70-OAC5A Grayhill Inc, 70-OAC5A Datasheet

I/O MODULE 240VAC 3.5A STD

70-OAC5A

Manufacturer Part Number
70-OAC5A
Description
I/O MODULE 240VAC 3.5A STD
Manufacturer
Grayhill Inc
Series
70r
Type
ACr
Datasheets

Specifications of 70-OAC5A

Turn Off Time
8.33ms
Turn On Time
8.33ms
Color
Black
Style
Standard
Voltage - Input
5VDC (2.5 ~ 10VDC)
Current - Input
16mA
Voltage - Output
24 ~ 280VAC (240VAC Nom)
Current - Output
0.03 ~ 3.5A
Features
Hold Down Screw
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Peak Surge Current
80A
No. Of Analog Outputs
1
Output Current Max
3.5A
Signal Input Type
2.5 To 10VDC
Connection To Host
Board Mount
Current, Input
16 mA
Current, Leakage
4 mA (RMS)
Module Type
Digital
Number Of Channels
1
Output
24 to 280 VAC
Output Type
Analog
Output, Range
24 to 280 VAC
Power Dissipation
1.0 W⁄A (Typ.)
Primary Type
Control
Resistance, Input
240 Ohms
Resistance, Insulation
100 Megohms (Min.) @ 500 VDC
Special Features
Optical Isolation
Standards
UL Listed, CSA Certified, and CE Marking
Temperature, Operating
-40 to +100 °C
Time, Turn-off
8.33 ms (Max.)
Time, Turn-on
8.33 ms (Max.)
Voltage, Isolation
4000 VAC
Voltage, Operating
240 VAC
Voltage, Supply
5 VDC
Contact Configuration
SPST-NO
No. Of Analog Inputs
1
No. Of Outputs
1
Output Current Min
0.03A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant, Contains lead / RoHS compliant by exemption
Other names
GH7413
PART NUMBER EXPLANATION: Digital I/O Modules
L-3
I/O MODULES
Our line of pluggable input and output modules
provide a low cost, versatile method for
interconnecting real world analog and digital
signals to data acquisition, monitoring, or control
systems. All modules provide an optically
i s o l a t e d b a r r i e r b e t w e e n s e n s i t i v e
microprocessor or digital logic circuits and
field power devices.
In the G5 and OpenLine
and digital I/O modules are available with the
same pin-out. This gives the flexibility of mixing
and matching module types on the same
mounting rack or base; making them perfect
in applications which require interface to a
variety of different sensors and loads.
The case color of the single point modules
identify their function. The industry standard
for single point I/O module case colors is:
DIGITAL OUTPUT MODULES
Digital output modules are used to switch AC
and DC loads such as solenoids, motors, or
lamps from logic signal levels. Their inputs are
directly compatible with TTL or CMOS interface
circuitry.
AC output modules have zero voltage turn-on
of the load to greatly reduce generated EMI
and RFI. They are highly immune to electrical
Digital AC Output Module = Black Case
Digital DC Output Module = Red Case
Digital AC Input Module = Yellow Case
Digital DC Input Module = White Case
70M-ODC5A
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
®
Digital I/O Module Engineering Information
packages, analog
Module Type
Function
Suffix
Logic Supply Voltage or Range
70
70G = Digital Module, G5 Package
70L = Digital Module, OpenLine
70M = Digital Module, Mini Package
OAC = Digital Output AC
ODC = Digital Output DC
IAC = Digital Input AC
IDC = Digital Input DC
AC Inputs:
DC Inputs:
AC Outputs:
DC Outputs: Blank = 3-60 Vdc Fast
Digital Modules:
Analog Modules:
= Digital Module, Standard Package
transients, and have built-in RC snubber
networks for increased capability with inductive
loads.
DC output modules can operate DC loads over
a wide voltage range and have built-in voltage
spike protection.
DIGITAL INPUT MODULES
Digital input modules are used to monitor the
status of a load or a sensor (such as a limit
switch, pressure switch, or temperature
switch). The output of these modules is a logic
level signal which corresponds to the status of
the device being monitored. A high level output
signal indicates the load is off (the switch is
open). A low level output signal indicates the
load is on (the switch is closed). Input modules
are designed to give fast, clean switching by
providing filtering and hysteresis.
Input and output modules are compatible in
that the output of one can drive the input of the
other.
UL, CSA AND CE APPROVALS
As one of the world's leading manufacturers of
I/O modules, we strive to assure that our
products comply with all of the applicable
international standards. In doing so, we believe
your products will also be readily accepted and
easily certified. All modules shown in this
section have been tested to UL Standard 508
and are documented in UL file number E58632.
Similarly, they have been tested to CSA
Blank = 120 Vac
Blank = 3-32 Vdc
G = 35-60 Vac/Vdc
L = Inductive loads
Blank = 120 Vac
MA
AMA = 240 Vac, Manual Override
MA = 3-60 Vdc, Manual Override
= 120 Vac, Manual Override A-5 = Normally Closed
Blank = 4.5-28 Vdc (OpenLine
5 Vdc, 15 Vdc, 24 Vdc = Logic Supply Voltage (Standard, Mini, G5)
4.75-5.25 Vdc
®
Package
A = 220 Vac
B = Fast Switching
D =2.5–28 Vdc
S = Dry Contacts
A = 220 Vac
A = 4-200 Vdc R = Dry Contact
B = 3-60 Vdc, Low Leakage
®
)
Standard 22.2 No. 14-95M and are documented
in CSA file LR38763. Additionally, OpenLine
modules were tested and passed CSA 22.2
No. 213-M1987 Class I, Div. 2 Groups A, B, C
and D. Parts bearing the CE logo indicate
conformance with EN50082-2 and EN50081-2
(89/336/EEC EMC directive) as well as EN60950
(61010-1) for the low voltage directive. Contact
Grayhill for copies of our Declaration of
Conformity or visit out website. Parts bearing
the TÜV logo indicate that they were the agency
which performed the EN60950 evaluation.
CONSTRUCTION AND LIFETIME
WARRANTY
All of our I/O modules are hard potted with
thermally conductive epoxy to withstand harsh
industrial environments. The modules provide
optical isolation, immunity to mechanical shock
and vibration, and operate over a wide
temperature range. The module cases are a
solvent resistant thermoplastic which meets
UL94-V-0 rating. The terminal pins are a tin-
plated copper wire. Component selection and
surface mount construction allow low operating
junction temperatures for long life. Superior
design, rigorous testing, and field data give us
the confidence to back our I/O modules with
the industry's first lifetime warranty.
I/O MODULE WIRING
Analog and digital modules can be placed at
any I/O location, however, to minimize the
possibility of crosstalk and noise pickup it is a
good practice to group similar module types
together. 14 or 16 gauge wire is typically used
to wire the field devices to the I/O rack terminal
block.
NP = 15-32 Vac/10-32 Vdc
K = 2.5-16 Vdc
A-11 = Non-Zero Cross
®

Related parts for 70-OAC5A

70-OAC5A Summary of contents

Page 1

... DC Outputs: Blank = 3-60 Vdc Fast Logic Supply Voltage or Range L-3 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com transients, and have built-in RC snubber networks for increased capability with inductive loads ...

Page 2

... Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com Digital I/O Modules Engineering Information FUSE HOLDERS (OUTPUTS ONLY) .34 (8,64) .10 .22 ...

Page 3

... DIGITAL DC INPUT DIGITAL CONTACT CLOSURE L-5 Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com Miniature Module 4–40 X 1-1/2" PHILLIPS HOLD- DOWN SCREW INCLUDED WITH EACH MODULE MAXIMUM TORQUE = 5 FT-LB 1.70 (43,2) Ø ...

Page 4

... Digital AC Input Digital DC Input Test Digital I/O Modules Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com Digital I/O Module Selection Chart Standard Compatible Industry Size Load Control Vcc 120 Vac ...

Related keywords