H5CX-A11 AC100-240 Omron, H5CX-A11 AC100-240 Datasheet - Page 30

RELAY TIMER DGTL SPDT 100/240VAC

H5CX-A11 AC100-240

Manufacturer Part Number
H5CX-A11 AC100-240
Description
RELAY TIMER DGTL SPDT 100/240VAC
Manufacturer
Omron
Series
H5CXr
Datasheet

Specifications of H5CX-A11 AC100-240

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.001 Sec ~ 9999 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC
Mounting Type
Socket
Termination Style
11 Pin Socketable
Timing Adjustment Method
DIP Switches
Timing Initiate Method
Input Voltage, Trigger Signal
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H5CX-A11-AC100-240
H5CXA11AC100240
Z2369
Timing Charts
Twin Timer Operation
The gate input is not included in the H5CX-L8@ models.
Self-diagnostic Function
The following displays will appear if an error occurs.
Note: This includes times when the life of the EEPROM has expired.
Sustained
Output
Sustained
Output
e1
e2
e2
Timing
diagram
Timing
diagram
Main display
Control output
Control output
Start signal
UP
DOWN
Start signal
UP
DOWN
OFF time
OFF time
ON time
ON time
OFF time
OFF time
ON time
ON time
Power
Reset
Reset
Gate
Power
Gate
0
0
0
0
Not lit
Not lit
sum
Sub-display
CPU
Memory error (RAM)
Memory error (EEP)
(See note)
Error
Output mode toff: Flicker OFF start
Output mode ton: Flicker ON start
OFF
OFF
OFF
Output status
Either press the reset key or reset the
power supply.
Reset the power supply.
Reset to the factory settings using
the reset key.
Correction method
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Start signal
input
*
**
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Start signal
input
*
**
Output
Output
Basic Operation
Power
Basic Operation
Power
Normal output operation will not be possible if the
ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).
Start signal input is disabled during timing.
Normal output operation will not be possible if the
ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).
Start signal input is disabled during timing.
**
**
Timing
OFF
Timing
ON
Timing
OFF
Timing
ON
H5CX-A/-L
No change
No change
0
Timing
OFF
Timing
ON
Set value after
reset
Timing
OFF
Timing
ON
30