IM-T-11A BANNER ENGINEERING, IM-T-11A Datasheet
IM-T-11A
Specifications of IM-T-11A
Related parts for IM-T-11A
IM-T-11A Summary of contents
Page 1
... Printed in USA Models IM-T-9A and IM-T-11A Interface Modules Interface Modules for use with a Primary Safety Device • Interface Modules provide isolated safety output contacts for a primary safety device (e.g., a safety light screen or safety module) which has solid-state or hard contact outputs and external device monitoring (EDM) capability. • ...
Page 2
... ISO 13849-1 (EN954-1) Safety of Machinery – Related Parts of Control Systems: Part 1 General Principles for Design Contact: Global Engineering Documents, 15 Inverness Way East, Englewood, CO 80112-5704, Tel: 800-854-7179 IM-T-11A Energized K1 Energized (S1/S2) K1 Machine Safety IM-T-11A K2 Ch.1 Ch Energized K2 Energized (S3/S4) Applicable International Standards Banner Engineering Corp. Banner Engineering Corp. Minneapolis, MN U.S.A. Minneapolis, MN U.S.A. ...
Page 3
... Minneapolis, MN U.S.A. • • www.bannerengineering.com • Tel: 763.544.3164 www.bannerengineering.com • Tel: 763.544.3164 Primary Safety Device Requirements Interface Modules IM-T-9A and IM-T-11A are driven by one or two safety output channels of a primary safety device. For higher risk applications, the design of the primary safety device must meet OSHA/ANSI control reliability requirements (U.S. applications) or ISO/IEC/ EN Category Performance Level and SIL requirements for European applications. IM-T-..A Modules must be used only with primary safety devices which have External Device Monitoring capability (see Figures 4 through 8 and the Warning Interfacing MPCEs on page 7). ...
Page 4
... Safety Output Safety Output Machine Control 33 K2 Feedback (optional) Figure 4. Generalized hookup to a 2-channel primary safety device with two hard-contact safety outputs (FSD1 and FSD2) and two monitoring inputs 4 P/N 62822 rev. C – Interface Modules – Interface Modules 0V dc EDM1 EDM2 IM-T- ...
Page 5
... Interface Modules – Interface Modules 0V dc NOTE: Although this hookup shows model MPCE 1 IM-T-9A, the hookup for model IM-T-11A is identical MPCE1 NOTE: Although this hookup shows model MPCE 1 IM-T-9A, the hookup for model IM-T-11A is identical. 2 P/N 62822 rev ...
Page 6
... MPCE2 MPCE1 MPCE NOTE: Although this hookup shows 1 model IM-T-9A, the hookup for MPCE 2 model IM-T-11A is identical. WARNING . . . Wiring of Arc Suppressors If arc suppressors are used, they MUST be installed as shown across the coils of the machine primary control elements (MPCE1 to MPCE3). NEVER install suppressors directly across the output contacts of the Interface Module ...
Page 7
... Connection to the Machine To Be Controlled The hookup diagrams in Figures 5 through 9 show a generic connection of two safety output channels of the Interface Module to Machine Primary Control Elements MPCE1 and MPCE2. A Machine Primary Control Element is an electrically powered device, external to the Interface Module, which stops the machinery being controlled by immediately removing electrical power from the machine and (when necessary) by applying braking to dangerous motion. IM-T- Figure 9. Interface Module pinouts – Interface Modules – Interface Modules IM-T-11A P/N 62822 rev. C ...
Page 8
... Auxiliary Monitor Contact (Model IM-T-11A Only) The action of the auxiliary monitor contact, terminals 31-32, inversely "follows" the action of the safety outputs. The 31-32 auxiliary monitor contact used only for control functions that are NOT safety-related. A typical use is to communicate the status of the Safety Module output to a programmable logic controller (PLC). Many types of mechanisms are used to arrest dangerous machine motion. Examples include mechanical braking systems, clutch mechanisms, and combinations of brakes and clutches ...
Page 9
... Tel: 763.544.3164 Initial and Periodic Checkout Procedure The Interface Module can be used safely only when its operation is controlled via an appropriate primary safety device, connected to the Interface according to the wiring diagrams shown in Figures 4 through 8. The functioning of the Safety Module and the device(s) connected to it must be verified at initial installation and on a regular periodic basis to ensure proper operation (see also the machine manufacturer's recommendations) ...
Page 10
... Pollution Degree 2 Output Configuration IM-T-9A: 3 normally open output channels IM-T-11A: 2 normally open output channels and 1 normally closed auxiliary output channel. Each normally open output channel is a series connection of contacts from two forced-guided (mechanically linked) relays, K1-K2. The normally closed contact 31- parallel connection of contacts from K1-K2. Contacts: AgNi, 5 µm gold-plated Low Current Rating: The 5 µm gold-plated contacts allow the switching of low current/low voltage. In these low- power applications, multiple contacts can also be switched in series (e.g., “dry switching”). To preserve the gold plating on the contacts, do not exceed the following max ...
Page 11
... Tel: 763.544.3164 www.bannerengineering.com • Tel: 763.544.3164 22.5 mm (0.89" 84.0 mm Machine Safety (3.31") IM-T-9A Ch.1 Ch Figure 10. Interface Module enclosure dimensions Figure 11. Interface Module label (model IM-T-9A shown) – Interface Modules – Interface Modules 118.0 mm (4.65") P/N 62822 rev ...
Page 12
... Models IM-T-9A and IM-T-11A Models IM-T-9A and IM-T-11A EC Declaration of Conformity Banner Enginering Corp. 9714 Tenth Avenue North Minneapolis, MN 55441-5019 USA We herewith declare that IM-T-9A and IM-T-11A Interface Modules for industrial control are in conformity with the provisions of the Machinery Directive (Directive 98/37/EEC), and all essential Health and Safety Requirements have been met. R. Eagle / Engineering Manager Download the complete EC Declaration of Conformity as a PDF file at For more information: Corporate Headquarters Contact your local Banner Banner Engineering Corp. representative or Banner 9714 Tenth Ave. North Corporate Offices around the Mpls ...