltage input
(open and short-
circuited input)
Input method
Output terminals (power supply side)
Monitor output terminals
Starting torque adjuster (default setting: 200%)
Ramp-up time adjuster (default setting: 1 s)
Ramp-down time adjuster (default setting: 1 s)
Output terminals (load side)
3.7 kW (17.4 A)
2.2 kW (11.1 A)
0.75 kW (4.8 A)
3.7 kW (17.4 A)
2.2 kW (11.1 A)
0.75 kW (4.8 A)
Applicable monitor capacity
(AC3)
200 to 220 VAC AC
switching
output
DC
switching
output
Monitor
output
G3J-T211BL-C AC100-240
G3J-T205BL-C AC100-240
G3J-T211BL-C DC12-24
G3J-T205BL-C DC12-24
G3J-T217BL-C AC100-240
G3J-T217BL-C DC12-24
CSM_G3J-T-C_DS_E_2_1
Model
1

Related parts for G3J-T205BL-C

G3J-T205BL-C Summary of contents

Page 1

... Applicable monitor capacity (AC3) No-voltage input 3.7 kW (17.4 A) 200 to 220 VAC AC (open and short- 2.2 kW (11.1 A) circuited input) 0.75 kW (4.8 A) 3.7 kW (17.4 A) 2.2 kW (11.1 A) 0.75 kW (4.8 A) CSM_G3J-T-C_DS_E_2_1 Monitor Model output G3J-T217BL-C AC100-240 switching G3J-T211BL-C AC100-240 output G3J-T205BL-C AC100-240 DC G3J-T217BL-C DC12-24 switching G3J-T211BL-C DC12-24 output G3J-T205BL-C DC12-24 1 ...

Page 2

... SSR input turned ON: Maximum residual voltage between short-circuited terminals SSR input turned OFF:Maximum leakage current of 0.15 mA Relay input: For minute signals G3J-T211BL-C G3J-T205BL-C 4.8 A (at 40°C) 150 A (60 Hz, 1 cycle 57 200 to 220 VAC 0.75 kW (4.8 A) 200 to 240 VAC 4 ...

Page 3

... Three-phase, 200 to 220 V L1/R L2/S L3 NPN Tr 24 VDC 4 G3J VDC 8 T1/U T2/V T3/W Thermal Relay M Motor G3J-T-C G3J-T205BL-C Approx. 760 g (PNP transistor input) Three-phase, 200 to 220 V L1/R L2/S L3 PNP Tr 24 VDC 4 G3J VDC 8 T1/U T2/V T3/W Thermal Relay M ...

Page 4

... T1/U T2/V T3/W Thermal Relay M Motor Note: Be sure to use a fuse or non-fuse breaker to protect the G3J. Time Chart Example Reversible contactor Forward rotation signal input (output form PLC) Reversible contactor Reverse rotation signal input (output from PLC) G3J-T-C Input signal (output from PLC) ...

Page 5

... Engineering Data Load Current vs. Ambient Temperature (at Continuous Power) 20 G3J-T217BL-C 16 G3J-T211BL G3J-T205BL − 100 Ambient temperature Ta (°C) Switching Frequency Conditions (AC3/AC4/AC53-a) AC3 Class (Immediate Start) 0.3 s 6Ie (Ue, cos θ = 0.35) Ie (Ue, cos θ = 0.35) 0. Ie: Rated carry current Ue: Rated load voltage (200/400 V) ...

Page 6

... Due to the soft-stop control characteristics, the load current continues flowing even after the motor stops. Set to the optimum value according to the application. 3. The operation indicator will light synchronized with the monitor output. Dimensions Note: All units are in millimeters unless otherwise indicated. G3J-T205BL-C G3J-T211BL-C 72 54.5 107.9 Input terminals Three, M3 × ...

Page 7

... In the interest of product improvement, specifications are subject to change without notice. 15.85 44.9 37.1 4.6 dia. 50 Stating torque adjuster Ramp-up time adjuster Output terminals 5.5 Six, M4 × 8 4.6 × 5.6 7.6 Oval hole 13.2 13.2 100 max. Ramp-down time adjuster G3J-T-C Mounting Hole Dimensions Two, 4.5-dia holes 50 ±0.2 130 max. 90 ±0.2 7 ...

Page 8

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a ...