G3JA-D416B AC100-240 Omron, G3JA-D416B AC100-240 Datasheet - Page 4

no-image

G3JA-D416B AC100-240

Manufacturer Part Number
G3JA-D416B AC100-240
Description
STARTR 3PHASE HYBRD 200-480V 16A
Manufacturer
Omron
Series
G3JAr
Datasheet

Specifications of G3JA-D416B AC100-240

Circuit
3PST (3 Form A)
Output Type
AC
Load Current
16A
Voltage - Input
100 ~ 240VAC
Voltage - Load
200 ~ 480 V
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Package / Case
Module
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3JA-D416BAC100-240
G3JAD416BAC100240
Control Circuits
Note: Overvoltage category II applies when control or auxiliary contacts are connected to an SELV or PELV circuit.
Auxiliary Contacts
Note: Overvoltage category II applies when control or auxiliary contacts are connected to an SELV or PELV circuit.
Standard Functions
Vibration and Shock Resistance
Item
Rated operational voltage
Voltage range
Overvoltage category
Input onstate voltage minimum during start (A1, A2) 90 VAC max. (100 to 240 VAC), 15.2 VAC/21.6 VDC max. (24 VAC/DC)
Input onstate current, during start with the G32J-
CF64 Fan (IN1, IN2)
Input offstate voltage maximum (A1, A2)
Offstate current consumption (IN1, IN2)
Onstate current consumption, with Fan (A2)
Onstate current consumption, without Fan (A2)
Item
Rated operational voltage
Rated impulse voltage
Dielectric strength
Overvoltage category
Operating frequency
Utilization category
TB-97, -98
(overload/fault)
TB-13, -14
(normal/up-to-
speed)
Item
Start time
Soft start (initial torque)
Current limit
Soft stop time
Weight
Item
Vibration resistance Destruction
Shock resistance
Control circuit configuration
Number of contacts
Contact
Current specifications
Rated operating current
Contact switching capacity
Control circuit configuration
Number of contacts
Contact
Current specifications
Rated operating current
Contact switching capacity
Malfunction
Destruction
Malfunction
Classification
Classification
Classification
Classification
2 s, 5 s, 10 s, 15 s, 20 s, 25 s, or 30 s
15%, 25%, 35%, or 65% of locked rotor torque
150%, 250%, 350%, or 450% of full-load current
0%, 100%, 200%, or 300% of the start time
Approx. 860 g
25-m/s
10-m/s
300 m/s
150 m/s
2
2
2
2
peak, 10 to 55 to 10 Hz, 0.19-mm single amplitude
peak, 10 to 55 to 10 Hz, 0.075-mm single amplitude
(30 G)
(15 G)
250 VAC/30 VDC
---
1,500 VAC
---
50/60 Hz
D300
Electromagnetic relay
1
NO contact
AC/DC
0.6 A at 120 VAC, 0.3 A at 240 VAC
Open: 72 VA
Close: 432 VA
Electromagnetic relay
1
NO contact
AC/DC
0.6 A at 120 VAC, 0.3 A at 240 VAC
Open: 72 VA
Close: 432 VA
100 to 240 VAC 50/60 Hz, 24 VAC 50/60 Hz, 24 VDC
±10% of control voltage
---
9.8 mA at 120 VAC; 19.6 mA at 240 VAC, 7.3 mA at 24 VAC/DC
15 VAC min. (100 to 240 VAC), 3.6 VAC/5.1 VDC min. (24 VAC/VDC)
10 mA max. (IN1), 12 mA max. (IN2)
215 mA max. at 120 VAC/180 mA max. at 240 VAC, 660 mA max. at 24 VAC/800 mA
max. at 24 VDC
205 mA max. at 120 VAC/145 mA max. at 240 VAC, 580 mA max. at 24 VAC/705 mA
max. at 24 VDC
cULus (UL 508)
cULus (UL 508)
cULus (UL 508)
cULus (UL 508)
4 kV
2,000 VAC
III (See note.)
AC15
III (See note.)
IEC (EN/IEC 60947-4-2)
IEC (EN/IEC 60947-4-2)
IEC (EN/IEC 60947-4-2)
IEC (EN/IEC 60947-4-2)
G3JA-C
4