DPA53CM48 CARLO GAVAZZI, DPA53CM48 Datasheet - Page 2

PHASE MONITORING RELAY, SPDT, 480VAC

DPA53CM48

Manufacturer Part Number
DPA53CM48
Description
PHASE MONITORING RELAY, SPDT, 480VAC
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of DPA53CM48

Contact Configuration
SPDT
Phase Type
3 Phase
Power Consumption
13VA
Supply Voltage Max
480VAC
Switching Voltage Max
250VAC
Operating Time Range
100ms To 300ms
Relay Mounting
DIN Rail
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
DPA53CM48
Manufacturer:
Carlo gavazzi
Quantity:
500
Part Number:
DPA53CM48
Manufacturer:
Carlo gavazzi
Quantity:
500
Part Number:
DPA53CM48
Manufacturer:
Carlo gavazzi
Quantity:
500
DPA53
General Specifications (cont.)
Environment
Housing dimensions
Weight
Screw terminals
Approvals
CE Marking
EMC
Wiring Diagrams
Operation Diagrams
2
Example 1
Hysteresis
Set level
Power supply
Relay ON
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Tightening torque
Immunity
Emission
@ Max. voltage, 50 Hz
@ Max. voltage, 60 Hz
Relay ON
L1
L2
L3
IP 20
2
-20 to +60°C, R.H. < 95%
-20 to +50°C, R.H. < 95%
-30 to +80°C, R.H. < 95%
17.5 x 81.5 x 67 mm
Approx. 75 g
Max. 0.5 Nm
acc. to IEC 60947
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 50081-1
Min {L1, L2, L3}
Level setting
Select the proper undervolt-
age level using the knob
according to the phase-
phase voltage and the need-
ed sensitivity.
Mode of Operation
DPA53 monitors its own
3- phase power supply.
The relay operates when all
the phases are present, the
phase sequence is correct
and each phase-phase volt-
age is above the adjusted
setpoint. The relay releases
when one phase-phase volt-
age drops below the set-
point or when the phase
sequence is incorrect.
Example 2
L2
L1
L3
Specifications are subject to change without notice (08.11.04)
L3
L2
L1
Centre knob:
Setting of under level on
absolute scale.
Example 1
The relay monitors that the
power supply has the correct
phase sequence and that all
phases are present.
Example 2
The relay releases in case of
interruption of one or more
phases, provided that the
regenerated voltage does
not exceed the set voltage.
L1
L2
L3

Related parts for DPA53CM48