LC1D09BD SQUARE D, LC1D09BD Datasheet - Page 13

no-image

LC1D09BD

Manufacturer Part Number
LC1D09BD
Description
CONTACTOR, 3PST-NO, 24VDC, 20A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D09BD

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
24V
Width
45mm
Relay Terminals
Screw Clamp
Contact Voltage Ac Max
600V
Operating Voltage
600VAC
Switching Power Ac1
1hp
Switching Power Ac3
7.5hp
Switching Current Ac1
25A
Switching Current Ac3
9A
Load Current Inductive
9A
Load Current Resistive
25A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
01/04
IEC 60529 Classification Designations — Second and Third Characteristic Numerals
Second Characteristic Numeral
Corresponds to protection of equipment against penetration of
water with harmful effects.
Conversion of NEMA Type Numbers to IEC Classification Designations
(cannot be used to convert IEC Classification Designations to NEMA Type Numbers)
NEMA Enclosure Type Number
1
2
3
3R
3S
0
1
2
3
4
5
6
7
8
Non-protected
15 cm
(6")
min
Protected against
vertical dripping water
(condensation).
Protected against dripping
water at an angle of up to
15°.
Protected against rain at an
angle of up to 60°.
Protected against splashing
water in all directions.
Protected against water jets
in all directions.
Protected against powerful
jets of water and waves.
Protected against the
effects of temporary
immersion.
Protected against the
effects of prolonged
immersion under specified
conditions.
The table below provides an equivalent conversion from NEMA Enclosure Type Numbers to IEC
Enclosure Classification Designations. The NEMA Types meet or exceed the test requirements for the
associated IEC Classifications; for this reason this table cannot be used to convert from IEC
Classifications to NEMA Types.
The comparison is based on tests specified in IEC Publication 60529, and is from NEMA Publication 250.
IEC Enclosure
Classification Designation
IP10
IP11
IP54
IP14
IP54
Additional Letter
Corresponds to protection of personnel against direct contact
with live parts.
A
B
C
D
With the back of the hand.
With the finger.
With a 2.5-mm (0.1”) diameter tool.
With a 1mm (0.04”) diameter wire.
NEMA Enclosure Type Number
4 and 4X
5
6 and 6P
12 and 12K
13
Technical Information: Degrees of Protection
©
2001-2004 Schneider Electric All Rights Reserved
Third Characteristic Numeral
Corresponds to the degree of protection against mechanical
impact. This numeral also corresponds to an external factor
classification as defined in standard NF C 15-100.
0
1
2
3
5
7
9
Non-protected
250 g (0.55 lb)
1.5 kg
(3.3 lb)
5 kg
(11 lb)
500 g
(1.1 lb)
250 g (0.55 lb)
150 g (0.33 lb)
IEC Enclosure
Classification Designation
IP56
IP52
IP67
IP52
IP54
15 cm
(6")
15 cm
(6")
40 cm
(8")
40 cm
(16")
40 cm
(8")
20 cm
(8")
Impact energy: at least
equal to 0.25 N m (external
classification factor AG1).
Impact energy: at least
equal to 0.375 N m.
Impact energy: at least
equal to 0.5 N m.
Impact energy: at least
equal to 0.5 N m.
Impact energy: at least
equal to 6 N m (external
classification factor AG3).
Impact energy: at least
equal to 20 N m (external
classification factor AG4).
13