K2CM-4HA Omron, K2CM-4HA Datasheet - Page 2

no-image

K2CM-4HA

Manufacturer Part Number
K2CM-4HA
Description
RELAY MOTOR PROTECTIVE 50-160A
Manufacturer
Omron
Series
K2CMr
Datasheet

Specifications of K2CM-4HA

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
K2CM4HA
Current Reverse-phase Detection Models
Note: The manual resetting method must be used with reverse-phase detection.
■ Related Product
Transformer
Note: Use this Transformer when a voltage reverse-phase detection model is used on a 400-V line.
Specifications
■ Ratings
Other features, such as 100% overcurrent capacity and flush mounting are also available. See Model Number Legend on page 1 for details.
Note: The start-up lock timer restarts when the operating value at starting becomes less than 30% of the set current value.
Resetting
method
Manual
Automatic
(See
note.)
SE-PT400
Supply voltage of motor circuit
Supply voltage of control circuit
Insulation breakdown of output contact
Operating voltage/current of output contact
(pf = 0.4 when breaking contact)
Contact form of output contact
Operating current range of input circuit
Operating voltage range of control circuit
Operating frequency range of control circuit 95% to 105% of rated frequency
Power consumption
Overcurrent function operating value
Overcurrent function operating time setting
range
Case color
Overcurrent function operating time
characteristics
Overcurrent function resetting value
Overcurrent function start-up operating
value
Open-phase operating value
Open-phase operating time
Reverse-phase operating value
Reverse-phase operating time
Imbalance operating value
Current imbalance factor
Model
100/110/120 VAC
200/220/240 VAC
400/440 VAC
100/110/120 VAC
200/220/240 VAC
400/440 VAC
Current setting range
Time specification
Operating voltage
Primary side
Secondary side
K2CM-1LS
K2CM-2LS
---
K2CM-1LSA K2CM-1LA K2CM-1MA K2CM-1HA K2CM-Q1LSA K2CM-Q1LA K2CM-Q1MA K2CM-Q1HA
K2CM-2LSA K2CM-2LA K2CM-2MA K2CM-2HA K2CM-Q2LSA K2CM-Q2LA K2CM-Q2MA K2CM-Q2HA
---
2 to 8 A
Voltage specification
200/220, 400/440 VAC, 50/60 Hz
100/110/120, 200/220/240, 400/440 VAC, 50/60 Hz
500 VAC
NO contact: 120 VAC/2 A, 240 VAC/1 A, 440 VAC/0.5 A, 110 VDC/0.2 A, 220 VDC/0.1 A
NC contact: 120 VAC/5 A, 240 VAC/2 A, 440 VAC/1 A, 110 VDC/0.2 A, 220 VDC/0.1 A
Current reverse-phase detection models: SPST-NO + SPST-NC
Voltage reverse-phase detection models: SPDT
2 to 160 A (Number of passes: 1)
85% to 110% of rated voltage, but operates normally at 50% of open-phase supply voltage
Approx. 3 VA (in standby state); 5 VA (in operating state)
115 ±10% of the setting value
Inverse Type
Inverse time both at startup and during operation:
Timer scale × 1 (s) at 600% overload
Timer scale × 3 (s) at 200% overload
Note: The above values are for a time factor setting of 1.
Instantaneous Type
Fixed time at starting (start-up lock)
• Time setting value (varies between 2 and 40 s) at 140% overload and starting
Instantaneous during operation: 0.5 s max. (when current is increased from 100 to 140% of the
set current value)
Munsell 5Y7/1
Inverse type: ±10% of maximum setting value (at 600% overload)
Instantaneous type: ±20% of maximum setting value (at 140% overcurrent and at starting)
100% min. of the setting value
Inverse type: Not applicable
Instantaneous type: 30% max. of the setting value (See note.)
85% max. of the set current value (at open-phase)
2 s max. (at overcurrent operating value)
50% max. of the current value (80% max. of the operating voltage)
1 s max. (at overcurrent operating value)
85% of the set current value
High: 35 ±10%; Low: 60% min. (at overcurrent operating value)
K2CM-1L
K2CM-2L
K2CM-4L
K2CM-4LA K2CM-4MA K2CM-4HA ---
380 to 480 V (wide power supply range) 7VA
190 to 240 V (wide power supply range)
where
8 to 26 A
Imbalance factor = Reverse phase portion
Inverse type
K2CM-1M
K2CM-2M
K2CM-4M
20 to 65 A 50 to 160 A
Normal phase portion
K2CM-1H
K2CM-2H
K2CM-4H
K2CM-Q1LS
K2CM-Q2LS
---
2 to 8 A
Secondary power
consumption
× 100 (%)
K2CM-Q1L
K2CM-Q2L
K2CM-Q4L
K2CM-Q4LA K2CM-Q4MA K2CM-Q4HA
8 to 26 A
Instantaneous type
K2CM-Q1M
K2CM-Q2M
K2CM-Q4M
20 to 65 A
K2CM
K2CM-Q1H
K2CM-Q2H
K2CM-Q4H
50 to 160 A
2