CSL-38-30010 Tyco Electronics, CSL-38-30010 Datasheet

no-image

CSL-38-30010

Manufacturer Part Number
CSL-38-30010
Description
RELAY SENSOR ADJ PICKUP/DROPOUT
Manufacturer
Tyco Electronics
Series
CSr
Datasheet

Specifications of CSL-38-30010

Relay Type
General Purpose
Contact Form
DPDT (2 Form C)
Contact Rating (current)
10A
Switching Voltage
120VAC
Coil Type
Standard
Coil Voltage
24VDC
Turn On Voltage (max)
Adjustable
Turn Off Voltage (min)
Adjustable
Mounting Type
Socket
Termination Style
8 Pin Socketable
Circuit
DPDT (2 Form C)
Contact Rating @ Voltage
10A @ 120VAC
Control On Voltage (max)
Adjustable
Control Off Voltage (min)
Adjustable
Contact Configuration
DPDT
Power Consumption
3W
Supply Voltage Max
32VDC
Relay Mounting
Plug In
Control Voltage Type
DC
Relay Terminals
8 Pin Octal
Carry Current
10A
Contact Rating
10 A
Supply Voltage
28 VDC
Mode Of Operation
Adjustable Pick Up, Adjustable Drop Out
Lead Free Status / RoHS Status
Lead free / RoHS non-compliant
Coil Current
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
1-1393138-6
1302
Sensing Modes
The CS can be used as an over or undervoltage sensor, depending upon
whether the load is connected to the normally closed (NC) or normally open
(NO) contacts of the sensor’s output relay.
Overvoltage sensor – The NC contacts are used. The relay remains de-
energized until an overvoltage is sensed.
Undervoltage sensor – The NO contacts are used. The relay remains en-
ergized until the voltage decreases to the preset level, where the sensor
de-energizes the relay.
Adjustable Voltage Sensor Operation
Outline Dimensions
Dimensions are shown for
reference purposes only.
NOTE 1
Adjustable Drop-out
Fixed Pick-up and
DE-ENERGIZED
.600 MAX.
ENERGIZED
HYSTERISIS
2.937 MAX.
(15.24)
2 VOLTS
RELAY
RELAY
(76.60)
NOTE 2
Note 1 – As voltage increases, the
relay will pick-up at its selected
point and remain energized while
voltage is maintained at that level or
higher.
Note 2 – As voltage decreases, af-
ter pick-up, the relay will drop-out at
its selected point.
Note 3 – Minimum hysterisis, the
voltage differential between pick-up
and drop-out, is typically 2% of
pick-up.
(14.22)
.560
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Adjustable Pick-up
and Drop-out
1.781 MAX.
(42.24)
(22.23)
.875
(30.15)
1.187
Catalog 1308242
Issued 3-03
Engineering Data
Power Requirement: Typically less than 3VA or 3W.
Duty Cycle: Continuous.
Repeatability: 1%, max.
Response Time: 10-25 ms, typ.
Internal Relay Contact Arrangement: 2 Form C (DPDT).
Internal Relay Contact Rating: 10A @ 28VDC , res., or 120VAC, 80% p.f.
Reverse Polarity Protection: On DC types.
Temperature Range: -10 C to +55 C.
Temperature Coefficient: 0.2%/ C, max.
Enclosure: Plastic dust cover.
Mounting: 8-pin octal style plug. Fits either 27E122 or 27E891 (snap-on)
Weight: 8 oz. (227g) approximately.
Ordering Information –
Distributors are more likely to stock boldface items.
Wiring Diagrams – Bottom Views
(pins numbered clockwise from keyway)
CS
Solid State Hybrid Voltage Sensor
• Close differential
• Choice of two types
• Internal 2 Form C (DPDT) output relay
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Fixed Pick-Up and Adjustable Drop-Out
Part Number
CSJ-38-71010
CSL-38-31010
Adjustable Pick-Up and Adjustable Drop-Out
Part Number
CSJ-38-70010
CSL-38-30010
CSL-38-40010
CSL-38-60010
* Actual maximum drop-out voltage is the selected pick-up voltage less the hysterisis
voltage.
File E22575
File LR15734
INPUT
– Fixed pick-up and knob adjustable drop-out
– Knob adjustable pick-up and drop-out
AC
Specifications and availability
subject to change.
series
screw terminal sockets.
Pick-Up Range Drop-Out Range*
Pick-Up
(Volts)
(Volts)
92-140
92-140
105
20-30
40-58
22
+
Drop-Out Range
INPUT
DC
(Volts)
(Volts)
90-103
90-138
90-138
16-21
18-28
38-56
-
140VAC (50/60 Hz.)
150VAC (50/60 Hz.)
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Maximum
Maximum
Voltage
Voltage
150VDC
32VDC
32VDC
60VDC
P&B

Related parts for CSL-38-30010

Related keywords