8910DPA33V02 SQUARE D, 8910DPA33V02 Datasheet - Page 13

CONTACTOR, 3PST-NO, 120VAC, 30A, PANEL

8910DPA33V02

Manufacturer Part Number
8910DPA33V02
Description
CONTACTOR, 3PST-NO, 120VAC, 30A, PANEL
Manufacturer
SQUARE D
Type
DPr
Datasheets

Specifications of 8910DPA33V02

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
Panel
Coil Voltage Vac Nom
120V
Relay Terminals
Screw
Contact Voltage Ac Nom
600V
Contact Current Max
30A
Mounting Type
Panel
Contact Form
3PST-NO
Current, Rating
30 A
Function
Contactor
Horsepower, Max, 1 Phase, At 115 V
2 @ 115 VAC, 5 @ 230 VAC
Horsepower, Max, 3 Phase, At 230 V
10 @ 230VAC, 15 @ 460VAC
Number Of Poles
3
Relay Type
Electro Mechanical
Voltage, Coil
120 VAC
Enclosure Type
Open
Maximum Voltage Rating
600 VAC
Phase
1-Phase
Operating Voltage
600VAC
Switching Power Ac1
5hp
Switching Power Ac3
15hp
Switching Current Ac1
40A
Switching Current Ac3
30A
Load Current Inductive
30A
Load Current Resistive
40A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Coil Voltage Codes
208-240
Volts,
60 Hz
120
277
480
600
24
Type DPR23V02
5/98
Volts,
50 Hz
110
220
440
550
24
Voltage
Code
V14
V02
V09
V04
V06
V07
Class 8965 Type DPR reversing/hoist contactors are designed for the control of motors in hoists,
overhead doors, small elevators, commercial laundry equipment, and other related products which use
reversing motors. They are rated to perform in the short periods of jogging experienced in hoist service.
The coils are designed to operate on line voltages of 85% to 110% of rated voltage, and are for
applications at 50 or 60 Hz only. Coils are easily replaced with external base removed.
Auxiliary contacts may be easily field–added to any Class 8965 reversing contactor. Type DPR
contactors accept one auxiliary contact module with up to two isolated circuits per side (two modules
per device). When auxiliary contacts are ordered separately, two modules are normally used for each
device; one for forward, one for reverse.
Approvals: UL Listed – File E42240, CCN NLDX
Reversing/Hoist Contactors – 600 Volts AC Maximum
Auxiliary Contacts Separate Module
Approximate Dimensions
f Order two replacement coils for reversing contactors.
t Voltage code must be specified to order this product. Refer to standard voltage codes listed to the left.
q For rapid operation (jogging duty), use the next larger size contactor.
j Order two modules for Type DPR, one for each side.
Poly-Phase
Poly-Phase
No. of
Poles
3-Pole
4-Pole
Description
1 N.O.
1 N.C.
1 N.O.-1 N.C.
2 N.O.
CSA Certified – File LR25490, Class 3211 04
115 V 1Ø
1
2
2
3
3
5
2
3
© 1998 Square D All Rights Reserved
3.72
95
230 V 1Ø
3.19
81
Type DPR13 through DPR43
Horsepower Ratingsq
Class 9999 Type
10
10
2
3
5
7
3
7
1
1
/
/
2
2
D10
D01
D11
D20
j
230 V 3Ø
10
15
15
25
10
3
7
7
6.87
3.37
5.87
1
1
174
Reversing Hoist, Type DPR — Class 8965
149
/
/
86
2
2
Factory Installed
460/575 V 3Ø
1 N.O. Each Side
1 N.C. Each Side
1 N.O.-1 N.C. Each Side
2 N.O. Each Side
Description
10
15
20
30
30
10
20
5
3.76
3.86
3.07
96
98
78
(Box Lugs)
(Fastons)
Open Type
DPR13t
DPR23t
DPR33t
DPR43t
DPR53t
DPR63t
DPR34t
DPR44t
Type
3.98
101
Replacement Coilf
Class 9998 Type
Form
X1010
X0101
X1111
X2020
DA1t
DA1t
DA1t
DA1t
DA2t
DA2t
DA2t
DA2t
13