8181980000 Weidmuller, 8181980000 Datasheet - Page 89

no-image

8181980000

Manufacturer Part Number
8181980000
Description
TERM DK45 TS35 24VDC SPDT
Manufacturer
Weidmuller
Datasheets

Specifications of 8181980000

Relay Type
General Purpose
Contact Form
SPDT (1 Form C)
Contact Rating (current)
5A
Switching Voltage
250VAC
Coil Type
Standard
Coil Current
11.5mA
Coil Voltage
24VDC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Circuit
SPDT (1 Form C)
Contact Rating @ Voltage
5A @ 250VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Control On Voltage (max)
-
Control Off Voltage (min)
-
Other names
DK45/35 24VDC SPDT
• Response delay
• Response delay and
• Additive response delay
• Wiping contact with
• Wiping function
• Turn-off delay with
• Pulse generator
• Pulse generator
• Wiping contact without
• Wiping contact, additive
146
Contact
Time periods
Repeat accuracy (const. parameter)
Accuracy of indication acc. to IEC 1812-1
Input voltage
Voltage tolerance
Duty factor
Rated power consumption
Min pulse duration type
Max. reset time at
voltage interruption
Protection against voltage interruption
Contact
Contact material
Service life
Switching current
Max. switching voltage
Switching current
Voltage applied
Relay output active
Approvals
Standards
Temperature
Clearance/creepage path. acc. to IEC 664/VDE 0110
Protection category IEC 529 - Terminal block
Mounting
Installation category to IEC 664
- with ferrule
- without ferrule
Enclosure material
Weight, typ.
Schematic circuit diagram
Ordering data
Input
Output
Status indicators
Connection
Multifunctional Timers
turn-off delay
control input
control input
(begins in the zero position)
(begins in the operating position)
control input
- Storage temperature
- Operating temperature
- mechanical
- electrical
- max.
- min.
- Front
ITM
Multifunctional timer relay
ITM
changeover
0.1 s - 100 h
1 s, 10 s, 1 min
1 h, 10 h, 100 h
± 0.5%
± 10% (25 °C)
12 V…240 Vac/dc / 50...60 Hz
85 - 110% U
100 %
7 VA / 230 V~
≥ 50 ms
≤ 100 ms
> 10 ms
2 changeover
AgCdO
5 x 10
10
8 A0 / changeover contact
100 mA0
250 V0
2000 VA / 80 W
green LED
yellow LED
UL / CSA
IEC 529 / IEC 664 / IEC 801 / IEC 255
VDE 0435/ VDE 0110
–30°C...+70°C
–20°C...+60°C
4 kV
IP 20
IP 50
DIN rail 35 mm
Category III
2 x 1.5 mm
2 x 2.5 mm
110 g
self extinguishing
Type
Relay output
5
switching operations at 2000 VA resistive load
6
switching operations
2
2
N
/ 1 x 4 mm
2
Cat. No.
8362550000
Function A: Response delay
As soon as the operating voltage is
applied, the preset delay period T
begins. After time period T has expired,
output R connects the load.
Function Ac:
Response delay and turn-off delay
As soon as operating voltage has
been applied and control input Y1 has
closed, delay period T begins. After time
period T has expired, output R connects
the load (delayed response). When con-
trol input Y1 is opened, the output dis-
connects the load after the preset time
period has expired (delayed turn-off).
Function At:
Additive response delay
As soon as the operating voltage has
been applied and delay period T has
expired, output R connects the load. At
control input Y1 the contact break inter-
vals are accumulated (additive process).
As soon as the operating voltage is
switched off, the load at output R is dis-
connected.
Function B:
Wiping contact with control input
As soon as the operating voltage has
been applied, a pulse (min 50 ms) or a
voltage can be applied to control input
Y1. Output R connects the load immedi-
ately. After delay period T has expired,
output R disconnects the load.
Function Bw: Wiping function
The operating voltage must be applied.
As soon as a voltage is applied to con-
trol input Y1, output R connects the
load for the prest time T. After time peri-
od T has expired, output R disconnects
the load. As soon as the control input is
opened, output R once more connects
the load for the duration of time period
T. After time period T has expired, out-
put R disconnects the load.
Function C:
Turn-off delay with control input
As soon as the operating voltage has
been applied and control input Y1 has
been activated, output R connects the
load for an indefinite period of time.
When the control input is opened and
after the preset time period T has
expired, the output disconnects the
load.
Function D: Pulse generator
(begins in the zero position)
As soon as the operating voltage has been
applied, output R simultaneously switches the
load alternately between the zero position and
operating position for the period of the preset
time T. With this function, the cycle begins at
the zero position.
Function Di: Pulse generator
(begins in the operating position)
As soon as the operating voltage has been
applied, output R simultaneously switches the
load alternately between the zero position and
operating position for the period of the preset
time T. With this function, the cycle
begins at the operating position.
Function H:
Wiping contact without control input
As soon as the operating voltage is
applied, output R connects the load
immediately. After delay period T has
expired, output R disconnects the load.
Function Ht:
Wiping contact, additive
As soon as the operating voltage is
applied, output R connects the load
immediately. At control input Y1 the
contact break intervals are accumulated
(additive process) and when the preset
delay period has expired, output R dis-
connects the load.
U = Operating voltage
R = Output relay or load
T = Delay
Y1 = Control input