S8VS-06024A Omron, S8VS-06024A Datasheet - Page 17

POWER SUPPLY W/DISP 24VDC 2.5A

S8VS-06024A

Manufacturer Part Number
S8VS-06024A
Description
POWER SUPPLY W/DISP 24VDC 2.5A
Manufacturer
Omron
Series
S8VSr
Datasheets

Specifications of S8VS-06024A

Power Supply Type
Switching (Closed Frame)
Voltage - Output
24V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Voltage - Input
85 ~ 264VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 2.5A
Size / Dimension
4.26" L x 1.57" W x 3.74" H (108.3mm x 40mm x 95mm)
Power (watts) - Rated
60W
Operating Temperature
-10°C ~ 60°C
Efficiency
78%
Approvals
CE, CSA, cUL, EN, UL, VDE
Product
Switching
Output Power Rating
60 W
Output Voltage (channel 1)
24 V
Output Current (channel 1)
2.5 A
Dimensions
108.3 mm L x 40 mm W x 95 mm H
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
2.5A
Power Rating
60W
Input Voltage
85V AC To 264V AC
Length
108.3mm
Width
40mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8VS06024A
Z1665
480-W Models
Standard Model
S8VS-48024
Models with Indication Monitor
S8VS-48024@
* The terminal arrangement is the same for models with screwless
Note: The illustration shows the S8VS-48024A model.
terminal blocks and standard models.
10
16
15
9
1
1
14
13
12
11
2
2
3
3
6
7
8
4
5
4
5
*1. The fuse is located on the (L) side. It is NOT user replaceable.
*2. This is the protective earth terminal specified in the safety standards.
*3. S8VS-48024A/B only.
*4. S8VS-48024A only.
*5. S8VS-48024B only.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15,
16
Always ground this terminal.
AC Input terminals
(L), (N)
Protective Earth
terminal (PE)
DC Output terminals
(−V), (+V)
Output indicator
(DC ON: Green)
Output voltage adjuster
(V.ADJ)
Main display (Red) *3
Operation
indicator
(Orange) *3
Mode Key *3
Up Key *3
Down Key *3
Alarm
outputs
*3
NC (Not connected)
Name
Undervoltage
output terminal
(DC Low)
(Emitter side)
Undervoltage
output terminal
(DC Low)
(Collector side)
Maintenance
Forecast
output terminal
(Yrs) *4
(Emitter side)
Total run time
output terminal
(kh) *5
(Emitter side)
Maintenance
Forecast
output terminal
(Yrs) *4
(Collector side)
Total run time
output terminal
(kh) *5
(Collector side)
V
A
Apk
Yrs
kh
Connect the input lines to these
terminals. *1
Connect the ground line to this
terminal. *2
Connect the load lines to these
terminals.
Lights while a direct current (DC)
output is ON.
Use to adjust the voltage.
Indicates the measurement or set
value.
Lights up when the output voltage is
indicated. Blinks during setup of
undervoltage alarm value.
Lights up during indication of output
current.
Lights up during indication of peak
hold current.
Lights up during indication of
maintenance forecast monitor.
Blinks during setup of maintenance
forecast monitor setting. (S8VS-
48024A)
Lights up during indication of total
run time monitor. Blinks during setup
of total run time monitor. (S8VS-
48024B)
Use the Mode Key to change the
indicated parameter or reset the
peak hold current value.
Use the Up Key to change to the
setting mode or to increase the set
value.
Use the Down Key to change to the
setting mode or to decrease the set
value.
Output when a drop is detected in
the output voltage (voltage drop =
transistor OFF).
Output when the set value for
maintenance is reached (transistor
OFF).
Output when the set value for total
run time is reached (transistor OFF).
Output when the set value for
maintenance is reached (transistor
OFF).
Output when the set value for total
run time is reached (transistor OFF).
Function
S8VS
17