SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ALARM
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
BATTERY CUT OFF
AC OK
BATTERY LOW
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
OUTPUT NUMBER
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
100W Single Output with Battery Charger(UPS Function)
Note.5
Note.3
Note.6
Note.2
PSC-100A
CH1
13.8V
4.75A
0 ~ 7A
100W
100mVp-p
CH1: 12 ~ 15V
2400ms, 30ms/230VAC
40ms/230VAC
90 ~ 264VAC
47 ~ 63Hz
2A/115VAC
COLD START 35A/115VAC
<1mA / 240VAC
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
CH1:14.49 ~ 18.63V
Protection type : Shut down o/p voltage, re-power on to recover
10 0.5V
Relay contact output, ON : AC OK ; OFF : AC Fail ; Max. rating : 30V / 1A
Relay contact output, OFF : Battery OK ; ON : Battery Low ; Max. rating : 30V / 1A
Battery low voltage : < 11V
-20 ~ +70
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
417.6K hrs min.
PCB:127*76.2*31mm (L*W*H) ; with optional CASE:130*85*37mm (L*W*H)
PCB:0.23Kg; 63pcs/15.5Kg/1.35CUFT ; with optional CASE:0.44Kg;32pcs/15Kg/0.64CUFT
86%
1.0%
0.5%
0.5%
0.03%/
(0~50 ) on CH1 output
(Refer to output load derating curve)
1.2A/230VAC
I/P-FG:1.5KVAC
127 ~ 370VDC
MIL-HDBK-217F (25 )
16ms/115VAC at full load
2400ms, 30ms/115VAC at full load
CH2
13.8V
2.5A
--------
--------
--------
--------
--------
70A/230VAC
O/P-FG:0.5KVAC
PSC-100B
CH1
27.6V
2.4A
0 ~ 3.5A
100.74W
100mVp-p
CH1: 24 ~ 29V
Battery low voltage : < 22V
88%
CH1:28.98 ~ 37.26V
20 1V
1.0%
0.5%
0.5%
P S C - 1 0 0
File Name:PSC-100-SPEC 2011-03-03
CH2
27.6V
1.25A
--------
--------
--------
--------
--------
s e r i e s

Related parts for PSC-100

PSC-100 Summary of contents

Page 1

... CH1 output I/P-FG:1.5KVAC O/P-FG:0.5KVAC MIL-HDBK-217F ( PSC-100B CH1 CH2 27.6V 27.6V 2.4A 1.25A 0 ~ 3.5A -------- 100.74W 100mVp-p -------- CH1 29V 1.0% -------- 0.5% -------- 0.5% -------- 88% CH1:28.98 ~ 37.26V 20 1V Battery low voltage : < 22V File Name:PSC-100-SPEC 2011-03- ...

Page 2

... PWM CONTROL O.V. Assignment Mating Housing Terminal AC OK JST SXH-001T-P0.6 JST XHP or equivalent or equivalent Bat. Low AC OK Bat. Low +V -V Bat. + Bat. - Battery Charger & Back up Control File Name:PSC-100-SPEC 2011-03- Unit:mm Optional cover: No. 946B-T Mylar film ...

Page 3

... INPUT VOLTAGE (VAC) 60Hz Load A : 12V B : 24V Battery AC OK (Battery low) CN3 Pin1(Pin3) R CN3 Pin2(Pin4) External voltage source (V) and resistor (R) (The max. Sink is 1A and 30V) Fig 2.2 Internal circuit (Battery Low) File Name:PSC-100-SPEC 2011-03- Ta=25 240 264 V ...