MKS3PIN-5 AC120 Omron, MKS3PIN-5 AC120 Datasheet - Page 4

RELAY 3PDT 120VAC POWER MKS SER

MKS3PIN-5 AC120

Manufacturer Part Number
MKS3PIN-5 AC120
Description
RELAY 3PDT 120VAC POWER MKS SER
Manufacturer
Omron
Series
MK-Sr
Datasheet

Specifications of MKS3PIN-5 AC120

Relay Type
General Purpose
Contact Form
3PDT (3 Form C)
Contact Rating (current)
10A
Switching Voltage
250VAC, 250VDC - Max
Coil Type
Standard
Coil Current
19.3mA
Coil Voltage
120VAC
Turn On Voltage (max)
96 VAC
Turn Off Voltage (min)
36 VAC
Mounting Type
Socket
Termination Style
11 Pin Socketable
Circuit
3PDT (3 Form C)
Contact Rating @ Voltage
10A @ 250VAC
Control On Voltage (max)
96 VAC
Control Off Voltage (min)
36 VAC
Coil Voltage Vac Nom
120V
Contact Current Max
10A
Contact Voltage Ac Nom
250V
Contact Voltage Dc Nom
30V
Coil Resistance
1130ohm
Contact Configuration
3PDT
Mounting Style
Socket
Contact Material
Silver Nickel Indium
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
MKS3PIN5AC120
Z3037
■ Characteristics
Note: 1. The values given above are initial values.
■ Approved Standards
UL Recognized (File No. E41515) - - Ambient Temp. = 40°C
Note: 10A UL ratings are with no load on the other contact set.
CSA Certified by
Engineering Data
■ Reference Data
Maximum Switching Power
280
Contact resistance
Operate time
Release time
Max. operating frequency
Insulation resistance
Dielectric strength
Insulation method
Impulse withstand voltage
Pollution degree
Rated insulation voltage
Vibration resistance
Shock resistance
Life expectancy
Min. permissible load
Ambient temperature
Ambient humidity
Weight
Coil ratings
6 to 110 VDC
6 to 240 VAC
2. Ambient temperature of models with LED indicator is −25 to 60°C.
N.O.
contact
N.C.
contact
General Purpose Relays
100
50
30
10
5
3
1
10
DC resistive
DC resistive load
NC contact
with NO contact
load with
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
Contact ratings
30
50
AC resistive load
with NC contact
100
AC resistive load
with NO contact
100 mΩ max.
AC: 20 ms max.
DC: 30 ms max.
20 ms max.(40 ms max. for built-in diode models)
Mechanical: 18,000 operations/hr (no load)
Electrical:1,800 operations/hr (at rated load)
100 MΩ min. (at 500 VDC)
2,500 VAC 50/60 Hz for 1 min. between coil and contacts
1,000 VAC 50/60 Hz for 1 min. between contacts of same polarity and terminals of the same polarity
2,500 VAC 50/60 Hz for 1 min. between current-carrying parts, non-current-carrying parts, and opposite
polarity
Basic insulation
4.5 kV between coil and contacts (with 1.2 × 50 μs impulse wave)
3.0 kV between contacts of different polarity (with 1.2 × 50 μs impulse wave)
3
250 V
Destruction:10 to 55 Hz, 1.5 mm double amplitude
Malfunction:10 to 55 Hz, 1.0 mm double amplitude
Destruction:1,000 m/s
Malfunction:100 m/s
Mechanical: 5,000,000 operations min.
Electrical:100,000 operations min.
10 mA at 1 VDC P level: λ
Operating: –40 to 60°C (with no icing or condensation)
Operating: 5% to 85%
Approx. 90 g
Switching voltage (V)
300
AC inductive
load
(p.f. = 0.4)
500 1.000
MKS
Operations
100,000
100,000
2
(approx. 10 G)
2
(approx. 100 G)
60
=0.1 x 10
IEC Standard/TUV Certification: IEC61810-1
(Certification No. R50104853)
Note: Maximum carrying current per TUV Certification is 9 A when
Rated Carry Current vs. Ambient Rated Temperature
Note: The lower limit of the ambient operating temperature for models
Coil ratings
6, 12, 24, 48,
100, 110 VDC
6, 12, 24, 100,
110, 200, 220,
240 VAC
-6
10
5
0
/ ops
−40
new MK-S relays are mounted in PF083A-E or PF113A-E
Sockets.
with built-in operation indicators is −25°C.
−20
UL derating curve
N.O.
contact
N.C.
contact
0
20
Ambient temperature (°C)
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
5 A, 250 V AC 50/60 Hz (Resistive)
5 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
40
Contact ratings
60
80
Operations
100,000
100,000