S8VS-18024AP Omron, S8VS-18024AP Datasheet - Page 4

POWER SPPLY SWITCH 24V 180W 7.5A

S8VS-18024AP

Manufacturer Part Number
S8VS-18024AP
Description
POWER SPPLY SWITCH 24V 180W 7.5A
Manufacturer
Omron
Series
S8VSr
Datasheet

Specifications of S8VS-18024AP

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
180W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 264VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 7.5A
Size / Dimension
4.93" L x 2.95" W x 4.53" H (125.3mm x 75mm x 115mm)
Power (watts) - Rated
180W
Operating Temperature
-10°C ~ 60°C
Efficiency
80%
Approvals
CE, CSA, cUL, EN, UL, VDE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8VS18024AP
Specifications
Ratings/Characteristics
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
*2. For a cold start at 25°C. Refer to Engineering Data (15-W, 30-W Models) on page 14 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
*4. The overvoltage protection of the S8VS-015 @@ uses a zener diode clamp. If the internal feedback circuit is destroyed by any chance, the load
*5. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
Item
Efficiency (typical)
(rated input voltage)
Input
Output
Additional
functions
Other
temperature of the Power Supply may result in ignition or burning.
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
may be destroyed by the clamped output voltage (approx. 140% to 190% of the rated output voltage).
Voltage *1
Frequency *1
Current
Power factor
Harmonic current regulation
Leakage current
Inrush current *2
Voltage adjustment range *3
Ripple
Input variation influence
Load variation influence
(rated input voltage)
Temperature variation influence
Startup time *2
Hold time *2
Overload protection *2
Overvoltage protection *2
Output voltage indication
Output current indication
Peak-hold current indication
Maintenance forecast monitor indication
Maintenance forecast monitor output
Total run time monitor indication
Total run time monitor output
Undervoltage alarm indication
Undervoltage alarm output
Parallel operation
Series operation
Operating ambient temperature
Storage temperature
Operating ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
EMI
EMS
Approved standards
SEMI
Weight
5-V models
12-V models
24-V models
With 100-VAC input
With 200-VAC input
With 100-VAC input
With 200-VAC input
With 100-VAC input
With 200-VAC input
Conducted
Emissions
Radiated Emissions
Power ratings
Type
72% min.
74% min.
77% min.
100 to 240 VAC (allowable range: 85 to 264 VAC)
50/60 Hz (47 to 450 Hz)
0.45 A max.
0.25 A max.
---
Conforms to EN61000-3-2
0.5 mA max.
1.0 mA max.
25 A max.
50 A max.
−10% to 15% (with V.ADJ)
2.0% (p-p) max. (at rated input/output voltage)
0.5% max. (at 85- to 264-VAC input, 100% load)
2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load)
0.05%/°C max.
100 ms max. (at rated input/output voltage)
20 ms min. (at rated input/output voltage)
105% to 160% of rated load current, inward-sloping voltage
drop, automatic reset
Yes (a zener diode clamp) *4
No
No
No
No
No
No
No
Yes (color: red)
No
No
Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)
Models with 5- or 12-V output: Not possible
Refer to the derating curve in Engineering Data (15-W, 30-W Models). (with no icing or condensation)
−25 to 65°C
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s
Yes (color: green)
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B
Conforms to EN61204-3 high severity levels
UL: UL508 (Listing; Class 2 Output: Per 1310), UL1604 (Class I/Division2), UL60950-1
cUL: CSA C22.2 No.14 (Class 2 Output), No.60950-1, No.213 (Class I/Division2)
cUR: CSA C22.2 No. No.60950-1
EN/VDE: EN50178 (=VDE0160)
F47-0706 (With 200-VAC input)
160 g max.
2
, 3 times each in ±X, ±Y, and ±Z directions
Standard
15 W
70% min.
76% min.
80% min.
0.9 A max.
0.6 A max.
1,000 ms max. (at rated input/output voltage)
105% to 160% of rated load current, inverted L voltage drop,
intermittent operation, automatic reset
Yes *5
180 g max.
Standard
30 W
S8VS
4

Related parts for S8VS-18024AP