Specifications of S82Y-J10F

Accessory Type
Mounting Bracket(s)
For Use With/related Products
S82J 100W Power Supplies
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YJ10F
Switching the AC Input Voltage
between 100 and 200 V (300- and 600-W
Models)
The input voltage can be switched between 100 and 200 V by
shorting or opening the input voltage selection terminals. Set the
required voltage as shown below. (The voltage is factory-set to
200 V.)
Note: A 300-W Model is shown above.
Series Operation
Only models with power ratings of 50, 100 (-5, -12, -15, 24-output),
150, 300, or 600-W allow series operation.
Up to two of the above Power Supplies can be used in series
operation. Models other than the above Power Supplies cannot be
used in series operation.
If series operation is attempted for other models, the output from one
of the Power Supplies may not come ON when the AC input is
applied. If that occurs and the Power Supplies are left in that state,
internal circuits may be damaged.
Although Power Supplies having different output capacities and
different output voltages can be connected in series, the current
flowing through the load must not exceed the smaller rated output
current.
With the S82J-05024@@ or S82J-10024@@, if the load is shorted a
reverse voltage may result in the Power Supply causing deterioration
and damage. It is recommended that diodes are connected as
shown in the previous diagram (D
S82J
Model
Short with the short bar.
Type
Dielectric strength
Forward current (I
(V
RRM
100 W
50, 150, 300, 600 W
100-V input
L
VOLTAGE SELECT
N
SHORT 100-120V
OMRON Corporation
OPEN 200-230V
SHORT BAR
MADE IN JAPAN
)
Output capacity
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
F
INPUT
INPUT
)
1
In the interest of product improvement, specifications are subject to change without notice.
+V
+V
−V
−V
, D
Schottky barrier diode
Twice the rated output voltage or
above
Twice the rated output current or
above
2
).
and leave the terminals open.
5, 12, 15, 24 VDC
24 VDC
Remove the short bar
D
D
Rated output voltage
1
2
200-V input
L
VOLTAGE SELECT
OMRON Corporation
N
SHORT 100-120V
OPEN 200-230V
SHORT BAR
V
V
V
L
1
2
MADE IN JAPAN
=
V
V
L
1
+
V
2
Parallel Operation
Only 300- and 600-W models can be in parallel operation. Do not
operate any other models in parallel. The output of the models in
parallel operation is a maximum of 80% of the rated output.
Set the parallel operation selector to PARALLEL if the Units are in
parallel operation and make sure that the thickness and the length of
all wires connected to the load are the same to ensure that the wires
will have no voltage drop differences.
If you adjust the voltage using the output voltage adjuster (V.ADJ),
adjust the output voltage from both Power Supplies.
Fan Replacement
The service life of the fan is approximately 50,000 hours (at 25°C).
The service life varies, however, depending on the ambient
temperature or other surrounding environmental conditions such as
dust. As a preventive maintenance measure, replace the fan within
approx. two years if it is used at an ambient temperature of 40°C.
Fans are available as replacements.
Fan Set:
Fan (above), four M4 x 35 sems screws, instruction sheet, and
packing case
Replace the fan as shown in the following illustration.
Model: S82Y-JFAN