detectors are specifically designed to meet the performance
requirements of fire detection/alarm systems. The 1151 ion-
ization detector uses a state-of-the-art, dual unipolar sensing
chamber. The detector is designed to provide open area de-
tection and, when installed in a two-wire base, is compatible
with FCI fire alarm control panels. The detector’s operation
and sensitivity can be tested in place.
the same base as the System Sensor 2151photoelectronic
smoke detector, making both models interchangeable. Bases
are available for two-wire, four-wire, 120 VAC four-wire op-
eration and also with an audible sounder.
indicating that power is being applied to the detector. The
LEDs light steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.
locity of 500 FPM.
against the cover. The LED on the detector should light
within 30 seconds.
with the aid of a voltmeter and Test Kit, MOD 400R.
The System Sensor 1151 low profile ionization type smoke
The 1151 detector is of plug-in construction and plugs into
Two visible LEDs on each detector flash every ten seconds
The 1151 detector is Listed for use inside ducts up to a ve-
Functional testing is performed by placing a test magnet
Field metering of detector sensitivity may be performed
Instruments, Inc. for their use. Specifications subject to change without notice.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
Sensitivity
Operating voltage
Standby current
Operating temperature
Relative humidity
Air velocity
Construction
Diameter
Height
Weight
DESCRIPTION
APPROVALS
SPECIFICATIONS
An ISO 9001 Certified Company
1.9 %/ft. (nominal)
15 - 32 VDC peak
200 uA max. avg.
32 to 120
10 to 93 % (non-condensing)
500 feet per minute maximum
Off-white flame retardant plastic
4 inches (10.2 cm)
1.7 inches (4.2 cm)
3.6 oz. (104 g)
o
F (0 to 49
PLUG-IN SMOKE DETECTOR
LOW PROFILE, IONIZATION
Unique Dual Unipolar Sensor
Provides Exceptional Stability
Low Profile Construction
Easy plug-in of the Head to Base
Tamper-resistant Feature
Test Switch
360
Compatible with FCI Control Panels
Audible Sounder Base (Optional)
Field Metering of Detector Sensitivity
Removable Insect Screen and Cover
for Field Cleaning
Insect-resistant Screening
(.020"/.508 mm openings)
o
o
C)
SYSTEM SENSOR
View Angle Of Alarm LEDs
FEATURES
© 2003 All Rights Reserved
1151
9020-0582/Ver. 1.1

Related parts for RA-400Z

RA-400Z Summary of contents

Page 1

... Height Weight Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. 16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099 ...

Page 2

... Model Contacts 1151 B110LP B112LP Form A & C B114LP Form A, C & Supv. B401BH RA-400Z PAM-1 Form B MOD 400R MAINTENANCE Cleaning programs should be adapted to the individ- ual environment. We recommend at least an annual cleaning of the unit. The detector screen and cover as- sembly can be removed, revealing the sensing cham- ber ...