5300 3M, 5300 Datasheet

Motor Splice Kit

5300

Manufacturer Part Number
5300
Description
Motor Splice Kit
Manufacturer
3M
Series
5300r
Datasheet

Specifications of 5300

Kit Contents
3 Splices, 3 Lug Covers, 3 Tubes Silicone Grease, 3 Mastic Sealing Strips
Wire Size (awg)
16-12
Insulator Material
EPDM Rubber
Accessory Type
Motor Splice Kit
Insulator Color
Black
Rohs Compliant
Yes
For Use With
Motor Leads Terminated With Compression Lugs
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
5300-02-RC
Manufacturer:
BOURNS/伯恩斯
Quantity:
20 000
Part Number:
5300-03-RC
Manufacturer:
BOURNS/伯恩斯
Quantity:
20 000
Part Number:
5300-04-RC
Manufacturer:
BOURNS/伯恩斯
Quantity:
20 000
Part Number:
5300-05-RC
Manufacturer:
BOURNS/伯恩斯
Quantity:
20 000
Part Number:
5300-06-RC
Manufacturer:
BOURNS/伯恩斯
Quantity:
20 000
Motor Lead Pigtail Splice
for 1000 volts (or less) cables with
one-hole lugs
Instructions
Kit Contents (kit contains 3 splices):
3 Lug Covers
3 Tubes Silicone Grease
3 Mastic Sealing Strips
Kit Selection Table
* Lug cover I.D. - use when calculating kit sizing for a connection of more than two conductors (e.g. 3-way, 4-way, etc. Use of one-hole stacking
Technical Information:
For use on Non-Shielded Cables 1000 Volts
(or less) with one-hole lugs.
Cable Size Range:
Feeder: 14 AWG-4 AWG
Motor Lead: 16 AWG-4 AWG
Copper Conductors
lugs is recommended.)
Working around energized high-voltage systems may
cause serious injury or death. Installation should be
performed by personnel familiar with good safety
practice in handling high-voltage electrical equipment.
De-energize and ground all electrical systems before
installing product.
Number
CAUTION
5300
5301
Kit
Feeder
(2,5 - 4)
(6 - 16)
14 - 10
10 - 4
Cable Size Range
AWG (mm
Motor Lead
(1,5 - 2,5)
(4 - 16)
16 -12
12 - 4
2
)
Cable Insulation
O.D. Range
0.12 - 0.21
0.17 - 0.36
in. (mm)
Table 1
(3 - 5)
(4 - 9)
Pigtail Splice Kits
3M
78-8126-0998-6-A
Lug Cover*
in. (mm)
for 1000 Volts (or less)
0.45
0.70
(11)
(18)
I.D.
5300, 5301
Motor Lead
Bolt Length
in. (mm)
Maximum
(10)
(13)
3/8
1/2

5300 Summary of contents

Page 1

... De-energize and ground all electrical systems before installing product. Cable Insulation Lug Cover* ) O.D. Range in. (mm) 0. 0. Table 1 3M Pigtail Splice Kits 78-8126-0998-6-A Maximum I.D. Bolt Length in. (mm) in. (mm) 0.45 3/8 (11) (10) 0.70 1/2 (18) (13) Motor Lead ™ for 1000 Volts (or less) 5300, 5301 ...

Page 2

... Note split bolt connector is used, refer to Table 2 below for maximum split bolt size for each kit. Max. Split Kit No. Bolt Size 5300 10 AWG 5301 8 AWG Table 2 Figure 1 For Jacketed Feeder Cable Only: If jacketed feeder cable is used, remove an additional 1/4" ...

Page 3

Overwrap the mastic with wraps of vinyl tape. 4. Install lug cover. Note: The kit contains a small tube of silicone grease. Use it to lightly lubricate the mastic-vinyl wrap. This will aid in installing the ...

Page 4

... MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential regardless of the legal theory asserted ...