H3CR-A8E AC100-240/DC100-125 Omron, H3CR-A8E AC100-240/DC100-125 Datasheet - Page 10

RELAY ANALOG SET DPDT 8PIN

H3CR-A8E AC100-240/DC100-125

Manufacturer Part Number
H3CR-A8E AC100-240/DC100-125
Description
RELAY ANALOG SET DPDT 8PIN
Manufacturer
Omron
Series
H3CR-Ar

Specifications of H3CR-A8E AC100-240/DC100-125

Mounting Type
Socket
Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC, 100 ~ 125VDC
Termination Style
8 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Timing Range
0.05 s to 300 Hrs
Supply Voltage
100 VAC to 240 VAC, 100 VDC to 125 VDC
Accuracy
+/- 0.2 %
Current Rating (max)
5 A
Display Type
Hand Dial
Operating Temperature Range
- 10 C to + 55 C
Time Range
0.05 Sec. To 300 Hr.
Supply Voltage Ac, Min
100VAC
No. Of Timing Functions
4
Body Material
94B3297
No. Of Pins
8
Supply Voltage Ac, Max
240VAC
Load Current Rms Max
5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H3CR-A8EAC100-240/DC100-125
H3CRA8EAC100240DC100125
H3CRA8EAC100240DC100125
Q3619148
H3CR-AP
Voltage Inputs
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Note: Before making connections, refer to Safety Precautions (H3CR-
No-contact Input
(Connection to PNP open
collector output sensor)
Sensor
Voltage Input Signal Levels
12 to 24 VDC
(sensor power supply)
No-contact
input
Contact
input
Operates with PNP transistor ON
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 VDC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
1. Transistor ON
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
+
2
10
6
7
Timer
DC power
supply
Power
supply (+)
Start
Input 0V
Power
supply
(−)
Note: The input circuit is isolated from the
No-contact Input
(Connection to NPN open
collector output sensor)
Sensor
power supply circuit. Thus, an NPN
transistor can be connected.
12 to 24 VDC
(sensor power supply)
Operates with NPN transistor ON
@
+
).
10
6
7
2
DC power
supply
Timer
Power
supply (+)
Start
Input 0V
Power
supply (−)
Note: Refer to the signal levels in the
Contact Input
Operates with relay ON
following table and be aware of the
minimum applicable load of the relay.
10
6
7
2
Timer
Power
supply (+)
Start
Input 0V
Power
supply (−)
H3CR-A
10

Related parts for H3CR-A8E AC100-240/DC100-125