LC1D09BD SQUARE D, LC1D09BD Datasheet - Page 30

no-image

LC1D09BD

Manufacturer Part Number
LC1D09BD
Description
CONTACTOR, 3PST-NO, 24VDC, 20A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D09BD

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
24V
Width
45mm
Relay Terminals
Screw Clamp
Contact Voltage Ac Max
600V
Operating Voltage
600VAC
Switching Power Ac1
1hp
Switching Power Ac3
7.5hp
Switching Current Ac1
25A
Switching Current Ac3
9A
Load Current Inductive
9A
Load Current Resistive
25A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Contactor Selection for Utilization Categories DC-1 to DC-5
30
©
2001-2004 Schneider Electric All Rights Reserved
Use in Category DC-1 to DC-5
The criteria for contactor selection are:
• The rated operational current Ie.
• The rated operational voltage Ve (see page 31).
• The utilization category and the time constant L/R (see page 31)
• The required electrical durability.
Maximum Operating Rate (Operating Cycles)
The following operating rate must not be exceeded: 120 operating cycles/hour at rated operational
current Ie.
Electrical Durability
Example: Series-wound motor with P = 1.5 kW, Ve = 200 V, and Ie = 7.5 A.
Use of Poles in Parallel
Electrical durability can be increased by using poles connected in parallel. With N poles connected in
parallel, the electrical durability becomes: electrical durability read from the curves x N x 0.7.
NOTE: Connecting the poles in parallel does not allow the maximum operational currents indicated on
pages 28 and 29 to be exceeded.
NOTE: Ensure that the connections are made in such a way as to equalize the currents in each pole.
0.08
0.06
0.04
0.02
0.01
0.8
0.6
0.4
0.2
0.1
10
8
6
4
2
1
0.2
0.3
Application: counter-current braking and inching (utilization category DC-5).
Select a contactor type LC1D25 or LP1D25 with 3 poles in series.
The power broken is: Pc total = 2.5 x 200 x 7.5 = 3.75 kW.
The power broken per pole is: 1.25 kW.
The electrical durability read from the curve above is
0.4 0.5 0.6
0.7
0.8
0.9
1
2
3
4
5
6
7
8
9
10
14
106 operating cycles.
16
20
24
30
32 36
Power broken per pole in kW
40 50 60 70 90
80
100
01/04