FCPS-24S6 ETC2 [List of Unclassifed Manufacturers], FCPS-24S6 Datasheet

no-image

FCPS-24S6

Manufacturer Part Number
FCPS-24S6
Description
6-Amp and 8-Amp 24-Volt Remote Power Supplies
Manufacturer
ETC2 [List of Unclassifed Manufacturers]
Datasheet
GENERAL
The FCPS-24S6 (6-amp) and FCPS-24S8 (8-amp) are com-
pact, cost-effective remote power supplies with battery charger.
The FCPS-24S6/-24S8 may be connected to any 12- or 24-
volt Fire Alarm Control Panel (FACP) or may be used as a
stand-alone supply. Primary applications include Notification
Appliance (bell) Circuit (NAC) expansion (to support ADA re-
quirements and NAC synchronization) or auxiliary power to
support 24-volt system accessories. The FCPS-24S6/-24S8
provides regulated and filtered 24 VDC power to four notifi-
cation appliance circuits configured as either four Class B (Style
Y) or Class A (Style Z, with ZNAC-4 option module). Alter-
nately, the four outputs may be configured as all non-resettable,
all resettable, or two non-resettable and two resettable. The
FCPS-24S6/-24S8 also contains a battery charger capable of
charging up to 18 AH batteries.
FEATURES
• UL-Listed NAC synchronization using System Sensor,
• Cascadable for up to ten power supplies (four for Gentex)
• Operates as a “sync follower” or as a “sync generator” (de-
• Contains two fully-isolated input/control circuits — triggered
• Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4
• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load output,
• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous out-
• Compatible with coded inputs; signals passed through.
• Optional power-supervision relay (A77-716B).
• In stand-alone mode, output power circuits may be config-
• Fully regulated and filtered power output — optimal for pow-
• Power-limiting technology meets UL power-limiting require-
• Form-C normally-closed trouble relay.
• Fully supervised power supply, battery, and NACs.
• Selectable earth fault detection.
• AC trouble report selectable for immediate or 8-hour delay.
• Works with virtually any UL 864 fire alarm control which uti-
• Requires input trigger voltage of 9.0 – 32 VDC.
• Self-contained in compact, locking cabinet — 15" (38.1 cm)
• Includes integral battery charger capable of charging up to 18
NOTIFIER® is a Honeywell company.
Wheelock, or Gentex “Commander²” appliances.
with strobe timing maintained.
fault). See note on page 2.
from FACP NAC (NAC expander mode) or jumpered per-
manently “ON” (stand-alone mode).
module) NACs.
with 3 amps maximum/circuit, in NAC expander mode (UL 864).
put in stand-alone mode (UL 1481).
ured as: resettable (reset line from FACP required), non-
resettable, or a mix of two and two.
ering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
ments.
lizes an industry-standard reverse-polarity notification cir-
cuit (including unfiltered and unregulated bell power).
high x 14.5" (36.83 cm) wide x 2.75" (6.985 cm) deep.
AH batteries. Cabinet capable of housing 7.0 AH batteries.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
July 20, 2004
• Battery charger may be disabled via DIP switch for applica-
• Fixed, clamp-type terminal blocks accommodate up to 12
STANDARDS and CODES
The FCPS-24S6/-24S8 complies with the following standards:
• NFPA 72 National Fire Alarm Code.
• UL 864 Standard for Control Units for Fire Alarm Systems
• UL 1481 Power Supplies for Fire Alarm Systems (stand-
SPECIFICATIONS
Primary (AC) power:
• FCPS-24S6/-24S8: 120 VAC, 60 Hz, 3.2 A maximum.
• Wire size: minimum #14 AWG (2.0 mm²) with 600 V insulation.
Control input circuit:
• Trigger input voltage: 9 to 32 VDC.
• Trigger current: 2.0 mA (16 – 32 V). Per input: 1.0 mA (9 –
Trouble contact rating: 5 amps at 24 VDC.
tions requiring larger batteries.
AWG (3.1 mm²) wire.
(NAC expander mode).
alone mode).
16 V).
S635
FCPS-24S6
24-Volt Remote Power Supplies
6-Amp and 8-Amp
Section: Power Supplies
and
DN-6927 • 07/20/04 — Page 1 of 3
FCPS-24S8
MEA
DN-6927 • E-30
California
State Fire
Marshal
7315-0028:225
299-02-E

Related parts for FCPS-24S6

FCPS-24S6 Summary of contents

Page 1

... GENERAL The FCPS-24S6 (6-amp) and FCPS-24S8 (8-amp) are com- pact, cost-effective remote power supplies with battery charger. The FCPS-24S6/-24S8 may be connected to any 12- or 24- volt Fire Alarm Control Panel (FACP) or may be used as a stand-alone supply. Primary applications include Notification Appliance (bell) Circuit (NAC) expansion (to support ADA re- quirements and NAC synchronization) or auxiliary power to support 24-volt system accessories ...

Page 2

... NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS-24S6/-24S8 can track (i.e., “follow”) the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attached to the FCPS ...

Page 3

DN-6927 • 07/20/04 — Page ...

Related keywords